background image

FMDQ50~125A7V3B
Air conditioning system
4PW47630-1

Installation and operation manual

6

W

IRING

 

EXAMPLE

 

AND

 

HOW

 

TO

 

SET

 

THE

 

REMOTE

 

CONTROLLER

How to connect wiring

From the outside of the unit

Remove the switch box cover as shown in 

figure 11b

, and make the

connections.

From the inside of the unit

Remove the small bottom plate and the interchangeable plate (in
case of rear suction) or the air filter holding plate (in case of bottom
suction). Lower the switch box as shown in 

figure 11c

Put the wires

through the wiring ports of the switch box cover before connecting
them.

PRECAUTIONS

1

Observe the notes mentioned below when wiring to the power
supply terminal board.

-

Do not connect wires of different gauge to the same power 
supply terminal. (Looseness in the connection may cause 
overheating.)

-

When connecting wires of the same gauge, connect them 
according to the figure.

2

Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal board of the unit
in accordance with electrical equipment standards, when using
two power wiring of a gauge greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

4

Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.

5

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

6

Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire
system.

7

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the switch box
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire.

Setting of static pressure changeover connector

According to the systems static pressure requirement, reposition
the adaptors of the PC board inside the switch box as shown in
the figure.

W

IRING

 

EXAMPLE

Fit the power supply wiring of each unit with a switch and fuse as
shown in 

figure 17

.

Complete system example (2 systems)

When using 1 remote controller for 1 indoor unit (Normal operation)

(See figure 15)

For group control or use with 2 remote controllers 

(See figure 16)

1

Small bottom plate

2

Air filter holding plate

3

Switch box

4

Interchangeable plate

5

Square hole (covered by the switch box cover)

60

FMDQ71~125

Low

not available

Standard

High

1

Black wire

2

Blue wire

NOTE

The unit is factory set for standard static pressure
(X4A) at the time of shipping.

1

Power supply

2

Main switch

3

Power supply wiring

4

Transmission wiring

5

Switch

6

Fuse

7

Indoor unit

8

Remote controller

1

Outdoor unit

2

Indoor unit

3

Remote controller (optional accessories)

4

Most downstream indoor unit

5

For use with 2 remote controllers

NOTE

It is not necessary to designate an indoor unit address
when using group control. The address is
automatically set when the power is activated.

X6A

X7A

X5A

X4A

X3A

1

2

X6A

X7A

X5A

X4A

X3A

1

2

X7A

X4A

X3A

1

2

X6A

X7A

X5A

X4A

X3A

1

2

X7A

X4A

X3A

1

2

Summary of Contents for FMDQ50A7V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FMDQ50A7V3B FMDQ60A7V3B FMDQ71A7V3B FMDQ100A7V3B FMDQ125A7V3B Air conditioning system...

Page 2: ...2 5 6 7 4 3 4 4 1 3 2 4 5 5 5 2 1 2 3 6a 6a 2 3 1 4 680 85 6b 6b 1 3 2 4 6 5 50 200 45 680 6c 6c 1 5 2 3 7 4 680 65 3 3 1 4 3 4 2 800 630 B A 145 7c 7c 4 2 2 3 1 460 180 350 A 8 8 1 1 5m 0 625mm 2 6...

Page 3: ...12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo te...

Page 4: ...volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near...

Page 5: ...age interference and noise in those electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if 1 meter is kept 2 Use suspension bolts f...

Page 6: ...ides of the hanger bracket See figure 5 2 Check if the unit is horizontally levelled Do not install the unit tilted The indoor unit is equipped with a built in drain pump and float switch If the unit...

Page 7: ...nside the building If the drain hose cannot be sufficiently set on a slope fit the hose with drain raising piping field supply HOW TO PERFORM PIPING See figure 8 Connect the drain hose to the drain ra...

Page 8: ...ndoor unit are mismatched the system may cause a malfunction Electrical characteristics MCA Min circuit Amps A MFA Max Fuse Amps A KW Fan Motor Rated Output kW FLA Full Load Amps A Specifications for...

Page 9: ...mote controller supplied with the remote controller 6 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 7 Use only specifi...

Page 10: ...to half the time inbetween 2 filter cleaning display indications Ultra long life filter Light 10 000 hrs Heavy 5 000 hrs Long life filter 2 500 hrs 1 250 hrs Standard filter 200 hrs 100 hrs 2 Thermos...

Page 11: ...installed in a room where the air is extremely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom...

Page 12: ...et are not blocked Remove any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main power supply switch...

Page 13: ...ADAPTOR FOR WIRING RyC RyF MAGNETIC RELAY RyH MAGNETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTOR...

Page 14: ...NOTES NOTES...

Page 15: ...1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 3 4 2 1 13 12 2 2 1 14 16 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P...

Page 16: ...4PW47630 1 Copyright Daikin...

Reviews: