5 Installation

Installation manual

13

(A)(F)TXP20~7 FTXF20~71A2V1B
Daikin room air conditioner
3P512025-1C – 2018.01

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

5.4.1

To connect the electrical wiring on the
indoor unit

Electrical  work  should  be  carried  out  in  accordance  with  the
installation manual and the national electrical wiring rules or code of
practice.

1

Set  the  indoor  unit  on  the  mounting  plate  hooks.  Use  the  " "
marks as a guide.

b

a

c

a

Mounting plate (accessory)

b

Interconnection cable

c

Wire guide

2

Open  the  front  panel,  and  then  the  service  cover.  Refer  to

"5.1.1 To open the indoor unit" on page 8

.

3

Pass  the  interconnection  cable  from  the  outdoor  unit  through
the  feed-through  wall  hole,  through  the  back  of  the  indoor  unit
and through the front side.

Note: 

  In  case  the  interconnection  cable  was  stripped  in  advance,

cover the ends with insulating tape.

4

Bend the end of the cable up.

NOTICE

▪ Be  sure  to  keep  the  power  line  and  transmission  line

apart  from  each  other.  Transmission  wiring  and  power
supply wiring may cross, but may NOT run parallel.

▪ In order to avoid any electrical interference the distance

between  both  wirings  should  ALWAYS  be  at  least
50 mm.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

a
b

c

a

Terminal block

b

Electrical component block

c

Wire retainer

5

Strip the wire ends approximately 15 mm.

6

Match  wire  colours  with  terminal  numbers  on  the  indoor  unit
terminal blocks and firmly screw the wires to the corresponding
terminals.

7

Connect the earth wire to the corresponding terminal.

8

Firmly fix the wires with the terminal screws.

9

Pull  the  wires  to  make  sure  that  they  are  securely  attached,
then retain the wires with the wire retainer.

10

Shape  the  wires  so  that  the  service  cover  fits  securely,  then
close the service cover.

5.5

Finishing the indoor unit
installation

5.5.1

To insulate the drain piping, refrigerant
piping and interconnection cable

1

After the drain piping, refrigerant piping and the electrical wiring
are  finished.  Wrap  refrigerant  pipes,  interconnection  cable  and
drain  hose  together  using  insulation  tape.  Overlap  at  least  half
the width of the tape with each turn.

d

e

c

b

f

a

a

Drain hose

b

Interconnection cable

c

Mounting plate (accessory)

d

Refrigerant pipes

e

Indoor unit fixing screw M4×12L (accessory)

f

Bottom frame

5.5.2

To pass the pipes through the wall hole

1

Shape the refrigerant pipes along the pipe path marking on the
mounting plate.

a

b

c

c

d

e

a

Drain hose

b

Caulk this hole with putty or caulking material.

Summary of Contents for FTXP20L2V1B

Page 1: ...tioner English Installation manual Daikin room air conditioner FTXP20L2V1B FTXP25L2V1B FTXP35L2V1B FTXP50L2V1B FTXP60L2V1B FTXP71L2V1B ATXP20L2V1B ATXP25L2V1B ATXP35L2V1B FTXF20A2V1B FTXF25A2V1B FTXF35A2V1B FTXF50A2V1B FTXF60A2V1B FTXF71A2V1B ...

Page 2: ...e în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструк...

Page 3: ...cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemia...

Page 4: ...trucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nuro...

Page 5: ...mitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitink...

Page 6: ...ATION Make sure that the user has the printed documentation and ask him her to keep it for future reference Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consis...

Page 7: ...additional insulation is required minimum 10 mm thickness polyethylene foam Wall strength Check whether the wall or the floor is strong enough to support the weight of the unit If there is a risk reinforce the wall or the floor before installing the unit Install power cables at least 1 metre away from televisions or radios to prevent interference Depending on the radio waves a distance of 3 metres...

Page 8: ... 1 Opening the units 5 1 1 To open the indoor unit To remove the front panel 1 Hold the front panel by the panel tabs on both sides and open it a a Indentation on the unit 2 Remove the front panel by sliding it to the left or the right and pulling it toward you Result The front panel shaft on 1 side will be disconnected 3 Disconnect the front panel shaft on the other side in the same manner a a Fr...

Page 9: ...he cover first hook the bottom tab onto the electrical wiring box and slide the cover into the 2 upper tabs To open the service cover 1 Remove 1 screw from the service cover 2 Pull out the service cover horizontally away from the unit a b a Service cover screw b Service cover 5 2 Installing the indoor unit 5 2 1 To install the mounting plate 1 Install the mounting plate temporarily 2 Level the mou...

Page 10: ...nd h Liquid pipe end 5 2 2 To drill a wall hole CAUTION For walls containing a metal frame or a metal board use a wall embedded pipe and wall cover in the feed through hole to prevent possible heat electrical shock or fire NOTICE Be sure to seal the gaps around the pipes with sealing material field supply in order to prevent water leakage 1 Bore a 65 mm large feed through hole in the wall with a d...

Page 11: ... to the drain hose as with embedded piping work use a field supplied drain socket nominal Ø13 mm a b c Ø18 a Drain hose supplied with the indoor unit b Drain socket with nominal Ø13 mm field supply c Rigid polyvinyl chloride pipe field supply Condensation Take measures against condensation Insulate the complete drain piping in the building 1 Insert the drain hose in the drain pipe as shown in the ...

Page 12: ...owing guidelines into account when connecting pipes Coat the flare inner surface with ether oil or ester oil when connecting a flare nut Tighten 3 or 4 turns by hand before tightening firmly ALWAYS use 2 wrenches together when loosening a flare nut ALWAYS use a spanner and torque wrench together to tighten the flare nut when connecting the piping This to prevent nut cracking and leaks a b c d a To...

Page 13: ...eep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electric...

Page 14: ... addresses for 2 user interfaces can be set 1 Remove the batteries from the user interface 2 Cut the address jumper a a a Address jumper NOTICE Be careful NOT to damage any of the surrounding parts when cutting the address jumper 3 Turn the power supply on Result The flap of the indoor unit will open and close to set the reference position INFORMATION For FTXF A units the following setting MUST be...

Page 15: ...erant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open 7 2 To perform a test run Prerequisite Power supply MUST be in the specified range Prerequisite Test run may be performed in cooling or heating mode Prerequisite Test run should be performed in accordance with the operation manual of the indoor unit ...

Page 16: ...TCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P512025 1C 2018 01 Copyright 2017 Daikin ...

Reviews: