5 Installation

Installation manual

12

(A)(F)TXP20~7 FTXF20~71A2V1B

Daikin room air conditioner

3P512025-1C – 2018.01

NOTICE

Do  NOT  apply  lubricating  oil  (refrigerant  oil)  to  the  drain
plug when inserting it. The drain plug may deteriorate and
cause drain leakage from the plug.

a

a

4 mm hexagonal wrench

3

Insert the drain hose on the left side and do not forget to tighten
it with the fixing screw; otherwise water leakage may occur.

a

b

a

b

a

Insulation fixing screw

b

Drain hose

4

Attach the drain hose to the refrigerant pipes bottom side using
adhesive vinyl tape.

A

B

b

a

A

Left-side piping

B

Left-back piping

C

Left-bottom piping

a

Remove the pipe port cover here for left-side piping.

b

Remove the pipe port cover here for left-bottom piping.

To check for water leaks

1

Remove the air filters.

2

Gradually pour approximately 1 l of water in the drain pan, and
check for water leaks.

5.3

Connecting the refrigerant piping

DANGER: RISK OF BURNING

5.3.1

Guidelines when connecting the
refrigerant piping

Take the following guidelines into account when connecting pipes:

▪ Coat  the  flare  inner  surface  with  ether  oil  or  ester  oil  when

connecting  a  flare  nut.  Tighten  3  or  4  turns  by  hand,  before
tightening firmly.

▪ ALWAYS use 2 wrenches together when loosening a flare nut.

▪ ALWAYS use a spanner and torque wrench together to tighten the

flare nut when connecting the piping. This to prevent nut cracking
and leaks.

a

b

c

d

a

Torque wrench

b

Spanner

c

Piping union

d

Flare nut

Piping size

(mm)

Tightening

torque (N•m)

Flare

dimensions (A)

(mm)

Flare shape

(mm)

Ø6.4

15~17

8.7~9.1

R=0.4~0.8

45° ±2

90°±2

A

Ø9.5

33~39

12.8~13.2

Ø12.7

50~60

16.2~16.6

5.3.2

To connect the refrigerant piping to the
indoor unit

Pipe length

. Keep refrigerant piping as short as possible.

Flare  connections

.  Connect  refrigerant  piping  to  the  unit  using

flare connections.

Insulation

.  Insulate  the  refrigerant  piping,  interconnection  cable

and drain hose on the indoor unit as follows:

c

a

b

f

d

g

e

a

Gas pipe

b

Gas pipe insulation

c

Interconnection cable

d

Liquid pipe

e

Liquid pipe insulation

f

Finishing tape

g

Drain hose

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

5.4

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

Summary of Contents for FTXP20L2V1B

Page 1: ...tioner English Installation manual Daikin room air conditioner FTXP20L2V1B FTXP25L2V1B FTXP35L2V1B FTXP50L2V1B FTXP60L2V1B FTXP71L2V1B ATXP20L2V1B ATXP25L2V1B ATXP35L2V1B FTXF20A2V1B FTXF25A2V1B FTXF35A2V1B FTXF50A2V1B FTXF60A2V1B FTXF71A2V1B ...

Page 2: ...e în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструк...

Page 3: ...cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemia...

Page 4: ...trucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nuro...

Page 5: ...mitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitink...

Page 6: ...ATION Make sure that the user has the printed documentation and ask him her to keep it for future reference Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consis...

Page 7: ...additional insulation is required minimum 10 mm thickness polyethylene foam Wall strength Check whether the wall or the floor is strong enough to support the weight of the unit If there is a risk reinforce the wall or the floor before installing the unit Install power cables at least 1 metre away from televisions or radios to prevent interference Depending on the radio waves a distance of 3 metres...

Page 8: ... 1 Opening the units 5 1 1 To open the indoor unit To remove the front panel 1 Hold the front panel by the panel tabs on both sides and open it a a Indentation on the unit 2 Remove the front panel by sliding it to the left or the right and pulling it toward you Result The front panel shaft on 1 side will be disconnected 3 Disconnect the front panel shaft on the other side in the same manner a a Fr...

Page 9: ...he cover first hook the bottom tab onto the electrical wiring box and slide the cover into the 2 upper tabs To open the service cover 1 Remove 1 screw from the service cover 2 Pull out the service cover horizontally away from the unit a b a Service cover screw b Service cover 5 2 Installing the indoor unit 5 2 1 To install the mounting plate 1 Install the mounting plate temporarily 2 Level the mou...

Page 10: ...nd h Liquid pipe end 5 2 2 To drill a wall hole CAUTION For walls containing a metal frame or a metal board use a wall embedded pipe and wall cover in the feed through hole to prevent possible heat electrical shock or fire NOTICE Be sure to seal the gaps around the pipes with sealing material field supply in order to prevent water leakage 1 Bore a 65 mm large feed through hole in the wall with a d...

Page 11: ... to the drain hose as with embedded piping work use a field supplied drain socket nominal Ø13 mm a b c Ø18 a Drain hose supplied with the indoor unit b Drain socket with nominal Ø13 mm field supply c Rigid polyvinyl chloride pipe field supply Condensation Take measures against condensation Insulate the complete drain piping in the building 1 Insert the drain hose in the drain pipe as shown in the ...

Page 12: ...owing guidelines into account when connecting pipes Coat the flare inner surface with ether oil or ester oil when connecting a flare nut Tighten 3 or 4 turns by hand before tightening firmly ALWAYS use 2 wrenches together when loosening a flare nut ALWAYS use a spanner and torque wrench together to tighten the flare nut when connecting the piping This to prevent nut cracking and leaks a b c d a To...

Page 13: ...eep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electric...

Page 14: ... addresses for 2 user interfaces can be set 1 Remove the batteries from the user interface 2 Cut the address jumper a a a Address jumper NOTICE Be careful NOT to damage any of the surrounding parts when cutting the address jumper 3 Turn the power supply on Result The flap of the indoor unit will open and close to set the reference position INFORMATION For FTXF A units the following setting MUST be...

Page 15: ...erant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open 7 2 To perform a test run Prerequisite Power supply MUST be in the specified range Prerequisite Test run may be performed in cooling or heating mode Prerequisite Test run should be performed in accordance with the operation manual of the indoor unit ...

Page 16: ...TCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P512025 1C 2018 01 Copyright 2017 Daikin ...