5 Installation

Installation manual

8

(A)(F)TXP20~7 FTXF20~71A2V1B

Daikin room air conditioner

3P512025-1C – 2018.01

4.2

Preparing refrigerant piping

4.2.1

Refrigerant piping requirements

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

Class

L1 liquid piping

L1 gas piping

20~35

Ø6.4

Ø9.5

50~71

Ø6.4

Ø12.7

Refrigerant piping material

Piping material:

 Phosphoric acid deoxidised seamless copper.

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

12.7 mm (1/2")

(a)

Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.

4.2.2

Refrigerant piping insulation

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

12~15 mm

12.7 mm (1/2")

14~16 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

5

Installation

5.1

Opening the units

5.1.1

To open the indoor unit

To remove the front panel

1

Hold the front panel by the panel tabs on both sides and open
it.

a

a

Indentation on the unit

2

Remove  the  front  panel  by  sliding  it  to  the  left  or  the  right  and
pulling it toward you.

Result: 

The front panel shaft on 1 side will be disconnected.

3

Disconnect  the  front  panel  shaft  on  the  other  side  in  the  same
manner.

a

a

Front panel shaft

To re-install the front panel

1

Attach the front panel. Align the shafts with the slots and push
them all the way in.

2

Close  the  front  panel  slowly  and  press  on  both  sides  at  the
centre.

To remove the front grille

CAUTION

Wear  adequate  personal  protective  equipment  (protective
gloves,  safety  glasses,…)  when  installing,  maintaining  or
servicing the system.

1

Remove the front panel to remove the air filter.

2

Remove 2 screws (class 20~35) or 3 screws (class 50~71) from
the front grille.

3

Push  down  the  3  upper  hooks  marked  with  a  symbol  with  3
circles.

a

b

a

a

Upper hook

b

Symbol with 3 circles

4

We  recommend  opening  the  flap  before  removing  the  front
grille.

5

Place both hands under the centre of the front grille, push it up
and then toward you.

1

2

To re-install the front grille

1

Install the front grille and firmly engage the 3 upper hooks.

2

Install  2  screws  (class  20~35)  or  3  screws  (class  50~71)  back
on the front grille.

3

Install the air filter and then mount the front panel.

Summary of Contents for FTXP20L2V1B

Page 1: ...tioner English Installation manual Daikin room air conditioner FTXP20L2V1B FTXP25L2V1B FTXP35L2V1B FTXP50L2V1B FTXP60L2V1B FTXP71L2V1B ATXP20L2V1B ATXP25L2V1B ATXP35L2V1B FTXF20A2V1B FTXF25A2V1B FTXF35A2V1B FTXF50A2V1B FTXF60A2V1B FTXF71A2V1B ...

Page 2: ...e în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструк...

Page 3: ...cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemia...

Page 4: ...trucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nuro...

Page 5: ...mitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitink...

Page 6: ...ATION Make sure that the user has the printed documentation and ask him her to keep it for future reference Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consis...

Page 7: ...additional insulation is required minimum 10 mm thickness polyethylene foam Wall strength Check whether the wall or the floor is strong enough to support the weight of the unit If there is a risk reinforce the wall or the floor before installing the unit Install power cables at least 1 metre away from televisions or radios to prevent interference Depending on the radio waves a distance of 3 metres...

Page 8: ... 1 Opening the units 5 1 1 To open the indoor unit To remove the front panel 1 Hold the front panel by the panel tabs on both sides and open it a a Indentation on the unit 2 Remove the front panel by sliding it to the left or the right and pulling it toward you Result The front panel shaft on 1 side will be disconnected 3 Disconnect the front panel shaft on the other side in the same manner a a Fr...

Page 9: ...he cover first hook the bottom tab onto the electrical wiring box and slide the cover into the 2 upper tabs To open the service cover 1 Remove 1 screw from the service cover 2 Pull out the service cover horizontally away from the unit a b a Service cover screw b Service cover 5 2 Installing the indoor unit 5 2 1 To install the mounting plate 1 Install the mounting plate temporarily 2 Level the mou...

Page 10: ...nd h Liquid pipe end 5 2 2 To drill a wall hole CAUTION For walls containing a metal frame or a metal board use a wall embedded pipe and wall cover in the feed through hole to prevent possible heat electrical shock or fire NOTICE Be sure to seal the gaps around the pipes with sealing material field supply in order to prevent water leakage 1 Bore a 65 mm large feed through hole in the wall with a d...

Page 11: ... to the drain hose as with embedded piping work use a field supplied drain socket nominal Ø13 mm a b c Ø18 a Drain hose supplied with the indoor unit b Drain socket with nominal Ø13 mm field supply c Rigid polyvinyl chloride pipe field supply Condensation Take measures against condensation Insulate the complete drain piping in the building 1 Insert the drain hose in the drain pipe as shown in the ...

Page 12: ...owing guidelines into account when connecting pipes Coat the flare inner surface with ether oil or ester oil when connecting a flare nut Tighten 3 or 4 turns by hand before tightening firmly ALWAYS use 2 wrenches together when loosening a flare nut ALWAYS use a spanner and torque wrench together to tighten the flare nut when connecting the piping This to prevent nut cracking and leaks a b c d a To...

Page 13: ...eep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electric...

Page 14: ... addresses for 2 user interfaces can be set 1 Remove the batteries from the user interface 2 Cut the address jumper a a a Address jumper NOTICE Be careful NOT to damage any of the surrounding parts when cutting the address jumper 3 Turn the power supply on Result The flap of the indoor unit will open and close to set the reference position INFORMATION For FTXF A units the following setting MUST be...

Page 15: ...erant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open 7 2 To perform a test run Prerequisite Power supply MUST be in the specified range Prerequisite Test run may be performed in cooling or heating mode Prerequisite Test run should be performed in accordance with the operation manual of the indoor unit ...

Page 16: ...TCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P512025 1C 2018 01 Copyright 2017 Daikin ...

Reviews: