Si04-402A
Outdoor Unit
Removal Procedure
159
2.2
Removal of Electrical Box
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
Remove the top panel.
Disconnect the connector
for fan motor.
1. Remove the electrical
box.
1
Disconnect the 2
reactor harnesses.
2
Disconnect the relay
connector for
compressor lead wire.
3
Disconnect the
connector for four way
valve (S80).
When reassembling, coil the
excessive lead wire and
hang the loop on the hook.