15 Troubleshooting

Installation and operation manual

22

FWF02~05D

Fan coil units

3P443944-9T – 2023.01

2

Remove the suction grille.

Standard panel:

45°

1

Design panel:

90°

3

Remove the air filter.

4

Clean  the  suction  grille.  Wash  with  a  soft  bristle  brush,  and
water or neutral detergent. If the suction grille is very dirty, use
a  typical  kitchen  cleaner,  leave  it  on  for  10  min,  then  wash  it
with water.

5

Reattach the air filter (step 3 in reverse order).

6

Reattach the suction grille and close it (step 2 and 1 in reverse
order).

14.4

After a long stop period

E.g., at the beginning of the season.

▪ Check  and  remove  everything  that  might  be  blocking  inlet  and

outlet vents of indoor units and outdoor units.

▪ Clean air filters and casings of indoor units (see 

"14.3.1 To clean

the air filter"

 [

4

 21] and To clean the air outlet and outside panels).

14.5

Before a long stop period

E.g., at the end of the season.

▪ Let the indoor units run in fan only operation for about half a day in

order  to  dry  the  interior  of  the  units.  Refer  to  About  cooling,
heating,  fan  only,  and  automatic  operation  for  details  on  fan  only
operation.

▪ Turn off the power. The user interface display disappears.

▪ Clean air filters and casings of indoor units (see 

"14.3.1 To clean

the air filter"

 [

4

 21] and To clean the air outlet and outside panels).

14.6

After-sales service and warranty

14.6.1

Recommended maintenance and
inspection

Since  dust  collects  when  using  the  unit  for  several  years,
performance  of  the  unit  will  deteriorate  to  some  extent.  As  taking
apart and cleaning interiors of units requires technical expertise and
in  order  to  ensure  the  best  possible  maintenance  of  your  units,  we
recommend to enter into a maintenance and inspection contract on
top  of  normal  maintenance  activities.  Our  network  of  dealers  has

access  to  a  permanent  stock  of  essential  components  in  order  to
keep your unit in operation as long as possible. Contact your dealer
for more information.

When asking your dealer for an intervention, always state:

▪ The complete model name of the unit.

▪ The manufacturing number (stated on the nameplate of the unit).

▪ The installation date.

▪ The symptoms or malfunction, and details of the defect.

WARNING

Do  NOT  modify,  disassemble,  remove,  reinstall  or  repair
the unit yourself as incorrect dismantling or installation may
cause an electrical shock or fire. Contact your dealer.

14.6.2

Shortened maintenance and replacement
cycles

Shortening of "maintenance cycle" and "replacement cycle" needs to
be considered in following situations:

The unit is used in locations where:

▪ Heat and humidity fluctuate out of the ordinary.

▪ Power fluctuation is high (voltage, frequency, wave distortion, etc.)

(the  unit  cannot  be  used  if  power  fluctuation  is  outside  the
allowable range).

▪ Bumps and vibrations are frequent.

▪ Dust,  salt,  harmful  gas  or  oil  mist  such  as  sulphurous  acid  and

hydrogen sulfide may be present in the air.

▪ The machine is started and stopped frequently or operation time is

long (sites with 24 hour air-conditioning).

Recommended replacement cycle of wear parts

Component

Inspection

cycle

Maintenance cycle

(replacements and/or

repairs)

Air filter

1 year

5 years

High efficiency filter

1 year

Fuse

10 years

Pressure containing parts

In case of corrosion,

contact your local dealer.

INFORMATION

Damage due to taking apart or cleaning interiors of units by
anyone  other  than  our  authorised  dealers  may  not  be
included in the warranty.

15

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

The system MUST be repaired by a qualified service person.

Malfunction

Measure

If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does not properly work.

Turn off the main power
switch.

If water leaks from the unit.

Stop the operation.

The operation switch does not work
well.

Turn off the power.

Summary of Contents for FWF02D

Page 1: ...Installation and operation manual Fan coil units English Installation and operation manual Fan coil units FWF02D FWF03D FWF04D FWF05D...

Page 2: ...kad gaminiai bus eksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami...

Page 3: ...ed in accordance with our instructions as amended S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Com...

Page 4: ...rille 21 14 4 After a long stop period 22 14 5 Before a long stop period 22 14 6 After sales service and warranty 22 14 6 1 Recommended maintenance and inspection 22 14 6 2 Shortened maintenance and r...

Page 5: ...the terminals see the warning label for persons performing service and maintenance CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit WARNING This...

Page 6: ...the claims agent of the carrier Bring the packed unit as close as possible to its final installation position to prevent damage during transport Prepare in advance the path along which you want to bri...

Page 7: ...e sure the installation site withstands the weight and vibration of the unit Take care that in the event of a water leak water cannot cause any damage to the installation space and surroundings Choose...

Page 8: ...per part of the packing a to create ceiling opening according to the outlines specified on the paper pattern Attach paper pattern to the unit using the four screws d from the accessory set and create...

Page 9: ...ation Type a mm Standard Model BYFQ60B Design Panel BYFQ60C No valve 600 660 595 600 Factory mounted valve 652 660 652 A a a A Hang the unit from the suspension bolts then adjust the size of the openi...

Page 10: ...er keeps circulating in the unit condensation will form on the unit and water may drip NOTICE Make sure to insulate all piping Any exposed piping might cause condensation DANGER RISK OF BURNING SCALDI...

Page 11: ...wn 1 1 5 m a a Hanging bar Allowed Not allowed Condensation Take measures against condensation Insulate the complete drain piping in the building Combining drain pipes You can combine drain pipes Make...

Page 12: ...panel Make sure there is no gap between the unit body and the decoration panel Possible consequence Air might leak and cause dew drop Make sure no oil remains on the plastic parts of the decoration p...

Page 13: ...NOTICE The PCB connection of the valves is only required when the Daikin ON OFF valve kit EKWV2V3W5A EKWV3V3W5A is used Technical specifications of the valves Kvs value Max operation pressure PN bar...

Page 14: ...1 3 way on off valve kit d 3 Valve insulations e and tie wraps m 2 way on off valve kit e m 3 way on off valve kit e m 4 The actuator surface f and the end of cable g are colour coded to prevent switc...

Page 15: ...ore the earth wire is in case the power supply is pulled loose from the stress relief WARNING After finishing the electrical work confirm that each electrical component and terminal inside the electri...

Page 16: ...er supply cables WARNING Use an all pole disconnection type breaker with at least 3 mm between the contact point gaps that provides full disconnection under overvoltage category III NOTICE Precautions...

Page 17: ...part of the X1M terminal 6 Cable clamps c c 7 7 Configuration 7 1 Decorative panel setting Make the following field settings so that they correspond with the actual installation setup and with the nee...

Page 18: ...2 W O N 1 G 1 2 W O N 1 G 1 2 W O N 1 G 1 2 W O N 1 G a b c d 1 2 W O N 1 G 35 a b c d 36 45 53 8 Commissioning NOTICE Do NOT interrupt the test run 8 1 Checklist before commissioning 1 After the ins...

Page 19: ...the unit be sure the installation has been carried out correctly by an installer WARNING The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continu...

Page 20: ...ng precision instruments food plants animals or works of art CAUTION Do NOT operate the system when using a room fumigation type insecticide Chemicals could collect in the unit and endanger the health...

Page 21: ...with a soft cloth If it is difficult to remove stains use water or a neutral detergent 14 3 1 To clean the air filter When to clean the air filter Rule of thumb Clean every 6 months If the air in the...

Page 22: ...rder to keep your unit in operation as long as possible Contact your dealer for more information When asking your dealer for an intervention always state The complete model name of the unit The manufa...

Page 23: ...your installer and state the symptoms the complete model name of the unit with manufacturing number if possible and the installation date 15 1 Relocation Contact your dealer to remove and reinstall th...

Page 24: ...2 A1P C305 1 3 BLK X36A YLW BRN 1 5 MSW M1S BLK BLK BRN BLU X2M HEAT COOL BLU RED BRN BLU ORG RED 1 3 X35A 1 3 1 5 1 1 1 8 7 1 4 3 A3P H3P X4A X2A X4A 06 01 A2P X1A C1 N X3A H1P H2P L A1 CA F1U Z2C GR...

Page 25: ...X20A BLDC motor X24A Fan modulation X25A Drain pump X27A Power supply X32A Cooling valve X33A R C signal and valve X35A Electrical heater X36A Stepping motor Decoration panel X37A Heating valve X50A...

Page 26: ...ata Installation and operation manual 26 FWF02 05D Fan coil units 3P443944 9T 2023 01 62 5 82 R 1 3 92 65 5 25 50 77 641 5 29 138 700 50 77 45 68 25 22 Side views with design panel mm 620 308 5 49 55...

Page 27: ...t grejanja Total electric power input Elektrische Gesamtleistungsaufnahme Entr e lectrique totale Totaal opgenomen vermogen Potencia el ctrica de entrada total Potenza elettrica totale assorbita Entra...

Page 28: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P443944 9T 2023 01 Copyright 20...

Reviews: