14 Maintenance and service

Installation and operation manual

21

FWF02~05D
Fan coil units
3P443944-9T – 2023.01

CAUTION

Before  accessing  terminal  devices,  make  sure  to  interrupt
all power supply.

NOTICE

When  cleaning  the  heat  exchanger,  make  sure  to  remove
the  switch  box,  fan  motor,  drain  pump  and  float  switch.
Water  or  detergent  might  deteriorate  the  insulation  of
electronic  components  and  result  in  burnout  of  these
components.

WARNING

Be careful with ladders when working in high places.

14.3

Cleaning the air filter, suction
grille, air outlet and outside panels

CAUTION

Turn off the unit before cleaning the air filter, suction grille,
air outlet and outside panels.

NOTICE

▪ Do  NOT  scrub  firmly  when  washing  the  blade  with

water. 

Possible  consequence: 

The  surface  sealing

peels off.

Clean with a soft cloth. If it is difficult to remove stains, use water or
a neutral detergent.

14.3.1

To clean the air filter

When to clean the air filter

:

▪ Rule  of  thumb:  Clean  every  6  months.  If  the  air  in  the  room  is

extremely contaminated, increase the cleaning frequency.

▪ If  the  dirt  becomes  impossible  to  clean,  change  the  air  filter

(= optional equipment).

How to clean the air filter

:

NOTICE

Do  NOT  use  water  of  50°C  or  higher. 

Possible

consequence: 

Discoloration and deformation.

1

Open the suction grille.

Standard panel:

Design panel:

1

2

Remove the air filter.

Standard panel:

1

3

3

2

4

Design panel:

3

3

1

2

4

3

Clean the air filter. Use a vacuum cleaner or wash with water. If
the air filter is very dirty, use a soft brush and neutral detergent.

4

Dry the air filter in the shadow.

5

Reattach the air filter and close the suction grille.

14.3.2

To clean the suction grille

NOTICE

Do  NOT  use  water  of  50°C  or  higher. 

Possible

consequence: 

Discoloration and deformation.

1

Open the suction grille.

Summary of Contents for FWF02D

Page 1: ...Installation and operation manual Fan coil units English Installation and operation manual Fan coil units FWF02D FWF03D FWF04D FWF05D...

Page 2: ...kad gaminiai bus eksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami...

Page 3: ...ed in accordance with our instructions as amended S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Com...

Page 4: ...rille 21 14 4 After a long stop period 22 14 5 Before a long stop period 22 14 6 After sales service and warranty 22 14 6 1 Recommended maintenance and inspection 22 14 6 2 Shortened maintenance and r...

Page 5: ...the terminals see the warning label for persons performing service and maintenance CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit WARNING This...

Page 6: ...the claims agent of the carrier Bring the packed unit as close as possible to its final installation position to prevent damage during transport Prepare in advance the path along which you want to bri...

Page 7: ...e sure the installation site withstands the weight and vibration of the unit Take care that in the event of a water leak water cannot cause any damage to the installation space and surroundings Choose...

Page 8: ...per part of the packing a to create ceiling opening according to the outlines specified on the paper pattern Attach paper pattern to the unit using the four screws d from the accessory set and create...

Page 9: ...ation Type a mm Standard Model BYFQ60B Design Panel BYFQ60C No valve 600 660 595 600 Factory mounted valve 652 660 652 A a a A Hang the unit from the suspension bolts then adjust the size of the openi...

Page 10: ...er keeps circulating in the unit condensation will form on the unit and water may drip NOTICE Make sure to insulate all piping Any exposed piping might cause condensation DANGER RISK OF BURNING SCALDI...

Page 11: ...wn 1 1 5 m a a Hanging bar Allowed Not allowed Condensation Take measures against condensation Insulate the complete drain piping in the building Combining drain pipes You can combine drain pipes Make...

Page 12: ...panel Make sure there is no gap between the unit body and the decoration panel Possible consequence Air might leak and cause dew drop Make sure no oil remains on the plastic parts of the decoration p...

Page 13: ...NOTICE The PCB connection of the valves is only required when the Daikin ON OFF valve kit EKWV2V3W5A EKWV3V3W5A is used Technical specifications of the valves Kvs value Max operation pressure PN bar...

Page 14: ...1 3 way on off valve kit d 3 Valve insulations e and tie wraps m 2 way on off valve kit e m 3 way on off valve kit e m 4 The actuator surface f and the end of cable g are colour coded to prevent switc...

Page 15: ...ore the earth wire is in case the power supply is pulled loose from the stress relief WARNING After finishing the electrical work confirm that each electrical component and terminal inside the electri...

Page 16: ...er supply cables WARNING Use an all pole disconnection type breaker with at least 3 mm between the contact point gaps that provides full disconnection under overvoltage category III NOTICE Precautions...

Page 17: ...part of the X1M terminal 6 Cable clamps c c 7 7 Configuration 7 1 Decorative panel setting Make the following field settings so that they correspond with the actual installation setup and with the nee...

Page 18: ...2 W O N 1 G 1 2 W O N 1 G 1 2 W O N 1 G 1 2 W O N 1 G a b c d 1 2 W O N 1 G 35 a b c d 36 45 53 8 Commissioning NOTICE Do NOT interrupt the test run 8 1 Checklist before commissioning 1 After the ins...

Page 19: ...the unit be sure the installation has been carried out correctly by an installer WARNING The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continu...

Page 20: ...ng precision instruments food plants animals or works of art CAUTION Do NOT operate the system when using a room fumigation type insecticide Chemicals could collect in the unit and endanger the health...

Page 21: ...with a soft cloth If it is difficult to remove stains use water or a neutral detergent 14 3 1 To clean the air filter When to clean the air filter Rule of thumb Clean every 6 months If the air in the...

Page 22: ...rder to keep your unit in operation as long as possible Contact your dealer for more information When asking your dealer for an intervention always state The complete model name of the unit The manufa...

Page 23: ...your installer and state the symptoms the complete model name of the unit with manufacturing number if possible and the installation date 15 1 Relocation Contact your dealer to remove and reinstall th...

Page 24: ...2 A1P C305 1 3 BLK X36A YLW BRN 1 5 MSW M1S BLK BLK BRN BLU X2M HEAT COOL BLU RED BRN BLU ORG RED 1 3 X35A 1 3 1 5 1 1 1 8 7 1 4 3 A3P H3P X4A X2A X4A 06 01 A2P X1A C1 N X3A H1P H2P L A1 CA F1U Z2C GR...

Page 25: ...X20A BLDC motor X24A Fan modulation X25A Drain pump X27A Power supply X32A Cooling valve X33A R C signal and valve X35A Electrical heater X36A Stepping motor Decoration panel X37A Heating valve X50A...

Page 26: ...ata Installation and operation manual 26 FWF02 05D Fan coil units 3P443944 9T 2023 01 62 5 82 R 1 3 92 65 5 25 50 77 641 5 29 138 700 50 77 45 68 25 22 Side views with design panel mm 620 308 5 49 55...

Page 27: ...t grejanja Total electric power input Elektrische Gesamtleistungsaufnahme Entr e lectrique totale Totaal opgenomen vermogen Potencia el ctrica de entrada total Potenza elettrica totale assorbita Entra...

Page 28: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P443944 9T 2023 01 Copyright 20...

Reviews: