58
Troubleshooting
Diagnostic Guidelines
By means of pressure readings:
Data
Circuit
Pressure
Probable cause
Too low
A
little low
Normal
A
little high
Too high
High side
Low side
•
•
1. Overcharged with refrigerant.
2. Non-condensable gases in refrigerant circuit (e.g. air).
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.
High side
Low side
•
•
1. Poor compression /no compression (compressor
defective)
2. Reversing valve leaking.
High side
Low side
•
•
1. Undercharged with refrigerant.
2. Refrigerant leakage.
3. Air fi lter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.
5. Defective defrost control, outdoor coil freeze up
(heating).
6. Outdoor fan locked / seized (heating).
High side
Low side
•
•
1. Outdoor fan blocked (cooling).
2. Outdoor coil dirty (cooling).
3. Indoor fan locked / seized (heating).
4. Indoor air fi lter clogged / dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air).
High side
Low side
•
•
1. Air intake temperature of indoor unit too high.
Summary of Contents for FTN25JXV1
Page 2: ......
Page 46: ...43 Wiring Diagram Indoor Unit Model FTN50 60JXV1 Outdoor Unit Model RN50 60CJXV1...
Page 47: ...44 Wiring Diagram Indoor Unit Model FTN80FXV1 Outdoor Unit Model RR71CXV1...
Page 48: ...45 Wiring Diagram Indoor Unit Model FTN80FXV1 Outdoor Unit Model RR71CXY1...
Page 49: ...46 Wiring Diagram Indoor Unit Model FTYN20JXV1 Outdoor Unit Model RYN20CGXV1...
Page 51: ...48 Wiring Diagram Indoor Unit Model FTYN50 60JXV1 Outdoor Unit Model RYN50 60CJXV1...
Page 52: ...49 Wiring Diagram Indoor Unit Model FTYN80FXV1 Outdoor Unit Model RQ71CXV1...
Page 53: ...50 Wiring Diagram Indoor Unit Model FTYN80FXV1 Outdoor Unit Model RQ71CXY1...
Page 62: ......