background image

1-21

English

OPTIONAL FUNCTIONS

Short Duct Speci

À

 cation

The indoor unit is provided with air discharge and air intake “knock-out” hole for duct connection. However the connection 
of the short duct for air discharge is possible on only one side.
The use of short duct for air discharge will improve airflow distribution if there is an obstruction (such as a lighting fixture) 
or in a long, narrow room or an L-shaped room. It also use for air conditioning of two rooms simultaneously.

Possible Direction For Air Discharge And Air Intake

Possible Opening Dimension For Duct Connection

NOTE

Avoid using the short duct on which the air discharge grille can be completely closed, to prevent evaporator 
freezing.
In order to prevent condensation forming, be sure that there is sufficient thermal insulation and no leakage of cool air 
when installing the short duct.
Keep the introduction of fresh air intake within 20% of total air 

Á

 ow. Also provide a chamber and use a booster fan.

Sealing Material

It is possible to seal one of the four air discharge outlet. (sealing two or more air discharge outlet could cause a 
malfunction)
Remove the front panel and insert the sealing material into the air discharge outlet on the indoor unit to seal the air 
outlet.
The sealing material is the same length as the longer air discharge outlet. If it is desired to seal the shorter air discharge 
outlet, cut the sealing material to shorten it.
Push the sealing material in about 10mm beyond the bottom surface of the indoor unit so that it does not touch the air 
louver. Be sure not to push the sealing material in any farther than about 10mm.

There are many ways of charging liquid in a “controlled manner” into the 
suction side:-

Use valve A on the manifold gauge set
Use the valve on the refrigerant cylinder
Charge through a Shredder valve
Use a hose with a Shredder valve depressor
Charge into the suction side at some distance from the compressor
All of the above

1.
2.
3.
4.
5.
6.

Charging procedures – Three phase compressors

The fundamental procedure is the same as for single phase models but the compressor can run in the wrong direction on 
starting.
If this happens reverse any two phases and start again. Short term reverse rotation will not damage the compressor.
All Specter compressors have internal discharge temperature protectors which are very effective in preventing dangerously 
high discharge temperatures during charging. The protection module will trip and lock the compressor out for 30 minutes. 
It is not normally necessary to wait 30 minutes for the module to reset. When the compressor has cooled down the module 
can be reset by breaking the power supply to the control circuit. Very often the serviceman does not understand why the 
module tripped and uses a jumper wire to bypass it. He continues to charge the system and removes the jumper when 
charging is complete. The compressor may or may not run with the protector back in the circuit but it is certain that the 
compressor has been damaged and premature failure is inevitable.

2.

Air Discharge

Air Discharge

Air Discharge

Air Discharge

Air Intake

Air Discharge Knock Out Hole

Air Intake Knock 

Out Hole

10

50

50

50

50

50

10

20

70

20

90

Ø100

PCD Ø140

115

20

115

A

EN CKE-0911(0)DK(saso).indd   21

12/6/11   3:05:11 PM

Summary of Contents for FHC20JEVLK

Page 1: ...DAIKIN SASO Part No R08019037002 MODELS FHC20JEVLK RD20JEVLK FHC25JEVLK RD25JEVLK FHC30JEVLK RD30JEVLK FHC40JEVLK RD40JEVLK FHC50JEVLK RD50JETLK FHYC20JEVLK RYD20JEVLK FHYC25JEVLK RYD25JEVLK FHYC30JE...

Page 2: ......

Page 3: ...L R Y D20JEVLK 855 628 328 520 179 46 93 149 101 113 603 126 R Y D25 30JEVLK 855 730 328 520 179 46 93 149 101 113 603 126 Dimension Model M N O P Q R S R Y D20JEVLK 164 15 34 23 362 73 75 R Y D25 30...

Page 4: ...2 Outdoor Unit All dimensions are in mm I J J D M E B G O Dimension Model A B C D E F G H I J K L M N O R Y D40JEVLK R Y D50JETLK 1030 826 400 410 57 72 90 40 746 142 60 26 448 22 28 N N K A L E F H...

Page 5: ...orted pictures and static Depending on the type and source of the electrical waves static may be heard even when more than 1m away Please take note of the following important points when installing Do...

Page 6: ...box from the top side of the unit This product is not designed for re packing In case of re packing contact to Daikin Dealer C K U N K E E P B A R For model FH Y C20 25 30 40 50JEVLK Carton Box Top 1...

Page 7: ...t pressure on the resin parts when opening the unit or when moving it after opening Do not move the unit from packaging while moving until it reaches the installation site Use safe material or protect...

Page 8: ...ole for the angle nut on the ceiling and fix the hanging rod The installation template is extended according to temperature and humidity Check on dimensions in use The dimensions of the installation t...

Page 9: ...ompleted connect the flexible drain hose to the drain connector on the indoor unit Drain Test NOTE This Indoor Unit uses a drain pump for condensed water drainage Install the unit horizontally to prev...

Page 10: ...l be followed Con rm that the unit had been switched off before servicing the unit Use screwdriver to unlock the screw on the grille lock cover Remove the grille lock cover and open the intake grille...

Page 11: ...l power supply wires and wires from outdoor unit Remove wire cover by removing 2 screws as shown in Figure C Wires will go through the hole as shown in Figure D and E respectively without crossing the...

Page 12: ...Allow sufficient space for maintenance around the unit Ensure that there is no obstruction of air ow into or out of the unit Remove obstacles which block air intake or discharge The location must be w...

Page 13: ...Obstacle Obstacle Service Space Obstacle C D Obstacle REFRIGERANT PIPING Maximum Allowable Pipe Length and Elevation If the piping is too long both the capacity and reliability of unit will drop As t...

Page 14: ...t the flare nuts mounted on the connection parts of both the indoor unit and outdoor unit into the copper pipes The exact length of pipe protruding from the top surface of the swaging block is determi...

Page 15: ...or 220V 1Ph 60Hz Power supply cable size mm2 Number of conductors 4 0 3 Interconnection cable size mm2 Number of conductors 2 5 4 Recommended time delay fuse A 30 There must be an all pole disconnecti...

Page 16: ...ge range Indoor 220V 1Ph 60Hz Outdoor 220V 3N 60Hz Power supply cable size mm2 Number of conductors 6 0 3 Interconnection cable size mm2 Number of conductors 2 5 4 Recommended time delay fuse A 35 The...

Page 17: ...N Indoor Unit Terminal Block Interconnection Cable Outdoor Unit Terminal Block Power Supply Cable Model Indoor FHYC30JEVLK Outdoor RYD30JEVLK Voltage range Indoor 220V 1Ph 60Hz Outdoor 220V 1Ph 60Hz P...

Page 18: ...uctors 2 5 4 3 Recommended time delay fuse A 35 Model Indoor FHYC40JEVLK Outdoor RYD40JEVLK Voltage range Indoor 220V 1Ph 60Hz Outdoor 220V 1Ph 60Hz Power supply cable size mm2 Number of conductors 6...

Page 19: ...for connecting wires to the power supply terminal block Connect the wires by matching to the indication on terminal block Refer to the wiring diagram attached on the unit Use the correct screwdriver...

Page 20: ...the suction valve 3 way and liquid valve 2 way in anti clockwise direction with 4mm key for hexagon sacked screw Charge Operation This operation must be done by using a gas cylinder and a precise wei...

Page 21: ...FHC30JEVLK FHC40JEVLK Outdoor RD30JEVLK RD40JEVLK Additional charge g m 57 40 Model Indoor FHC50JEVLK Outdoor RD50JETLK Additional charge g m 58 Heat Pump Unit Model Indoor FHYC20JEVLK FHYC25JEVLK Ou...

Page 22: ...Minimal equipment is required for field charging The minimum equipment required to do a satisfactory job is Set of service gauges 1 Vacuum gauge 4 Hoses 2 Scales 5 Vacuum pump 3 Thermometer 6 The prop...

Page 23: ...o that it does not touch the air louver Be sure not to push the sealing material in any farther than about 10mm There are many ways of charging liquid in a controlled manner into the suction side Use...

Page 24: ...Code 1 Room Sensor Open or Short Blink 1 time Blink Fan Blink E1 2 Indoor Coil Sensor Open Blink 2 times Blink Sleep Blink E2 3 Outdoor Coil Sensor Open Blink 3 times Blink Dry Blink E3 4 Compressor...

Page 25: ...r phase protector under normal operation and fault conditions NOTE 1 indicates additional functions for PP01 phase protector 2 When R phase missing no LED or buzzer will indicate the error but relay 7...

Page 26: ...power plug is disconnected It is possible that your delay timer has been set incorrectly The air flow is too low 3 The air filter is dirty The air suction and discharge are clogged The regulated temp...

Page 27: ...o Daikin Dealer Additional refrigerant charge of 0 2kg is needed in order to achieve the stated performance data MODEL INDOOR UNIT FHYC20JEVLK FHYC25JEVLK OUTDOOR UNIT RYD20JEVLK RYD25JEVLK RATED VOLT...

Page 28: ...OUNTRY OF ORIGIN INDOOR UNIT Malaysia OUTDOOR UNIT Malaysia MODEL INDOOR UNIT FHYC30JEVLK FHYC40JEVLK OUTDOOR UNIT RYD30JEVLK RYD40JEVLK RATED VOLTAGE V 220 220 RATED FREQUENCY Hz 60 60 COOLING T1 IND...

Page 29: ...RANT R22 kg 2 60 COUNTRY OF ORIGIN INDOOR UNIT Malaysia OUTDOOR UNIT Malaysia MODEL INDOOR UNIT FHYC50JEVLK OUTDOOR UNIT RYD50JETLK RATED VOLTAGE V 220 RATED FREQUENCY Hz 60 COOLING T1 INDOOR 27DB C 1...

Page 30: ...MEMO...

Page 31: ......

Page 32: ...revise any of the speci cation and design contain herein at any time without prior noti cation Lot 60334 Persiaran Bukit Rahman Putra 3 Taman Perindustrian Bukit Rahman Putra 47000 Sungai Buloh Selang...

Reviews: