![background image](http://html1.mh-extra.com/html/daikin/ftn25jxv1/ftn25jxv1_technical-manual_2459374012.webp)
9
Application Information
Cable Size
Model Unit
FTN25JXV1
FTN35JXV1
RN25CJXV1
RN25FXV1
RN35CJXV1
RN35FXV1
Power supply cable size
Number of wire
mm
2
1.5
3
1.5
3
1.5
3
1.5
3
Interconnection cable size
Number of wire
mm
2
1.5
3
1.5
3
1.5
3
1.5
3
Recommended fuse
A
15
15
15
15
Model Unit
FTN50JXV1
FTN60JXV1
FTN80FXV1
RN50CJXV1
RN60CJXV1
RR71CXV1
RR71CXY1
Power supply cable size
Number of wire
mm
2
2.5
3
2.5
3
2.5
3
1.5
5
Interconnection cable size
Number of wire
mm
2
2.5
3
2.5
3
2.5
3
1.5
4
Recommended fuse
A
20
20
20
15
Model Unit
FTYN20JXV1
FTYN25JXV1
FTYN35JXV1
RYN20CGXV1
RYN25CJXV1
RYN35CJ(H)XV1
Power supply cable size
Number of wire
mm
2
1.5
3
1.5
3
1.5
3
Interconnection cable size
Number of wire
mm
2
1.5
5
1.5
3
1.5
3
Recommended fuse
A
15
15
15
Model Unit
FTYN50JXV1
FTYN60JXV1
FTYN80FXV1
RYN50CJXV1
RYN60CJXV1
RQ71CXV1
RQ71CXY1
Power supply cable size
Number of wire
mm
2
2.5
3
2.5
3
2.5
3
2
5
Interconnection cable size
Number of wire
mm
2
2.5
5
2.5
5
2.5
3
1.5
6
Recommended fuse
A
20
20
20
15
Summary of Contents for FTN25JXV1
Page 2: ......
Page 46: ...43 Wiring Diagram Indoor Unit Model FTN50 60JXV1 Outdoor Unit Model RN50 60CJXV1...
Page 47: ...44 Wiring Diagram Indoor Unit Model FTN80FXV1 Outdoor Unit Model RR71CXV1...
Page 48: ...45 Wiring Diagram Indoor Unit Model FTN80FXV1 Outdoor Unit Model RR71CXY1...
Page 49: ...46 Wiring Diagram Indoor Unit Model FTYN20JXV1 Outdoor Unit Model RYN20CGXV1...
Page 51: ...48 Wiring Diagram Indoor Unit Model FTYN50 60JXV1 Outdoor Unit Model RYN50 60CJXV1...
Page 52: ...49 Wiring Diagram Indoor Unit Model FTYN80FXV1 Outdoor Unit Model RQ71CXV1...
Page 53: ...50 Wiring Diagram Indoor Unit Model FTYN80FXV1 Outdoor Unit Model RQ71CXY1...
Page 62: ......