background image

4

REFRIGERANT PIPING WORK

For refrigerant piping of outdoor unit, refer to the installation
manual supplied with the outdoor unit.
Before rigging tubes, check which type of refrigerant is used.

All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.

Use a pipe cutter and flare suitable for the used refrigerant.

If R407C refrigerant is used, apply ether oil or ester oil around
the flare portions before connecting.

To prevent dust, moisture or other foreign matter from
infiltrating the tube, either pinch the end, or cover it with tape.

The outdoor unit is charged with refrigerant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

Do not mix anything other than the specified refrigerant, such
as air, etc.., inside the refrigerant circuit.

Refer to Table 1 for the dimensions of flare nut spaces and
the appropriate tightening torque. (Overtightening may
damage the flare and cause leaks.)

Table 1

Pipe gauge

Tightening torque

Flare dimension A

Flare shape

(mm)

Ø 6.4

1420~1720 N•cm

8.3~8.7

(144~176 kgf•cm)

Ø 9.5

3270~3990 N•cm

12.0~12.4

(333~407 kgf•cm)

Ø 12.7

4950~6030 N•cm

15.4~15.8

(504~616 kgf•cm)

Ø 15.9

6180~7540 N•cm

18.6~19.0

(630~770 kgf•cm)

Ø 19.1

9720~11860 N•cm

22.9~23.3

(990~1210 kgf•cm)

When connecting the flare nut, coat the flare both inside and
outside with refrigerating machine oil and initially tighten by
hand 3 or 4 turns before tightening firmly.

1

Coat here with refrigerating
machine oil

 • Check the pipe connector for gas leaks, then insulate it as

shown in the figure below.

1

Liquid pipe

2

Gas pipe

3

Insulation for fitting of liquid line
(supplied with the unit)

4

Insulation for fitting of gas line
(supplied with the unit)

5

Clamps (use 2 clamps
per insulation)

If the refrigerant gas leaks during the work, ventilate the area.
A toxic gas is emitted by the refrigerant gas being exposed to
a fire.

Finally make sure there is no refrigerant gas leak. A toxic gas
may be released by the refrigerant gas leaking indoor and
being exposed to flames from an area heater, cooking stove,
etc.

DRAIN PIPING WORK

Rig the drain piping as shown in figure and take measures
against condensation. Improperly rigged piping could lead to
leaks and eventually wet furniture and belongings.

1

Hanging bar

1. Install the drain pipes.

Keep piping as short as possible and slope it downwards
so that air may not remain trapped inside the pipe.

Keep pipe size equal to or greater than that of the
connecting pipe (Vinyl pipe of 25mm nominal diameter and
32mm outer diameter).

Insert the supplied drain hose into the drain socket, up to
the white tape.

Tighten the clamp until the screw head is less then 4mm
from the hose.

1

Clamp metal
(supplied with the unit)

2

Drain hose
(supplied with the unit)

3

White tape (field supply)

Insulate the drain piping inside the building.

If the drain hose cannot be sufficiently set on a slope, fit
the hose with drain raising piping (field supply).

HOW TO PERFORM PIPING (see figure 8)

1

Ceiling slab

2

Hanger bracket

3

Adjustable range

4

Drain raising pipe

5

Drain hose (supplied with the unit)

6

Clamp metal (supplied with the unit)

1 Connect the drain hose to the drain raising pipes, and insulate

them.

2 Connect the drain hose to the drain outlet on the indoor unit,

and tighten it with the clamp.

PRECAUTIONS

Instal the drain raising pipes at a height of less than 550mm.

Install the drain raising pipes at a right angle to the indoor unit
and no more than 300mm from the unit.

1

1-1.5m

2

1

3

5

4

2

1

3

R0.4~0.8

45

° ±

2

90

°±

0.5

A

2

3

1

4

1

1

Summary of Contents for FHC35B7V1

Page 1: ...onditioners FHC35BZ7V1 FHC45BZ7V1 FHC60BZ7V1 FHYC35BZ7V1 FHYC45BZ7V1 FHYC35B7V1 FHYC45B7V1 FHYC60B7V1 FHYC71B7V1 FHYC100B7V1 FHYC125B7V1 FHYCP35B7V1 FHYCP45B7V1 FHYCP60B7V1 FHYCP71B7V1 FHYCP100B7V1 FH...

Page 2: ...vore instrukser respektive utrustning r utf rd i verensst mmelse med och f ljer f ljande standard er eller andra normgivande dokument under f ruts ttning att anv ndning sker i verensst mmelse med v r...

Page 3: ...100 mm 1 3 2 5 4 1 7 6 100 12 13 8 9 7 6 3 4 5 1 2 1 840 910 840 910 1 2 3 4 5 1 50 100 1500 1500 1000 H 1 1 2 8 3 1 4 6 7 5 2 1500 1500 H 1 1 2 4 2 5 6 3 860 860 910 20 20 35 35 1 2 3 1 3 2 1 10mm 2...

Page 4: ...15 14 17 18 1 2 3 4 7 6 8 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 6 1 2 3 4 5 6 S M S S M 2 3 1 20 21 22 SETTING 2 4 3 1 1 2 3 4 7 7 8 1 2 3 4 5 6 8 19 16...

Page 5: ...outdoor units must be designed exclusively for R407C If outdoor units for R22 are connected the system will not work properly Washer for hanging bracket 8 pcs for gas pipe for liquid pipe Insulation...

Page 6: ...lation pitch is marked on the paper pattern for installation Refer to it to check for points requiring reinforcing Space required for installation see figure 2 air flow direc tion 1 Air discharge 2 Ai...

Page 7: ...ion tightly around the hole of the unit as shown The ends of the side plate and the inner insulation must be completely adhered without leaving any clearance along the circumference of the hole Make s...

Page 8: ...tting of liquid line supplied with the unit 4 Insulation for fitting of gas line supplied with the unit 5 Clamps use 2 clamps per insulation If the refrigerant gas leaks during the work ventilate the...

Page 9: ...converging drain pipes 2 After piping work is finished check if drainage flows smoothly Open the water inlet lid add approximately 2l of water gradually and check the drainage flow Method of adding w...

Page 10: ...than 2mm2 1 6 The branch must be sheathed in order to provide an equal or greater degree of insulation as power supply wiring itself 3 Do not connect wires of different gauge to the same grounding te...

Page 11: ...performance filters refer to the option handbook of the high performance filters Setting air filter sign Remote controllers are equipped with liquid crystal air filter signs to display the time to cle...

Page 12: ...RUCTION AND CHECK AFTER INSTALLATION IS FINISHED p 2 After finishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit TEST...

Page 13: ...MITTING DIODE SERVICE MONITOR RED H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN H3P LIGHT EMITTING DIODE SERVICE MONITOR RED H4P LIGHT EMITTING DIODE SERVICE MONITOR ORANGE SS1 SELECTOR SWITCH MAIN S...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW10740 1...

Reviews: