background image

13

English

Table 7

10-4 Setting air filter sign

• Remote controllers are equiped with liquid crystal dis-

play air filer signs to display the time to clean air filters.

• Change the SECOND CODE NO. according to Table 8 

depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to “01” for filter con-
tamination-light)

Table 8

10-5 Setting indoor unit number of simultaneous 

operation system

• When using in simultaneous operation system mode, 

change the SECOND CODE NO. as shown in Table 9.
(SECOND CODE NO. is factory set to “01” for Pair sys-
tem.)

Table 9

• When using in simultaneous operation system mode, 

refer to 

“Simultaneous Operation System Individual 

Setting”

 section to set master and slave units sepa-

rately.

<When using wireless remote controllers>

• When using wireless remote controllers, wireless 

remote controller address setting is necessary. Refer to 
the installation manual attached to the wireless remote 
controller for setting instructions.

10-6 Simultaneous operation system individual 

setting

It is easier if the optional remote controller is used 
when setting the slave unit.

• Perform the following procedures when setting the mas-

ter and slave unit separately.

Procedure
(1)

Change the SECOND CODE NO. to “02”, individual 
setting, so that the slave unit can be individually set. 
( Refer to Table 10 )
(SECOND CODE NO. is factory set to “01”, unified 
setting.)

Table 10

(2)

Perform field setting for the master unit.

(3)

Turn off the main power supply switch after (2).

(4)

Detach remote controller from the master unit and 
connect it to the slave unit.

(5)

Turn on the main power supply switch again, and as 
in (1), change the SECOND CODE NO. to “02”, indi-
vidual setting.

(6)

Perform field setting for the slave unit.

(7)

Turn off the main power supply switch after (6).

(8)

If there is more than one slave unit, repeat steps 4 to 
7.

(9)

Detach the remote controller from the slave unit after 
the setting, and reattach to the master unit. This is the 
end of the setting procedure.
* You do not need to rewire the remote controller from 
the master unit if the optional remote controller for 
slave unit is used.
(However, remove the wires attached to the remote 
controller terminal board of the master unit.)

10-7 CONTROL BY 2 REMOTE CONTROLLERS

(Controlling 1 indoor unit by 2 remote 
controllers)

• When using 2 remote controllers, one must be set to 

“MAIN” and the other to “SUB”.

MAIN/SUB CHANGEOVER

(1)

Insert a wedge-head screwdriver into the recess 
between the upper and lower parts of remote control-
ler and, working from the 2 positions, remove care-
fully the upper part. 

(Refer to Fig. 34)

(The remote controller PC board is attached to the 
upper part of the remote controller.)

(2)

Turn the MAIN/SUB changeover switch on one of the 
two remote controller PC board to “S”.
(Leave the switch of the other remote controller set to 
“M”.) 

(Refer to Fig. 35)

Setting

Mode No.

FIRST CODE NO. SECOND CODE NO.

4-way air 
discharge

13 (23)

1

01

3-way air 
discharge

02

2-way air 
discharge

03

Setting

Spacing time of 
display air filter 
sign (long life 
type)

Mode No.

FIRST 
CODE 
NO.

SECOND 
CODE 
NO.

Air filter con-
tamination-
light

Approx. 2500 hrs

10 (20)

0

01

Air filter con-
tamination-
heavy

Approx. 1250 hrs

02

Setting

Mode No.

FIRST CODE 
NO.

SECOND 
CODE NO.

Pair system (1 unit)

11 (21)

0

01

Simultaneous  operation 
system (2-unit)

02

Simultaneous  operation 
system (3-unit)

03

Setting

Mode No.

FIRST 

CODE NO.

SECOND 

CODE NO.

Unified setting

11 (21)

1

01

Individual setting

02

P1 P2

1 2 3

P1 P2

1 2 3

P1 P2

P1 P2

1 2 3

1 2 3

P1 P2

1 2 3

1 2 3

P1 P2

Main power supply

Main power supply

Main switch

Fuse

Fuse

Outdoor unit

Outdoor unit

Main switch

Indoor unit (Master)

Indoor unit (Master)

Indoor unit (Slave)

Indoor unit 
(Slave)

Remote controller

Remote controller

(1) (2)

(3) (7)

(4)

(8)

(5) (6)

Insert the screwdriver here and gently 
work off the upper part of remote controller.

Upper part of 
remote controller

Fig. 34

Lower part of 
remote controller

S

M

S

S

M

(Factory setting)

Fig. 35

(Only one remote controller needs to be changed 
if factory settings have remained untoched.)

Remote controller 
PC board

01_EN_3P249378-5G.fm  Page 13  Friday, January 20, 2012  2:01 PM

Summary of Contents for FUQ100BUV1B x 2

Page 1: ...RE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGV...

Page 2: ...eenkomstig de bepalingen van Richtlijnen zoals geamendeerd siguiendo las disposiciones de Directivas seg n lo enmendado secondo le prescrizioni per Direttive come da modifica de acordo com o previsto...

Page 3: ...71BV1 FHYP100BV1 FHYP125BV1 FH35BZV1 FH45BZV1 FH60BZV1 III FHQ35BUV1B FHQ50BUV1B FHQ60BUV1B FHQ71BUV1B FHQ100BUV1B FHQ125BUV1B FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B FUQ71...

Page 4: ...t and never connect additional wiring to the existing circuit An insufficient power supply capacity or improper electrical work may lead to electric shocks or fire Be sure to earth the air conditioner...

Page 5: ...here the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels 2 2 ACCESSORIES Check the following acc...

Page 6: ...rection therefore select flow direction from the below patterns Air flow patterns Refer to Fig 1 IIlustrations seen from ceiling A B C and D indicate drain pans Refrigerant pipe direction To the rear...

Page 7: ...Fig 4 and 5 Slide the locking knobs 2 on the air intake grille inward direction of arrows and lift upwards Fig 4 Fig 5 Open the air intake grille to a 45 angle and detach from the unit Detach the corn...

Page 8: ...hole in anchor for existing ceilings and a sunken insert sunken anchor or other field supplied parts for new ceilings to reinforce the ceiling to bear the weight of the unit Adjust clearance from the...

Page 9: ...ged by sliding the shutter Refer to Fig 14 CAUTION Be careful not to touch the heat exchanger fins 2 way air discharge Refer to Fig 15 NOTE Illustrations seen from ceiling Fig 15 Retainers for blockin...

Page 10: ...18 Lock the unit to the hangers on side A Hook the unit onto the other 2 hangers and lock with bottom washers and nuts 5 3 Check whether the unit is horizontally level from sides C and D both Refer t...

Page 11: ...ly ester oil or ether oil to the inside of the flare section and spin 3 4 times before screwing in Refer to Fig 22 CAUTION Do not let oil get on the screw holders on the dressing board Oil can weaken...

Page 12: ...a flared or a flanged connection Nitrogen should be set to 0 02MPa with a pressure reducing valve if brazing while inserting nitrogen into the piping Refer to Fig 25 Fig 25 7 DRAIN PIPING WORK 7 1 Ri...

Page 13: ...ing after the test run is complete Remove the control box lid and change the emergency switch above the PC board assembly of the indoor unit from NORM to EMERG Connect the single phase power supply an...

Page 14: ...wires After all the wiring connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit from outside...

Page 15: ...g ceiling height Select the SECOND CODE NO that corresponds to the ceiling height Refer to Table 5 and 6 SECOND CODE NO is factory set to 01 for a ceiling height of less than 2 7m Table 5 Table 6 10 2...

Page 16: ...the end of the setting procedure You do not need to rewire the remote controller from the master unit if the optional remote controller for slave unit is used However remove the wires attached to the...

Page 17: ...rystal display In such a case diagnose the fault contents by referning to the table on the Error code list it case of group control the unit No is displayed so that the indoor unit no with the trouble...

Page 18: ...4 Low pressure switch faulty outdoor unit H7 Outdoor fan motor position signal malfunction out door unit H9 Outdoor air thermistor faulty outdoor unit NOTE 1 J1 Pressure sensor system error batch outd...

Page 19: ...elivering the product to the customer after the test run is completed check that the control box lid the air filter and the suction grille are mounted In addition explain to the customer regarding the...

Page 20: ...NG CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 4 X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS BEING USED 5 REMOTE CONTROLLER MO...

Page 21: ...RMINAL CONNECTOR 2 FIELD WIRING 3 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 4 X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTRO...

Page 22: ...TEM SEE THE INDOOR UNIT WIRING ONLY 4 FOR THE DETAIL SEE WIRING DIAGRAM ATTACHED TO OUTDOOR UNIT 5 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTAL...

Page 23: ...1201 3P249378 5G EM11A075 HT 00_CV_3P249378 5G fm Page 2 Thursday December 8 2011 4 16 PM...

Reviews: