FMDQ50~125A7V3B
Air conditioning system
4PW47630-1

Installation and operation manual

2

For the following items, take special care during 
construction and check after installation is finished

Notes to the installer

Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the system
and show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.

I

MPORTANT

 

INFORMATION

 

REGARDING

 

THE

 

REFRIGERANT

 

USED

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

(1)

 GWP = global warming potential

Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.

S

ELECTING

 

INSTALLATION

 

SITE

(See 

figure 1

 and 

figure 2

)

1

Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.

-

Where optimum air distribution can be ensured.

-

Where nothing blocks air passage.

-

Where condensate water can be properly drained.

-

Where the false ceiling is not noticeably on an incline.

-

Where sufficient clearance for maintenance and service can 
be ensured.

-

Where piping between indoor and outdoor units is possible 
within the allowable limit. (Refer to the installation manual of 
the outdoor unit.)

-

This is a class A product. In a domestic environment this 
product may cause radio interference in which case the user 
may be required to take adequate measures.

-

Keep indoor unit, outdoor unit, power supply wiring and 
transmission wiring at least 1 meter away from televisions 
and radios. This is to prevent image interference and noise in 
those electrical appliances. (Noise may be generated 
depending on the conditions under which the electric wave is 
generated, even if 1 meter is kept.)

2

Use suspension bolts for installation. Check whether the ceiling
is strong enough to support the weight of the indoor unit. If there
is a risk, reinforce the ceiling before installing the unit.

P

REPARATIONS

 

BEFORE

 

INSTALLATION

1

Relation of ceiling opening to unit and suspension bolt position.

(See figure 3)

For installation, choose one of the possibilities as listed further.

Standard rear suction 

(See figure 6a)

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 
name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 
outdoor units?

It may result in insufficient cooling.

Are refrigerant piping length and additional refrigerant charge 
noted down?

The refrigerant charge in the system might not be clear.

Are the air filters fixed properly (when installing with rear duct)?

Maintenance of the air filters can be impossible.

1

Service space 

300

2

Drain pipe

3

Power supply wiring port

4

Transmission wiring port

5

Maintenance drain outlet

6

Gas pipe

7

Liquid pipe

Model

A

B

FMDQ50

700

750

FMDQ60

1000

1050

FMDQ71~125

1400

1450

1

Indoor unit

2

Pipe

3

Suspension bolt pitch (x4)

4

Suspension bolt pitch distance

1

Ceiling surface

2

Ceiling opening

3

Service access panel (optional accessory)

4

Air filter

5

Air inlet duct

6

Duct service opening

7

Interchangeable plate

Summary of Contents for FMDQ50A7V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FMDQ50A7V3B FMDQ60A7V3B FMDQ71A7V3B FMDQ100A7V3B FMDQ125A7V3B Air conditioning system...

Page 2: ...2 5 6 7 4 3 4 4 1 3 2 4 5 5 5 2 1 2 3 6a 6a 2 3 1 4 680 85 6b 6b 1 3 2 4 6 5 50 200 45 680 6c 6c 1 5 2 3 7 4 680 65 3 3 1 4 3 4 2 800 630 B A 145 7c 7c 4 2 2 3 1 460 180 350 A 8 8 1 1 5m 0 625mm 2 6...

Page 3: ...12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo te...

Page 4: ...volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near...

Page 5: ...age interference and noise in those electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if 1 meter is kept 2 Use suspension bolts f...

Page 6: ...ides of the hanger bracket See figure 5 2 Check if the unit is horizontally levelled Do not install the unit tilted The indoor unit is equipped with a built in drain pump and float switch If the unit...

Page 7: ...nside the building If the drain hose cannot be sufficiently set on a slope fit the hose with drain raising piping field supply HOW TO PERFORM PIPING See figure 8 Connect the drain hose to the drain ra...

Page 8: ...ndoor unit are mismatched the system may cause a malfunction Electrical characteristics MCA Min circuit Amps A MFA Max Fuse Amps A KW Fan Motor Rated Output kW FLA Full Load Amps A Specifications for...

Page 9: ...mote controller supplied with the remote controller 6 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 7 Use only specifi...

Page 10: ...to half the time inbetween 2 filter cleaning display indications Ultra long life filter Light 10 000 hrs Heavy 5 000 hrs Long life filter 2 500 hrs 1 250 hrs Standard filter 200 hrs 100 hrs 2 Thermos...

Page 11: ...installed in a room where the air is extremely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom...

Page 12: ...et are not blocked Remove any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main power supply switch...

Page 13: ...ADAPTOR FOR WIRING RyC RyF MAGNETIC RELAY RyH MAGNETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTOR...

Page 14: ...NOTES NOTES...

Page 15: ...1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 3 4 2 1 13 12 2 2 1 14 16 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P...

Page 16: ...4PW47630 1 Copyright Daikin...

Reviews: