3-1. FUQ
If the temperature or the humidity is beyond the fol-
lowing conditions, safety devices may work and the
air conditioner may not operate, or sometimes,
water may drop from the indoor unit.
COOLING
3. OPERATION RANGE
OUTDOOR
UNIT
INDOOR
OUTDOOR
TEMPERA-
TURE
TEMPERA-
TURE
HUMID-
ITY
RZQ71, 100,
125, 140
D
B
18 to 37
80% or
below
D
B
–15 to 50
W
B
12 to 28
RZQ200
D
B
21 to 37
80% or
below
D
B
– 5 to 46
W
B
14 to 28
RQ71,100,125
D
B
18 to 37
80% or
below
D
B
–5 to 46
W
B
12 to 28
RR71,100,125
D
B
18 to 37
80% or
below
D
B
–15 to 46
W
B
12 to 28
RZQG71, 100,
125, 140
D
B
18 to 37
80% or
below
D
B
–15 to 50
W
B
12 to 28
HEATING
D
B: Dry bulb temperature (
°
C)
WB: Wet bulb temperature (
°
C)
The setting temperature range of the remote con-
troller is 16°C to 32°C.
3-2. FXUQ
If the temperature or the humidity is beyond the fol-
lowing conditions, safety devices may work and the
air conditioner may not operate, or sometimes,
water may drop from the indoor unit.
*To avoid condensation and water dripping out the
unit.
D
B: Dry bulb temperature (
°
C)
WB: Wet bulb temperature (
°
C)
The setting temperature range of the remote con-
troller is 16°C to 32°C.
OUTDOOR
UNIT
INDOOR
TEMPERATURE
OUTDOOR
TEMPERATURE
RZQ71, 100,
125, 140
D
B
10 to 27
D
B
–19.5 to 21
W
B
–20 to 15.5
RZQ200
D
B
10 to 27
D
B
–14 to 21
W
B
–15 to 15
RQ71,100,125
D
B
10 to 27
D
B
–9 to 21
W
B
–10 to 15
RZQG71, 100,
125, 140
D
B
10 to 27
D
B
–19.5 to 21
W
B
–20 to 15.5
COOLING
HEATING
OUTDOOR
TEMPERATURE
D
B
–5 to 43
D
B
–19.5 to 21
W
B
–20 to 15.5
INDOOR
TEMPERATURE
D
B
21 to 37
D
B
10 to 27
W
B
14 to 28
INDOOR HUMIDITY
80%* or below