Indoor Unit Installation

3-2. Left-side, left-back, or left-bottom piping

1) Attach the drain hose to the underside of the refrigerant pipes 

with adhesive vinyl tape.

2) Be sure to connect the drain hose to the drain port in place of 

a drain plug.

3) Shape the refrigerant pipes along the pipe 

path marking on the mounting plate.

4) Pass the drain hose and refrigerant pipes 

through the wall hole, then set the indoor 
unit on mounting plate hooks, using the 

markings at the top of the indoor unit as 

a guide.

5) Pull in the inter-unit wire.
6) Connect the inter-unit pipes.

7) Wrap the refrigerant pipes and drain hose together with insulation tape as 

shown in the figure on the right (in case of setting the drain hose through 
the back of the indoor unit.

8) While exercising care so that the inter-unit wire does not catch indoor unit, 

press the bottom edge of indoor unit with both hands until it is firmly caught 
by the mounting plate hooks. Secure indoor unit to the mounting plate with 
indoor unit fixing screws (M4 × 12L).

3-3. Wall embedded piping

Follow the instructions given under left-side, left-back, or left-bottom piping.
1) Insert the drain hose to this depth so it won’t be pulled out of the drain pipe.

How to replace the drain plug and drain hose

• Replacing onto the left side

1) Remove the insulation fixing screw on the 

right and remove the drain hose.

2) Remove the drain plug on the left side and 

attach it to the right side.

3) Insert the drain hose and tighten with 

included insulation fixing screw.
* (Forgetting to tighten this may cause 
   water leakages.)

Drain hose attachment position

* The drain hose is on the back of the unit.

Front side of unit

Attachment on the right side (factory default)

Attachment on the left side

Drain hose

Drain hose

Insulation 
fixing screw

Insulation 
fixing screw

Left side

Right side

Remove pipe port cover here for left-bottom piping.

Remove pipe 
port cover 
here for left-
side piping.

Left-bottom piping

Left-side 
piping

Left-back 
piping

How to set drain plug

No gap.

Do not apply lubricating 
oil (refrigerant oil) to the 
drain plug when inserting it.
The application of lubrication 
oil to the drain plug will deteriorate 
the plug and cause drain leakage 
from the plug.

Insert a hexagonal wrench (4mm).

Drain 
hose

Caulk this hole 
with putty or 
caulking material.

Bind with adhesive 
vinyl tape.

Mounting plate

Wrap insulating tape around the 
bent portion of refrigerant pipes. 
Overlap at least half the width of 
the tape with each turn.

Refrigerant 
pipes

Drain hose

Bottom frame

Indoor unit fixing screw
(M4 × 12L) (2 locations)

Mounting 
plate

Inter-unit wire

Inner wall

Vinyl chloride 
drain pipe 
(VP-30)

Drain hose

50mm 
or more

Insert drain hose 
to this depth so 
it won’t be pulled 
out of drain pipe.

Outer wall

Summary of Contents for FTXS25K2V1B

Page 1: ...liano E Portugues Pycc T rk e DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series MODELS FTXS20K2V1B FTXS20K3V1B FTXS25K2V1B FTXS25K3V1B CTXS15K2V1B CTXS15K3V1B CTXS35K2V1B CTXS35K3V1B...

Page 2: ...con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certific...

Page 3: ...ece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e...

Page 4: ...y Control Department DAIKIN TCF 015 N20 09 2011 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan DAIKIN INDUSTRIES LTD Low Volta...

Page 5: ...Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan FTXS20K2V1B FTXS25K2V1B CTXS15K2V1B CTXS35K2V1B 3SB65451 2 Shinri Sada Manager Quality Control Department...

Page 6: ......

Page 7: ...abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Impr...

Page 8: ...e remote controller range 8 the unit is at least 1m away from any television or radio set unit may cause interference with the picture or sound 9 install at the recommended height 1 8m 10 no laundry e...

Page 9: ...he front grille there are 3 upper hooks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand When there is no work space because the un...

Page 10: ...rille Opening service lid Service lid is removable Opening method 1 Remove the service lid screw 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down The mounting plate...

Page 11: ...he hole 3 Insert a wall cover into wall pipe 4 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 3 Installing the indoor unit In the case of bending or curing...

Page 12: ...s by using the markings at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to preparation before installation 5 Pass the inter unit wire from the outdoor u...

Page 13: ...ng onto the left side 1 Remove the insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and t...

Page 14: ...s remote controller SIGNAL RECEIVER Signal receiver BZ Buzzer C101 C102 Capacitor FG Frame ground F1U Fuse 3 15A H1P H3P Pilot lamp MR10 Magnetic relay M1F Fan motor M1S M3S Swing motor PCB1 PCB4 Prin...

Page 15: ...available on the right side of the indoor unit the work can be performed with the electrical component box attached Omit the steps involved with removing and installing the electrical component box in...

Page 16: ...l component box 2 Route the connection cord as shown in Figure 3 5 8 Install the electrical component box in its original position 1 Install the electrical component box 1 screw 2 Install the thermist...

Page 17: ...ARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installat...

Page 18: ...igerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insul...

Page 19: ...ore the original operation mode when the circuit breaker is opened again 2 Test items If the is not displayed change the dipswitch setting for the remote controller Slide the dipswitch to the left han...

Page 20: ...3P363588 1B 2014 06 Copyright 2013 Daikin...

Reviews: