Specifications
Si04-402A
6
Specifications
230V, 50Hz
Notes:
MAX. interunit piping length: 20m
MAX. interunit height difference: 15m
Amount of additional charge of refrigerant 20g/m for piping length exceeding 10m
The data are based on the conditions shown in the table below.
Model
Indoor Units
FTXG35CVMAW
FTXG35CVMAS
Outdoor Units
RXG35CVMA
RXG35CVMA
Cooling
Heating
Cooling
Heating
Capacity
Rated (Min.~Max.)
kW
3.5 (1.4~3.8)
4.2 (1.4~5.0)
3.5 (1.4~3.8)
4.2 (1.4~5.0)
Btu/h
11,950 (4,750~12,950)
14,300 (4,750~17,050)
11,950 (4,750~12,950)
14,300 (4,750~17,050)
kcal/h
3,010 (1,200~3,270)
3,610 (1,200~4,300)
3,010 (1,200~3,270)
3,610 (1,200~4,300)
Moisture Removal
L/h
1.9
—
1.9
—
Running Current (Rated)
A
4.9
5.2
4.9
5.2
Power Consumption
Rated (Min.~Max.)
W
1,060 (300~1,290)
1,135 (310~1,560)
1,060 (300~1,290)
1,135 (310~1,560)
Power Factor
%
94.0
94.9
94.0
94.9
COP
W/W
3.30
3.70
3.30
3.70
Piping
Connections
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
9.5
φ
9.5
Drain
mm
φ
18.0
φ
18.0
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Indoor Unit
FTXG35CVMAW
FTXG35CVMAS
Front Panel Color
Mat Crystal White
Mat Crystal Silver
Air Flow Rate
m³/min
(cfm)
H
8.2 (289)
8.4 (296)
8.2 (289)
8.4 (296)
M
7.1 (250)
7.5 (264)
7.1 (250)
7.5 (264)
L
5.8 (204)
6.3 (222)
5.8 (204)
6.3 (222)
SL
4.9 (172)
5.5 (194)
4.9 (172)
5.5 (194)
Fan
Type
Cross Flow Fan
Cross Flow Fan
Motor Output
W
40
40
Speed
Steps
5 Steps, Silent and Auto
5 Steps, Silent and Auto
Air Direction Control
Right, Left, Horizontal and Downward
Right, Left, Horizontal and Downward
Air Filter
Removable / Washable / Mildew Proof
Removable / Washable / Mildew Proof
Running Current (Rated)
A
0.14
0.14
0.14
0.14
Power Consumption (Rated)
W
30
30
30
30
Power Factor
%
93.2
93.2
93.2
93.2
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
275×840×150
275×840×150
Packaged Dimensions (H×W×D)
mm
222×894×345
222×894×345
Weight
kg
9
9
Gross Weight
kg
13
13
Operation
Sound
H/M/L/SL
dBA
39/35/32/29
39/35/31/28
39/35/32/29
39/35/31/28
Sound Power H
dBA
57
57
57
57
Outdoor Unit
RXG35CVMA
RXG35CVMA
Casing Color
Ivory White
Ivory White
Compressor
Type
Hermetically Sealed Swing Type
Hermetically Sealed Swing Type
Model
1YC23NXD#A
1YC23NXD#A
Motor Output
W
600
600
Refrigerant
Oil
Model
FVC50K
FVC50K
Charge
L
0.375
0.375
Refrigerant
Model
R410A
R410A
Charge
kg
1.00
1.00
Air Flow Rate
(H/L)
m³/min
31.3/22.4
28.1/22.4
31.3/22.4
28.1/22.4
cfm
1,105/791
992/791
1,105/791
992/791
Fan
Type
Propeller
Propeller
Motor Output
W
35
35
Running Current (Rated)
A
4.76
5.06
4.76
5.06
Power Consumption (Rated)
W
1,030
1,105
1,030
1,105
Power Factor
%
94.1
94.9
94.1
94.9
Starting Current
A
5.2
5.2
Dimensions (H×W×D)
mm
550×765×285
550×765×285
Packaged Dimensions (H×W×D)
mm
589×882×363
589×882×363
Weight
kg
32
32
Gross Weight
kg
38
38
Operation
Sound
H/L
dBA
47/44
48/45
47/44
48/45
Sound Power H
dBA
62
63
62
63
Drawing No.
3D046345A
3D046346A
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Cooling
Heating
Piping Length
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB/24°CWB
Indoor ; 20°CDB
Outdoor ; 7°CDB/6°CWB
7.5m
Summary of Contents for FTXG25CVMAW
Page 181: ...Outdoor Unit Si04 402A 172 Removal Procedure...
Page 185: ...Others Si04 402A 176 Others...