background image

9

English

CAUTION

For local insulation, be sure to insulate all the way to the 
pipe connections inside the machine.
Exposed piping may cause leaking or burns on contact.

6-2 For upward and rightward running pipes

• Upward and rightward running pipes are easily rigged with 

the optional connecting elbow kit.

• For upward running pipes, detach the pipe hole cover.
• Once pipes are rigged, cut the pipe hole cover to size and 

reattach. Use scissors for cutting.

(Refer to Fig. 24)

Since there exists a possibility that small animals and insects 
might get inside the indoor unit, attach the wiring through 
covers and make sure there are no gaps in the through holes 
by applying putty or insulation (procured locally.)

• When doing this, block any gaps between the piping penetra-

tion lid and the pipes using putty to prevent dust from enter-
ing the indoor unit.

CAUTION

CAUTION TO BE TAKEN WHEN BRAZING REFRIGER-
ANT PIPING

“Do not use flux when brazing refrigerant piping. Therefore, 
use the phosphor copper brazing filler metal (BCuP-2: JIS Z 
3264/B-Cu93P-710/795: ISO 3677) which does not require 
flux.”
(Flux has extremely harmful influence on refrigerant piping 
systems. For instance, if the chlorine based flux is used, it 
will cause pipe corrosion or, in particular, if the flux contains 
fluorine, it will damage the refrigerant oil.)

• Before brazing local refrigerant piping, nitrogen gas shall be 

blown through the piping to expel air from the piping.
If you brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

• When brazing the refrigerant piping, only begin brazing after 

having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant piping. Once this is done, con-
nect the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 0.02MPa with a pressure-reducing 

valve if brazing while inserting nitrogen into the piping. 

(Refer to Fig. 25)

Fig. 25

7.

DRAIN PIPING WORK

7-1 Rig drain piping (Refer to Fig. 26)

As for drain work, perform piping in such a manner that 
water can be drained properly.
As for drain piping, the connection can be made from three 
different directions.

• Employ a pipe with either the same diameter or with the 

diameter larger (excluding the raising section) than that 
of the connecting pipe (PVC pipe, nominal diameter 
20mm, outside diameter 26mm).

• Keep the drain pipe short and sloping downwards at a 

gradient of at least 1/100 to prevent air pockets from 
forming. 

(Refer to Fig. 27)

CAUTION

Water pooling in the drainage piping can cause the drain to 
clog.

• To keep the drain hose from sagging, space hanging wiring 

every 1 to 1.5m. 

(Refer to Fig. 26)

• Use only the included drain hose (1), (for rightward running 

drain hose) or elbow (9) (for upward running drain hose) and 
clamp (2).

• Fit the drain hose (1) or elbow (9) over the drain piping up to 

the neck and fasten tight with the clamp (2).

• Tighten the clamp (2) until the screw head is less than 4mm 

from the hose.

• Insulate the clamp (2) and drain hose or elbow (9) with the 

included sealing pad (8). 

(Refer to Fig. 28)

• Make sure that heat insulation work is executed on the fol-

lowing 2 spots to prevent any possible water leakage due to 
dew condensation.

• Insulate the drain hose inside the building
• Drain socket

Pipe hole cover

For liquid pipe

For gas pipe

For wiring

Fig. 24

For drain pipe

Nitrogen

Pressure-reducing valve

Hands valve

Taping

Refrigerant piping

Part to be
brazed 

Nitrogen

1 - 1.5 m

VP20

VP20

Drain hose
(Procure in field.)

Drain hose (1) (For VP20 connection)

500

Clamp (2)

Notes on upward running drain hose

Fig. 26

Ceiling slab

Hanger 
bracket

Elbow (9)

Sealing pad (8)

Min. 1/100 gradient

Rear running pipe

GOOD

WRONG

Fig. 27

Right running drain hose

01_EN_3P249378-5G.fm  Page 9  Friday, January 20, 2012  2:01 PM

Summary of Contents for FUQ100BUV1B x 2

Page 1: ...RE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGV...

Page 2: ...eenkomstig de bepalingen van Richtlijnen zoals geamendeerd siguiendo las disposiciones de Directivas seg n lo enmendado secondo le prescrizioni per Direttive come da modifica de acordo com o previsto...

Page 3: ...71BV1 FHYP100BV1 FHYP125BV1 FH35BZV1 FH45BZV1 FH60BZV1 III FHQ35BUV1B FHQ50BUV1B FHQ60BUV1B FHQ71BUV1B FHQ100BUV1B FHQ125BUV1B FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B FUQ71...

Page 4: ...t and never connect additional wiring to the existing circuit An insufficient power supply capacity or improper electrical work may lead to electric shocks or fire Be sure to earth the air conditioner...

Page 5: ...here the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels 2 2 ACCESSORIES Check the following acc...

Page 6: ...rection therefore select flow direction from the below patterns Air flow patterns Refer to Fig 1 IIlustrations seen from ceiling A B C and D indicate drain pans Refrigerant pipe direction To the rear...

Page 7: ...Fig 4 and 5 Slide the locking knobs 2 on the air intake grille inward direction of arrows and lift upwards Fig 4 Fig 5 Open the air intake grille to a 45 angle and detach from the unit Detach the corn...

Page 8: ...hole in anchor for existing ceilings and a sunken insert sunken anchor or other field supplied parts for new ceilings to reinforce the ceiling to bear the weight of the unit Adjust clearance from the...

Page 9: ...ged by sliding the shutter Refer to Fig 14 CAUTION Be careful not to touch the heat exchanger fins 2 way air discharge Refer to Fig 15 NOTE Illustrations seen from ceiling Fig 15 Retainers for blockin...

Page 10: ...18 Lock the unit to the hangers on side A Hook the unit onto the other 2 hangers and lock with bottom washers and nuts 5 3 Check whether the unit is horizontally level from sides C and D both Refer t...

Page 11: ...ly ester oil or ether oil to the inside of the flare section and spin 3 4 times before screwing in Refer to Fig 22 CAUTION Do not let oil get on the screw holders on the dressing board Oil can weaken...

Page 12: ...a flared or a flanged connection Nitrogen should be set to 0 02MPa with a pressure reducing valve if brazing while inserting nitrogen into the piping Refer to Fig 25 Fig 25 7 DRAIN PIPING WORK 7 1 Ri...

Page 13: ...ing after the test run is complete Remove the control box lid and change the emergency switch above the PC board assembly of the indoor unit from NORM to EMERG Connect the single phase power supply an...

Page 14: ...wires After all the wiring connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit from outside...

Page 15: ...g ceiling height Select the SECOND CODE NO that corresponds to the ceiling height Refer to Table 5 and 6 SECOND CODE NO is factory set to 01 for a ceiling height of less than 2 7m Table 5 Table 6 10 2...

Page 16: ...the end of the setting procedure You do not need to rewire the remote controller from the master unit if the optional remote controller for slave unit is used However remove the wires attached to the...

Page 17: ...rystal display In such a case diagnose the fault contents by referning to the table on the Error code list it case of group control the unit No is displayed so that the indoor unit no with the trouble...

Page 18: ...4 Low pressure switch faulty outdoor unit H7 Outdoor fan motor position signal malfunction out door unit H9 Outdoor air thermistor faulty outdoor unit NOTE 1 J1 Pressure sensor system error batch outd...

Page 19: ...elivering the product to the customer after the test run is completed check that the control box lid the air filter and the suction grille are mounted In addition explain to the customer regarding the...

Page 20: ...NG CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 4 X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS BEING USED 5 REMOTE CONTROLLER MO...

Page 21: ...RMINAL CONNECTOR 2 FIELD WIRING 3 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 4 X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTRO...

Page 22: ...TEM SEE THE INDOOR UNIT WIRING ONLY 4 FOR THE DETAIL SEE WIRING DIAGRAM ATTACHED TO OUTDOOR UNIT 5 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTAL...

Page 23: ...1201 3P249378 5G EM11A075 HT 00_CV_3P249378 5G fm Page 2 Thursday December 8 2011 4 16 PM...

Reviews: