Daikin FHC35B7V1 Installation Manual Download Page 10

6

WIRING EXAMPLE AND HOW TO SET THE
REMOTE CONTROLLER

How to connect wiring (see figure 13)

Power supply wiring
Remove the switch box lid (1) and connect the wires to the
power supply terminal board inside. While doing this, pull the
wires inside through the rubber bush A and clamp the wires
along with other wires using clamp A, untightening the clip of
clamp A by pressing. After the connection, tighten clamp A as
before.

Unit wiring and remote controller wiring
Remove the switch box lid (2) and pull the wires inside
through the rubber bush B and connect to the terminal board
for unit transmission wiring.

After connection
Attach the small sealing (supplied with the unit) around the
cables to prevent infiltrating of water from the outside into the
unit. If two or more cables are used, divide the small sealing
into the required number of pieces and wrap them around all
the cables.

1

Switch box lid (1)

2

Power supply

3

Power supply terminal board

4

Rubber bush A

5

Clamp A

6

Switch box lid (2) with wiring diagram label

7

Transmission wiring

8

Terminal board for transmission wiring

9

Rubber bush B

10

Clamp B

11

Outside of the unit

12

Inside of the unit

13

Cable (power supply or transmission wiring)

14

Opening for the cable

15

Small sealing

PRECAUTIONS

1 Observe the notes mentioned below when wiring to the power

supply terminal board.

Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)

When connecting wires of the same gauge, connect them
according to the figure.

Use the specified electric wire. Connect the wire securely
to the terminal. Lock the wire down without applying
excessive force to the terminal. (Tightening torque:
131Ncm 

±

10%).

2 Keep total current of crossover wiring between indoor units

less than 12A. Branch the line outside the terminal board of
the unit in accordance with electrical equipment standards,
when using two power wiring of a gauge greater than 2mm

2

(Ø1.6).
The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3 Do not connect wires of different gauge to the same

grounding terminal. Looseness in the connection may
deteriorate the protection.

4 Remote controller cords and wires connecting the units

should be located at least 50mm away from power supply
wiring. Not following this guideline may result in malfunction
due to electrical noise.

5 For the remote controller wiring, refer to the "Installation

manual of the remote controller" supplied with the remote
controller.

Note

 

The customer has the ability to select the remote controller
thermistor (only for FHYCP35~125B7V1).

6 Never connect the power supply wiring to the terminal board

for transmission wiring. This mistake could damage the entire
system.

7 Use only specified wires and tightly connect wires to the

terminals. Be careful that wires do not place external stress
on the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete
connections could result in overheating, and in the worse
case, electric shock or fire.

WIRING EXAMPLE

For the wiring of outdoor units, refer to the installation manual
attached to the outdoor units.

Confirm the system type:

Pair type: 1 remote controller controls 1 indoor unit (standard
system).

Simultaneous operation system: 1 remote controller controls
2 indoor units (2 indoor units operate equally)

Group control: 1 remote controller controls up to 16 indoor
units (All indoor units operate according to the remote
controller).

2 remote controller control: 2 remote controllers control 1
indoor unit.

Pair type (figure 15)

Simultaneous operation system (figure 16)

Group control (figure 17)

2 remote controller control (figure 18)

1

Main power supply

2

Main switch

3

Fuse

4

Outdoor unit

5

Indoor unit

6

Remote controller (optional accessories)

7

Indoor unit (Master)

8

Indoor unit (Slave)

NOTE

It is not necessary to designate indoor unit address when
using group control. The address is automatically set when
the power is activated.

Summary of Contents for FHC35B7V1

Page 1: ...onditioners FHC35BZ7V1 FHC45BZ7V1 FHC60BZ7V1 FHYC35BZ7V1 FHYC45BZ7V1 FHYC35B7V1 FHYC45B7V1 FHYC60B7V1 FHYC71B7V1 FHYC100B7V1 FHYC125B7V1 FHYCP35B7V1 FHYCP45B7V1 FHYCP60B7V1 FHYCP71B7V1 FHYCP100B7V1 FH...

Page 2: ...vore instrukser respektive utrustning r utf rd i verensst mmelse med och f ljer f ljande standard er eller andra normgivande dokument under f ruts ttning att anv ndning sker i verensst mmelse med v r...

Page 3: ...100 mm 1 3 2 5 4 1 7 6 100 12 13 8 9 7 6 3 4 5 1 2 1 840 910 840 910 1 2 3 4 5 1 50 100 1500 1500 1000 H 1 1 2 8 3 1 4 6 7 5 2 1500 1500 H 1 1 2 4 2 5 6 3 860 860 910 20 20 35 35 1 2 3 1 3 2 1 10mm 2...

Page 4: ...15 14 17 18 1 2 3 4 7 6 8 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 6 1 2 3 4 5 6 S M S S M 2 3 1 20 21 22 SETTING 2 4 3 1 1 2 3 4 7 7 8 1 2 3 4 5 6 8 19 16...

Page 5: ...outdoor units must be designed exclusively for R407C If outdoor units for R22 are connected the system will not work properly Washer for hanging bracket 8 pcs for gas pipe for liquid pipe Insulation...

Page 6: ...lation pitch is marked on the paper pattern for installation Refer to it to check for points requiring reinforcing Space required for installation see figure 2 air flow direc tion 1 Air discharge 2 Ai...

Page 7: ...ion tightly around the hole of the unit as shown The ends of the side plate and the inner insulation must be completely adhered without leaving any clearance along the circumference of the hole Make s...

Page 8: ...tting of liquid line supplied with the unit 4 Insulation for fitting of gas line supplied with the unit 5 Clamps use 2 clamps per insulation If the refrigerant gas leaks during the work ventilate the...

Page 9: ...converging drain pipes 2 After piping work is finished check if drainage flows smoothly Open the water inlet lid add approximately 2l of water gradually and check the drainage flow Method of adding w...

Page 10: ...than 2mm2 1 6 The branch must be sheathed in order to provide an equal or greater degree of insulation as power supply wiring itself 3 Do not connect wires of different gauge to the same grounding te...

Page 11: ...performance filters refer to the option handbook of the high performance filters Setting air filter sign Remote controllers are equipped with liquid crystal air filter signs to display the time to cle...

Page 12: ...RUCTION AND CHECK AFTER INSTALLATION IS FINISHED p 2 After finishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit TEST...

Page 13: ...MITTING DIODE SERVICE MONITOR RED H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN H3P LIGHT EMITTING DIODE SERVICE MONITOR RED H4P LIGHT EMITTING DIODE SERVICE MONITOR ORANGE SS1 SELECTOR SWITCH MAIN S...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW10740 1...

Reviews: