background image

English

14

11. INSTALLATION OF CORNER COVER 

AND AIR INTAKE GRILLE 

• Attach the corner covers to the unit and lock in place by 

screw. (The screws are taped to the corner covers.)

• For upward or rightward running pipes, cut the corner covers 

as shown at Fig. 36 before attaching them.

(Refer to Fig. 36)

• Attach the air intake grille.
• Hook the strings to the unit to prevent the grille from drop-

ping. 

(Refer to Fig. 37)

12. TEST OPERATION

Refer to the section of “FOR THE FOLLOWING ITEMS, 
TAKE SPECIAL CARE DURING CONSTRUCTION AND 
CHECK AFTER INSTALLATION IS FINISHED”.

• After finishing the construction of refrigerant piping, drain 

piping, and electric wiring, conduct test operation accord-
ingly to protect the unit.

12-1 HOW TO TEST OPERATION

1. Open the gas side stop valve.
2. Open the liquid side stop valve.
3. Electrify crank case heater for 6 hours (Not required in 

case of a unit exclusively designed for cooling only).

4. Set to cooling operation with the remote controller and 

start operation by pushing ON/OFF button (

).

5. Press INSPECTION/TEST OPERATION button (

) 4 

times (2 times for wireless remote controller) and operate 
at Test Operation mode for 3 minutes.

6. Push AIR FLOW DIRECTION ADJUST button (

) to 

make sure the unit is in operation.

7. Press INSPECTION/TEST OPERATION button (

) and 

operate normally.

8. Confirm function of unit according to the operation man-

ual.

PRECAUTIONS

• Refer to the diagnoses below if the unit does not oper-

ate properly.

• Conduct test operation after installing AIR INTAKE 

GRILLE if the wireless remote controller is used.

• After completing the test run, press the INSPECTION/

TEST OPERATION button once to put the unit in 
inspection mode, and make sure the malfunction code 
is “00” (=normal).
If the code reads anything other than “00”, refer to the 
malfunction diagnoses below.

12-2 HOW TO DIAGNOSE FOR PROBLEMS

With the power on. Troubles can be monitored on the 
remote controller or the LED’s on the PC board of the 
indoor unit.

„

Trouble shooting with the display on the liquid crystal

   display remote controller.

1

With the wired remote controller. (NOTE 1) 
When the operation stops due to trouble, operation lamp 
flashed, and “ 

 ” and the error code are indicated on 

the liquid crystal display. In such a case, diagnose the 
fault contents by referning to the table on the Error code 
list it case of group control, the unit No. is displayed so 
that the indoor unit no with the trouble can be recog-
nized. (NOTE 2)

2

With the wireless remote controller.
(Refer also to the operation manual attached to the wire-
less remote controller)
When the operation stops due to trouble. the display on 
the indoor unit flashes. In such a case, diagnose the fault 
contents with the table on the Error code list looking for 
the error code which can be found by following proce-
dures. (NOTE 2)

(1)

Press the INSPECTION /TEST OPERATION button, 

” is displayed and  “ 0 ” flashes.

(2)

Press the PROGRAMMING TIME button and find the 
unit No. which stopped due to trouble.
Number of beeps
3 short beeps ........ Perform all the following operations
1 short beep..........Perform (3) and (6)
1 long beep ...........No trouble

(3)

Press the OPERATION MODE SELECTOR button 
and upper figure of the error code flashes.

(4)

Continue pressing the PROGRAMMING TIME button 
unit it makes 2 short beeps and find the upper code.

(5)

Press the OPERATION MODE SELECTOR button 
and lower figure of the error code flashes.

(6)

Continue pressing the PROGRAMMING TIME button 
unit it makes a long beep and find the lower code.

y

 A long beep indicate the error code.

„

Trouble shooting with the LEDs on the PC board

    

(Refer to Table 11)

The following checking can be made with the service 
monitor LEDs (green). (Normal when flashing)

: LED on      

Q

 : LED off      

: LED flashing

 —

: Not used for trouble shooting

Table 11

NOTE

1

In case wired remote controller. Press the INSPECTION 
/TEST OPERATION button on remote controller, “

” 

starts flashing.

Pipe hole area  
Cut with saw, etc

Pipe hole area  
Cut with saw, etc

For rear running pipes

Fig. 36

For rightward running pipes

Fig. 37

TEST

TEST

Microcomputer 
normal monitor

Transmission 
normal monitor

Details

HAP(H1P)

HBP(H2P)

Indoor unit is normal

Diagnose 

the outdoor unit

Miswiring between the indoor and 
outdoor units

Q

If the outdoor unit HAP(H1P) does 
not light, diagnose the outdoor unit. 
If it is flashed, it is due to either 
miswiring or malfunction of the 
indoor or outdoor unit PC board 
assembly. 
(NOTE 4)

Malfunction of the indoor unit PC 
board (NOTE 5)

Q

Abnormal power supply, malfunc-
tion of PC board assembly or dis-
connection between the indoor and 
outdoor units (NOTE 5)

01_EN_3P249378-5G.fm  Page 14  Friday, January 20, 2012  2:01 PM

Summary of Contents for FUQ100BUV1B x 2

Page 1: ...RE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGV...

Page 2: ...eenkomstig de bepalingen van Richtlijnen zoals geamendeerd siguiendo las disposiciones de Directivas seg n lo enmendado secondo le prescrizioni per Direttive come da modifica de acordo com o previsto...

Page 3: ...71BV1 FHYP100BV1 FHYP125BV1 FH35BZV1 FH45BZV1 FH60BZV1 III FHQ35BUV1B FHQ50BUV1B FHQ60BUV1B FHQ71BUV1B FHQ100BUV1B FHQ125BUV1B FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B FUQ71...

Page 4: ...t and never connect additional wiring to the existing circuit An insufficient power supply capacity or improper electrical work may lead to electric shocks or fire Be sure to earth the air conditioner...

Page 5: ...here the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels 2 2 ACCESSORIES Check the following acc...

Page 6: ...rection therefore select flow direction from the below patterns Air flow patterns Refer to Fig 1 IIlustrations seen from ceiling A B C and D indicate drain pans Refrigerant pipe direction To the rear...

Page 7: ...Fig 4 and 5 Slide the locking knobs 2 on the air intake grille inward direction of arrows and lift upwards Fig 4 Fig 5 Open the air intake grille to a 45 angle and detach from the unit Detach the corn...

Page 8: ...hole in anchor for existing ceilings and a sunken insert sunken anchor or other field supplied parts for new ceilings to reinforce the ceiling to bear the weight of the unit Adjust clearance from the...

Page 9: ...ged by sliding the shutter Refer to Fig 14 CAUTION Be careful not to touch the heat exchanger fins 2 way air discharge Refer to Fig 15 NOTE Illustrations seen from ceiling Fig 15 Retainers for blockin...

Page 10: ...18 Lock the unit to the hangers on side A Hook the unit onto the other 2 hangers and lock with bottom washers and nuts 5 3 Check whether the unit is horizontally level from sides C and D both Refer t...

Page 11: ...ly ester oil or ether oil to the inside of the flare section and spin 3 4 times before screwing in Refer to Fig 22 CAUTION Do not let oil get on the screw holders on the dressing board Oil can weaken...

Page 12: ...a flared or a flanged connection Nitrogen should be set to 0 02MPa with a pressure reducing valve if brazing while inserting nitrogen into the piping Refer to Fig 25 Fig 25 7 DRAIN PIPING WORK 7 1 Ri...

Page 13: ...ing after the test run is complete Remove the control box lid and change the emergency switch above the PC board assembly of the indoor unit from NORM to EMERG Connect the single phase power supply an...

Page 14: ...wires After all the wiring connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit from outside...

Page 15: ...g ceiling height Select the SECOND CODE NO that corresponds to the ceiling height Refer to Table 5 and 6 SECOND CODE NO is factory set to 01 for a ceiling height of less than 2 7m Table 5 Table 6 10 2...

Page 16: ...the end of the setting procedure You do not need to rewire the remote controller from the master unit if the optional remote controller for slave unit is used However remove the wires attached to the...

Page 17: ...rystal display In such a case diagnose the fault contents by referning to the table on the Error code list it case of group control the unit No is displayed so that the indoor unit no with the trouble...

Page 18: ...4 Low pressure switch faulty outdoor unit H7 Outdoor fan motor position signal malfunction out door unit H9 Outdoor air thermistor faulty outdoor unit NOTE 1 J1 Pressure sensor system error batch outd...

Page 19: ...elivering the product to the customer after the test run is completed check that the control box lid the air filter and the suction grille are mounted In addition explain to the customer regarding the...

Page 20: ...NG CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 4 X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS BEING USED 5 REMOTE CONTROLLER MO...

Page 21: ...RMINAL CONNECTOR 2 FIELD WIRING 3 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 4 X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTRO...

Page 22: ...TEM SEE THE INDOOR UNIT WIRING ONLY 4 FOR THE DETAIL SEE WIRING DIAGRAM ATTACHED TO OUTDOOR UNIT 5 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTAL...

Page 23: ...1201 3P249378 5G EM11A075 HT 00_CV_3P249378 5G fm Page 2 Thursday December 8 2011 4 16 PM...

Reviews: