10
Application Information
Refrigerant Piping
Piping Length and Elevation
When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases,
system piping resistance to the refrigerant fl ow increases, thus lowering the cooling capacity, and as the result
the compressor may become defective. Always choose the shortest path and follow the recommendation as
tabulated below:
Outdoor Unit
Indoor Unit
L
E
Cooling Only Model
Model
Indoor
FTN25JXV1
FTN25JXV1
FTN35JXV1
FTN35JXV1
Outdoor
RN25CJXV1
RN25FXV1
RN35CJXV1
RN35FXV1
Min.Allowable Length (L), m
3
Max.Allowable Length (L), m
20
25
20
25
Max.Allowable Elevation (E), m
10
15
10
15
Gas Pipe Size, mm/(in)
9.52 / (3/8")
9.52 / (3/8")
12.70 / (1/2")
12.70 / (1/2")
Liquid Pipe Size, mm/(in)
6.35 / (1/4")
6.35 / (1/4")
6.35 / (1/4")
6.35 / (1/4")
Model
Indoor
FTN50JXV1
FTN60JXV1
FTN80FXV1
Outdoor
RN50CJXV1
RN60CJXV1
RR71CXV1
RR71CXY1
Min.Allowable Length (L), m
3
Max.Allowable Length (L), m
20
20
15
15
Max.Allowable Elevation (E), m
15
15
8
8
Gas Pipe Size, mm/(in)
12.70 / (1/2")
15.88 / (5/8")
15.88 / (5/8")
15.88 / (5/8")
Liquid Pipe Size, mm/(in)
6.35 / (1/4")
6.35 / (1/4")
9.52 / (3/8")
9.52 / (3/8")
Heatpump Model
Model
Indoor
FTYN20JXV1
FTYN25JXV1
FTYN35JXV1
FTYN35JXV1
Outdoor
RYN20CGXV1
RYN25CJXV1
RYN35CJXV1
RYN35CJHXV1
Min.Allowable Length (L), m
3
Max.Allowable Length (L), m
12
20
20
20
Max.Allowable Elevation (E), m
5
10
10
10
Gas Pipe Size, mm/(in)
9.52 / (3/8")
9.52 / (3/8")
12.70 / (1/2")
12.70 / (1/2")
Liquid Pipe Size, mm/(in)
6.35 / (1/4")
6.35 / (1/4")
6.35 / (1/4")
6.35 / (1/4")
Model
Indoor
FTYN50JXV1
FTYN60JXV1
FTYN80FXV1
Outdoor
RYN50CJXV1
RYN60CJXV1
RQ71CXV1
RQ71CXY1
Min.Allowable Length (L), m
3
Max.Allowable Length (L), m
20
20
15
15
Max.Allowable Elevation (E), m
15
15
8
8
Gas Pipe Size, mm/(in)
12.70 / (1/2")
15.88 / (5/8")
15.88 / (5/8")
15.88 / (5/8")
Liquid Pipe Size, mm/(in)
6.35 / (1/4")
6.35 / (1/4")
9.52 / (3/8")
9.52 / (3/8")
Summary of Contents for FTN25JXV1
Page 2: ......
Page 46: ...43 Wiring Diagram Indoor Unit Model FTN50 60JXV1 Outdoor Unit Model RN50 60CJXV1...
Page 47: ...44 Wiring Diagram Indoor Unit Model FTN80FXV1 Outdoor Unit Model RR71CXV1...
Page 48: ...45 Wiring Diagram Indoor Unit Model FTN80FXV1 Outdoor Unit Model RR71CXY1...
Page 49: ...46 Wiring Diagram Indoor Unit Model FTYN20JXV1 Outdoor Unit Model RYN20CGXV1...
Page 51: ...48 Wiring Diagram Indoor Unit Model FTYN50 60JXV1 Outdoor Unit Model RYN50 60CJXV1...
Page 52: ...49 Wiring Diagram Indoor Unit Model FTYN80FXV1 Outdoor Unit Model RQ71CXV1...
Page 53: ...50 Wiring Diagram Indoor Unit Model FTYN80FXV1 Outdoor Unit Model RQ71CXY1...
Page 62: ......