1-6

Ensure a location where:

Drainage can be done easily.
Convenient for wiring and piping.
Which have enough space for installation and service work.
Where no risk of 

Á

 ammable gas leakage.

 When free from any obstacles in path of cool air discharge and warm air return and must allow spreading of air 
throughout the room (near the center of the room).
Must be provided clearance for indoor unit from the wall and obstacles as shown in 

À

 gure below.

 The installation place must be strong enough to support a load 4 times the indoor unit weight to avoid amplifying 
noise and vibration.
 The installation place (hanging ceiling surface) must be assuring levelness and the height in the ceiling is 350mm or 
more.
The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).

a)
b)
c)
d)
e)

f)
g)

h)

i)

Unit Installation

Measure and mark the position for the hanging rod. 
Drill the hole for the angle nut on the ceiling and fix the 
hanging rod.
The installation template is extended according to 
temperature and humidity. Check on dimensions in use.
The dimensions of the installation template are the same 
as those of the ceiling opening dimensions.
Before ceiling laminating work is completed, be sure to 
fit the installation template to the indoor unit.

NOTE

Be sure to discuss the ceiling drilling work with the 
installers concerned.

Unit Hanging

Confirm the pitch of the hanging rod is 770mm x 622mm 
sharp.
Hold the unit and hang it on the hanging rod with the nut 
and washer.
Adjust the unit height to 30mm between the indoor unit 
bottom surface and the ceiling surface.
Confirm with a level gauge that the unit is installed 
horizontally and tighten the nut and bolt to prevent unit 
falling and vibration.
Open the ceiling board along the outer edge of the paper 
installation template.

Unit size 820mm

Piping Direction

Ceiling Opening Site = 890mm

Ceiling Opening Site = 890mm

Hanging Rod Site = 790mm

Unit size 820mm

Unit

Indoor Unit

30 mm

Ceiling 

Board

Hanging rod size = 621mm

EN CKE-0911(0)DK(saso).indd   6

12/6/11   3:05:08 PM

Summary of Contents for FHC20JEVLK

Page 1: ...DAIKIN SASO Part No R08019037002 MODELS FHC20JEVLK RD20JEVLK FHC25JEVLK RD25JEVLK FHC30JEVLK RD30JEVLK FHC40JEVLK RD40JEVLK FHC50JEVLK RD50JETLK FHYC20JEVLK RYD20JEVLK FHYC25JEVLK RYD25JEVLK FHYC30JE...

Page 2: ......

Page 3: ...L R Y D20JEVLK 855 628 328 520 179 46 93 149 101 113 603 126 R Y D25 30JEVLK 855 730 328 520 179 46 93 149 101 113 603 126 Dimension Model M N O P Q R S R Y D20JEVLK 164 15 34 23 362 73 75 R Y D25 30...

Page 4: ...2 Outdoor Unit All dimensions are in mm I J J D M E B G O Dimension Model A B C D E F G H I J K L M N O R Y D40JEVLK R Y D50JETLK 1030 826 400 410 57 72 90 40 746 142 60 26 448 22 28 N N K A L E F H...

Page 5: ...orted pictures and static Depending on the type and source of the electrical waves static may be heard even when more than 1m away Please take note of the following important points when installing Do...

Page 6: ...box from the top side of the unit This product is not designed for re packing In case of re packing contact to Daikin Dealer C K U N K E E P B A R For model FH Y C20 25 30 40 50JEVLK Carton Box Top 1...

Page 7: ...t pressure on the resin parts when opening the unit or when moving it after opening Do not move the unit from packaging while moving until it reaches the installation site Use safe material or protect...

Page 8: ...ole for the angle nut on the ceiling and fix the hanging rod The installation template is extended according to temperature and humidity Check on dimensions in use The dimensions of the installation t...

Page 9: ...ompleted connect the flexible drain hose to the drain connector on the indoor unit Drain Test NOTE This Indoor Unit uses a drain pump for condensed water drainage Install the unit horizontally to prev...

Page 10: ...l be followed Con rm that the unit had been switched off before servicing the unit Use screwdriver to unlock the screw on the grille lock cover Remove the grille lock cover and open the intake grille...

Page 11: ...l power supply wires and wires from outdoor unit Remove wire cover by removing 2 screws as shown in Figure C Wires will go through the hole as shown in Figure D and E respectively without crossing the...

Page 12: ...Allow sufficient space for maintenance around the unit Ensure that there is no obstruction of air ow into or out of the unit Remove obstacles which block air intake or discharge The location must be w...

Page 13: ...Obstacle Obstacle Service Space Obstacle C D Obstacle REFRIGERANT PIPING Maximum Allowable Pipe Length and Elevation If the piping is too long both the capacity and reliability of unit will drop As t...

Page 14: ...t the flare nuts mounted on the connection parts of both the indoor unit and outdoor unit into the copper pipes The exact length of pipe protruding from the top surface of the swaging block is determi...

Page 15: ...or 220V 1Ph 60Hz Power supply cable size mm2 Number of conductors 4 0 3 Interconnection cable size mm2 Number of conductors 2 5 4 Recommended time delay fuse A 30 There must be an all pole disconnecti...

Page 16: ...ge range Indoor 220V 1Ph 60Hz Outdoor 220V 3N 60Hz Power supply cable size mm2 Number of conductors 6 0 3 Interconnection cable size mm2 Number of conductors 2 5 4 Recommended time delay fuse A 35 The...

Page 17: ...N Indoor Unit Terminal Block Interconnection Cable Outdoor Unit Terminal Block Power Supply Cable Model Indoor FHYC30JEVLK Outdoor RYD30JEVLK Voltage range Indoor 220V 1Ph 60Hz Outdoor 220V 1Ph 60Hz P...

Page 18: ...uctors 2 5 4 3 Recommended time delay fuse A 35 Model Indoor FHYC40JEVLK Outdoor RYD40JEVLK Voltage range Indoor 220V 1Ph 60Hz Outdoor 220V 1Ph 60Hz Power supply cable size mm2 Number of conductors 6...

Page 19: ...for connecting wires to the power supply terminal block Connect the wires by matching to the indication on terminal block Refer to the wiring diagram attached on the unit Use the correct screwdriver...

Page 20: ...the suction valve 3 way and liquid valve 2 way in anti clockwise direction with 4mm key for hexagon sacked screw Charge Operation This operation must be done by using a gas cylinder and a precise wei...

Page 21: ...FHC30JEVLK FHC40JEVLK Outdoor RD30JEVLK RD40JEVLK Additional charge g m 57 40 Model Indoor FHC50JEVLK Outdoor RD50JETLK Additional charge g m 58 Heat Pump Unit Model Indoor FHYC20JEVLK FHYC25JEVLK Ou...

Page 22: ...Minimal equipment is required for field charging The minimum equipment required to do a satisfactory job is Set of service gauges 1 Vacuum gauge 4 Hoses 2 Scales 5 Vacuum pump 3 Thermometer 6 The prop...

Page 23: ...o that it does not touch the air louver Be sure not to push the sealing material in any farther than about 10mm There are many ways of charging liquid in a controlled manner into the suction side Use...

Page 24: ...Code 1 Room Sensor Open or Short Blink 1 time Blink Fan Blink E1 2 Indoor Coil Sensor Open Blink 2 times Blink Sleep Blink E2 3 Outdoor Coil Sensor Open Blink 3 times Blink Dry Blink E3 4 Compressor...

Page 25: ...r phase protector under normal operation and fault conditions NOTE 1 indicates additional functions for PP01 phase protector 2 When R phase missing no LED or buzzer will indicate the error but relay 7...

Page 26: ...power plug is disconnected It is possible that your delay timer has been set incorrectly The air flow is too low 3 The air filter is dirty The air suction and discharge are clogged The regulated temp...

Page 27: ...o Daikin Dealer Additional refrigerant charge of 0 2kg is needed in order to achieve the stated performance data MODEL INDOOR UNIT FHYC20JEVLK FHYC25JEVLK OUTDOOR UNIT RYD20JEVLK RYD25JEVLK RATED VOLT...

Page 28: ...OUNTRY OF ORIGIN INDOOR UNIT Malaysia OUTDOOR UNIT Malaysia MODEL INDOOR UNIT FHYC30JEVLK FHYC40JEVLK OUTDOOR UNIT RYD30JEVLK RYD40JEVLK RATED VOLTAGE V 220 220 RATED FREQUENCY Hz 60 60 COOLING T1 IND...

Page 29: ...RANT R22 kg 2 60 COUNTRY OF ORIGIN INDOOR UNIT Malaysia OUTDOOR UNIT Malaysia MODEL INDOOR UNIT FHYC50JEVLK OUTDOOR UNIT RYD50JETLK RATED VOLTAGE V 220 RATED FREQUENCY Hz 60 COOLING T1 INDOOR 27DB C 1...

Page 30: ...MEMO...

Page 31: ......

Page 32: ...revise any of the speci cation and design contain herein at any time without prior noti cation Lot 60334 Persiaran Bukit Rahman Putra 3 Taman Perindustrian Bukit Rahman Putra 47000 Sungai Buloh Selang...

Reviews: