Indoor Unit Installation
9) In case of connecting to an adapter system, run the remote controller cable and attach the S21.
(Refer to
“5. When connecting to an HA system”
on page 13.)
10) Attach the conduit mounting plate.
11) Shape the wires so that the service lid fits securely.
12) Attach the front grille. (Refer to removal method on page 11.)
13) Attach the service lid and the upper front panel. (Refer to the opening method on page 4.)
14) Take care to ensure that all wiring between the indoor unit and the outdoor unit has a consistent connection. Any splices
can cause communication errors.
5.
Drain piping
1) Connect the drain hose, as described on the right.
• Avoid placing the end of the drain hose in a drainage location that could
cause bad odors or corrosive gas to flow backward into the outlet.
• The drainage water may change color due to bacteria or other
organisms. Place in a location where the flow of drainage water will not
cause a problem.
• Minimize the number of bends in the drain hose as much as possible.
If bending the drain hose, bend it gently.
2) Remove the air filters and transfer some water to the indoor heat
exchanger by pouring water into the drain pan.
3) Make sure that water flows out of the drain hose.
4) If drain hose extension or embedded drain piping is required, use
appropriate parts that match the hose front end.
Figure of hose front end
• When drain hose requires extension, obtain an extension
hose with an inner diameter of 5/8 inch (16mm).
Be sure to thermally insulate the indoor section of the
extension hose.
• When connecting a rigid polyvinyl chloride pipe
(nominal diameter 1/2 inch (13mm)) directly to
the drain hose attached to the indoor unit as with
embedded piping work, use any commercially
available drain socket (nominal diameter 1/2 inch
(13mm)) as a joint.
Refrigerant Piping Work
WARNING
• Do not apply mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the service life of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a dryer to this R410A unit in order to guarantee its service life.
• The drying material may dissolve and damage the system.
• Incomplete flaring may result in refrigerant gas leakage.
Make a downward slope
Getting higher
Wrong
Wrong
Containing waves
Wrong
With the end of the hose
in the drain outlet
Leave a gap of 1-15/16 inches (50mm) or
more at the end of the outlet
ϕ
11/16” (
ϕ
18mm)
ϕ
5/8” (
ϕ
16mm)
Indoor unit
drain hose
Extension drain hose
Heat insulation tube (field supply)
ϕ
5/8” (
ϕ
16mm)
Drain hose supplied
with the indoor unit
Commercially available
drain socket
(nominal diameter 1/2 inch
(13mm))
Commercially available
rigid polyvinyl chloride pipe
(nominal diameter 1/2 inch
(13mm))
Drain hose supplied with
the indoor unit
ϕ
11/16” (
ϕ
18mm)