Piping Works And Flaring Technique

Do not use contaminated or damaged copper tubing. If 
any piping, evaporator or condenser had been exposed or 
had been opened for 15 seconds or more, the system must 
be vacuumed. Generally do not remove plastic, rubber 
plugs and brass nuts from the valves, fittings, tubing and 
coils until it is ready to connect suction or liquid line into 
valves or fittings.
If any brazing work is required, ensure that nitrogen gas 
is passed through coil and joints while the brazing work 
is being done. This will eliminate soot formation on the 
inside wall of copper tubings.
Cut the pipe stages by stages, advancing the blade of pipe 
cutter slowly. Extra force and a deep cut will cause more 
distortion of pipe and therefore extra burr. See Figure I.
Remove burrs from cut edges of the pipes with remover. See 
Figure II. Hold the pipe on top position and burr remover 
at lower position to prevent metal chips from entering the 
pipe. This will avoid unevenness on the flare faces which 
will cause gas leak.
Insert the flare nuts, mounted on the connection parts 
of both the indoor unit and outdoor unit, into the copper 
pipes.
The exact length of pipe protruding from the top surface 
of the swaging block is determined by the flaring tool. 
See Figure III.
Fix the pipe firmly on the swaging block. Match the centers 
of both the swaging block and the flaring punch, then 
tighten the flaring punch fully.

Piping Connection To The Units

Align the center of the piping and tighten the flare nut 
sufficiently with fingers. See Figure IV.
Finally, tighten the flare nut with torque wrench until the 
wrench clicks.
When tightening the flare nut with the torque wrench, 
ensure that the tightening direction follows the arrow 
indicated on the wrench.
The refrigerant pipe connection are insulated by closed 
cell polyurethane.

1/4t

Cutting Copper Tube

Copper Tube

Swaging Block

Remove Burr

Copper Tube

Figure I

D

A

Pipe Size mm/(in)

Torque Nm/(ft-Ib)

6.35 (1/4")

18 (13.3)

9.52 (3/8")

42 (31.0)

15.88 (5/8") 

65 (48.0)

Flared Tube

Flare Joint

Flare Nut

Indoor Piping

Torque Wrench

Spanar

Ø Tube, D

A (mm)

Inch

mm

Imperial 

(Wing-nut Type)

Rigid 

(Clutch Type)

1/4"

6.35

1.3

0.7

3/8"

9.52

1.6

1.0

5/8"

15.88

2.2

1.7

Figure II

Figure III

Figure IV

1-EN-IM WMJ-1111(0)Daikin.indd   8

11/29/11   2:04:43 PM

Summary of Contents for FTD20JEV1K

Page 1: ...INSTALLATION MANUAL MODELS FTD20JEV1K RD20JEV1K FTD25JEV1K RD25JEV1K R22 SPLIT SERIES English Installation Manual R22 Split Series IM WMJ 1111 0 DAIKIN Part No R08019033301...

Page 2: ......

Page 3: ...E TERMINAL BLOCK WITH EARTH TERMINAL All dimensions are in mm Original Instruction OUTLINE AND DIMENSIONS D B G H J L M A K F I G F E Through the wall hole 65mm Drain hose position Liquid pipe end Gas...

Page 4: ...mm Outdoor Unit Dimension Model A B C D E F G H I J K L M N O RD20JEV1K 855 628 328 520 181 44 93 149 101 113 603 126 164 17 34 RD25JEV1K 855 730 328 520 182 44 93 149 101 113 603 126 164 17 34 Dimen...

Page 5: ...useinroomwheremineraloil oilvapour or oil steam exist this may cause plastic part to melt or deform as a result of excessive heat or chemical reaction When the unit is used in kitchen keep flour away...

Page 6: ...the smooth air flow Please follow the installation clearances shown in the figure Select the coolest possible place where intake air temperature is not greater than the outside air temperature please...

Page 7: ...to the required position in order to align it with the holes For the side and bottom hold the bottom of the piping and then position it to the required direction see figure The condensation drain hose...

Page 8: ...indoor unit with the upper edge of the installation plate Ensure that the hooks are properly seated on the installation plate by moving it to the left and right How To Attach The Indoor Unit Hook the...

Page 9: ...iquid Pipe Size mm in 6 35 1 4 9 52 3 8 L E Remark The refrigerant pre charged in the outdoor unit is for piping length up to 7 5m Be sure to add the proper amount of additional refrigerant Failure to...

Page 10: ...cause gas leak Insert the flare nuts mounted on the connection parts of both the indoor unit and outdoor unit into the copper pipes The exact length of pipe protruding from the top surface of the swa...

Page 11: ...d All wires must not touch the refrigerant piping compressor or any moving parts of the fan motor The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps T...

Page 12: ...vacuum pump Evacuate for approximately 30 minutes The evacuation time varies with different vacuum pump capacity Confirm that the charging gauge needle has moved towards 760mmHg Caution If the gauge...

Page 13: ...Indicator Lights for Cooling Unit IR Receiver Cooling Unit The table shows the LED indicator lights for the air conditioner unit under normal operation and fault conditions The LED indicator lights ar...

Page 14: ...e Room air sensor contact Loose Short Call your dealer Blink E1 3 times Outdoor coil sensor open Call your dealer Blink E3 2 times Indoor coil sensor open Call your dealer Blink E2 1 time Compressor o...

Page 15: ...occur on the louver thus resulting in drippings Frost Prevention When the air lter is dirty the evaporating temperature will decrease and eventually cause frosting If the evaporating temperature reach...

Page 16: ...e old Bio Filter as nonflammable garbage after use Operation with dirty filters 1 cannot deodorize the air 3 results in poor heating or cooling 2 cannot clean the air 4 may cause odour To order Bio Fi...

Page 17: ...eft and pull it to the front side to remove it 2 Attach the front panel Align the right and left rotating shafts of the front panel with the grooves and push them all the way in Gently close the front...

Page 18: ...been set incorrectly If the fault persist after all these verifications please contact the air conditioner unit installer The air flow is too low 3 The air filter is dirty The doors or windows are ope...

Page 19: ......

Page 20: ...fication and design contain herein at any time without prior notification Lot 60334 Persiaran Bukit Rahman Putra 3 Taman Perindustrian Bukit Rahman Putra 47000 Sungai Buloh Selangor Darul Ehsan Malays...

Reviews: