, install as described in the installation manual supplied with the multi outdoor unit.

1.

Flaring the pipe end 

1) Cut the pipe end with a pipe cutter.

2) Remove burrs with the cut surface facing downward, 

so that the filings do not enter the pipe.

3) Put the flare nut on the pipe.

4) Flare the pipe.

5) Check that the flaring has been done correctly.

2.

Refrigerant piping

CAUTION

• Use the flare nut fixed to the main unit. (This is to prevent the flare nut from cracking as a result of deterioration over time.)

• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)

• Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

• Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand, then tighten them fully with a spanner and a 

torque wrench.

2-1. Caution on piping handling 

• Protect the open end of the pipe against dust and moisture.

• All pipe bends should be as gentle as possible. Use a pipe bender for 

bending. 

2-2. Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following: 

• Insulation material:  Polyethylene foam

Heat transfer rate:  0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 to 
0.045kcal/mh°C))
Be sure to use insulation that is designed for use with HVAC Systems. 

• ACR Copper only.

• Be sure to insulate both the gas and liquid piping and observe the insulation dimensions as below. 

• Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

• Using finishing tape, bundle and wrap the indoor unit piping and drain hose together so that the drain hose is below 

the other piping.

Piping size

Minimum bend radius

Piping thickness

Thermal insulation size

Thermal insulation 

thickness

Gas side

O.D. 3/8 inch

(9.5mm)

1-3/16 inch (30mm)

or more

0.031 inch (0.8mm)

(C1220T-O)

I.D. 15/32-19/32 inch

(12-15mm)

13/32 inch

(10mm) Min.

O.D. 1/2 inch

(12.7mm)

1-9/16 inch (40mm)

or more

I.D. 9/16-5/8 inch

(14-16mm)

Liquid side

O.D. 1/4 inch

(6.4mm)

1-3/16 inch (30mm)

or more

I.D. 5/16-13/32 inch

(8-10mm)

With a multi indoor unit

A

A

Flaring

Set exactly at the position shown below.

Die

0-0.020 inch

(0-0.5mm)

Clutch-type

Flare tool for 

R32 or R410A

0.039-0.059 inch

(1.0-1.5mm)

Clutch-type

(Rigid-type)

0.059-0.079 inch

(1.5-2.0mm)

Wing-nut type

(Imperial-type)

Conventional flare tool

The flare’s inner surface must be 

flaw-free.
When flaring, do not over-tighten 

and crack.

The pipe end must be evenly flared 

in a perfect circle.

Make sure that the flare nut is fitted.

Check

Cut exactly at 

right angles.

 Remove burrs.

Do not apply refrigeration 

oil to the outer surface.

Flare nut

Apply refrigeration 

oil only to the inner 

surface of the flare.

Do not apply refrigeration oil to 

the flare nut to avoid tightening 

with excessive torque.

Apply oil

Torque wrench

Piping union

Flare nut

Spanner

Tighten

Gas side

Piping size

O.D. 3/8 inch 

(9.5mm)

O.D. 1/2 inch 

(12.7mm)

O.D. 1/4 inch 

(6.4mm)

24-1/8–29-1/2ft • Ibf 

(32.7-39.9N • m)

36-1/2–44-1/2ft • lbf 

(49.5-60.3N • m)

10-1/2–12-3/4ft • lbf 

(14.2-17.2N • m)

Flare nut tightening torque

Liquid side

Wall

If no flare cap is 

available, cover the 

flare mouth with 

tape to keep dirt 

and water out.

Rain

Be sure to 

place a cap.

Gas pipe

Liquid pipe

Gas pipe 

insulation

Liquid pipe 

insulation

Finishing tape

Drain hose

01_EN_3P674703-1.fm  10 ページ  2022年3月29日 火曜日 午後3時40分

Summary of Contents for FTXR09WVJUW9

Page 1: ...R CONDITIONER R410A Split Series English Fran ais Espa ol MODELS FTXR09WVJUW9 FTXR12WVJUW9 FTXR18WVJUW9 FTXR09WVJUS9 FTXR12WVJUS9 FTXR18WVJUS9 Installation manual Manuel d installation Manual de insta...

Page 2: ...ials used for transportation may cause injuries or death by suffocation WARNING Only qualified personnel licensed or certified in their jurisdiction must carry out the installation work Installation m...

Page 3: ...tem b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse e...

Page 4: ...the unit is away from electronic ignition type fluorescent lamps inverter or rapid start type as they may affect the remote controller range 9 no laundry equipment is nearby 2 Wireless remote controll...

Page 5: ...filters Screws M4 5 8 M4 16mm C D Wireless remote controller E Remote controller holder When dismounting the front grille refer to 2 Removing and installing the front grille on page 11 A Mounting plat...

Page 6: ...the pipe hole gap with putty Recommended mounting plate retention spots 5 spots in all Bolt size 3 8 M10 Bolt size 3 8 M10 Gas pipe end Liquid pipe end Place a leveler on these tabs Through the wall...

Page 7: ...h a copping saw Apply the blade of the copping saw to the notch and cut off the pipe port cover along the uneven inner surface 2 After cutting off the pipe port cover perform filing Remove the burrs a...

Page 8: ...le side and unit side 2 After cutting off the pipe port cover perform filing Remove the burrs along the cut section using a half round needle file NOTE Be careful not to let chips enter the driving se...

Page 9: ...the removal method on page 11 4 Remove the conduit mounting plate and then secure the conduit to the conduit mounting plate with the lock nut as shown in the illustration 5 Strip wire ends 3 4 inch 20...

Page 10: ...match the hose front end Figure of hose front end When drain hose requires extension obtain an extension hose with an inner diameter of 5 8 inch 16mm Be sure to thermally insulate the indoor section o...

Page 11: ...ng finishing tape bundle and wrap the indoor unit piping and drain hose together so that the drain hose is below the other piping Piping size Minimum bend radius Piping thickness Thermal insulation si...

Page 12: ...t panel locks on the back of the front panel upward to release the locks left and right sides 2 Insert the panel shafts on both sides of the upper front panel into the shaft holes 3 Slide the front pa...

Page 13: ...f the two units When cutting the jumper be careful not to damage any of the surrounding parts 1 Remove the upper front panel and front grille Refer to the removal method on page 11 2 Cut the address j...

Page 14: ...ot interfere with the printed circuit board 3 Attach the connection cord to the S21 connector and pull the harness out through the notched part in the figure Attachment methods for metal plate electri...

Page 15: ...consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 2 Test items Test ite...

Page 16: ...2203 HT M21B356 The two dimensional bar code is a manufacturing code 3P674703 1 00_CV_3P674703 1 fm 2...

Reviews: