background image

3

English

2-2

OPTIONAL ACCESSORIES

• For this indoor unit, the remote controller is separately 

required.

• There are 2 kinds of remote controller; wired type and wire-

less type.
Install the remote controller to the place where the customer 
has given consent.
Refer to the catalog for the applicable model.
(Refer to the installation manual attached to the remote con-
troller for how to install.)

CARRY OUT THE WORK GIVING CAUTION TO THE FOL-
LOWING ITEMS AND AFTER THE WORK IS COMPLETED 
CHECK THESE AGAIN.

1. Items to be checked after the installation work is completed

*Make sure to recheck the items of “SAFETY PRECAUTIONS” 

2. Items to be checked at delivery 

3. Points of the operation explanation

3.

SELECTION OF INSTALLATION LOCATION

Make sure the area is well ventilated. Do NOT block any 
ventilation openings.
When unpacking and moving the indoor unit after 
unpacked, do not apply force to the piping (refrigerant and 
drain) and resin parts.

(1) Select the installation location that meets the following con-

ditions and get approval of the customer.
• Where the cool and warm air spreads evenly in the room.
• Where there is no obstacles in the air passage.
• Where drainage can be ensured.
• Where the ceiling lower surface is not inclined.

Name

(5) Installa-
tion pattern 

paper

Joint insulat-

ing material

Sealing mate-

rial

(10) Resin 

bushing

Quantity

1 sheet

1 each

1 each

1 pc.

Shape

(6) For gas 

piping

(7) For liq-

uid piping

(8) Large

(9) Small

Name

(11) Wiring 

fixture

(12) Screw 

for wiring 

fixture

(Miscellaneous)

• Operation manual
• Installation manual
• Declaration of confor-

mity

Quantity

2 pcs.

2 pcs.

Shape

M4 × 12

Items to be checked

In case of defec-
tive

Check 

column

Are the indoor and outdoor 
units rigidly fixed?

Drop · vibration · 
noise

Are the installation work of the 
outdoor and indoor units com-
plete?

Does not operate 
· burnout

Have you carried out a 
leakage test with the test 
pressure specified in the 
outdoor unit installation 
manual?

Does not cool / 
Does not heat

Is the insulation of refriger-
ant piping and drain piping 
completely carried out? 

Water leakage

Does the drain flow out 
smoothly?

Water leakage

Is the power supply voltage 
identical to that stated in 
the manufacturer’s label on 
the air conditioner?

Does not operate 
· burnout

Are you sure that there is 
no wrong wiring or piping or 
no loose wiring? 

Does not operate 
· burnout

Is earthing completed?

Danger in case of 
leakage

Are the sizes of electric wir-
ing according to the specifi-
cation?

Does not operate 
· burnout

Is any of air outlets or inlets 
of the indoor and outdoor 
units blocked with obsta-
cles?

Does not cool / 
Does not heat
(It may lead to 
capacity drop due 
to fan speed drop 
or malfunction of 
equipment.)

Have you recorded the 
refrigerant piping length 
and the refrigerant charge 
added?

Refrigerant 
charge amount is 
not clear

Items to be checked

Check 

column

Have you carried out field setting? (if necessary)
Are the control box cover, the air filter and the suction 
grille attached?
Does the cool air discharge during the cooling opera-
tion and the warm air discharge during heating opera-
tion comes out of the unit?

Have you explained how to operate the air condi-
tioner showing the operation manual to the cus-
tomer? 
Have you explained the description of cooling, 
heating, program dry and automatic (cooling/
heating) given in the operation manual to the 
customer?
If you set the fan speed at thermostat OFF, did 
you explain the set fan speed to the customer?
Have you handed the operation manual and the 
installation manual to the customer?

In addition to the general usage, since the items in the 
operation manual with the 

WARNING and 

CAU-

TION marks are likely to result in human bodily injuries 
and property damages, it is necessary not only to 
explain these items to the customer but also to have the 
customer read them.
It is also necessary to explain the items of “NOT MAL-
FUNCTION OF THE AIR CONDITIONER” to the customer 
and have the customer read them carefully.

4PEN469440-1H.book  Page 3  Friday, March 22, 2019  2:36 PM

Summary of Contents for FHA35AVEB99

Page 1: ...INSTALLATION MANUAL FHA35AVEB99 FHA50AVEB99 FHA60AVEB99 FHA71AVEB99 FHA100AVEB9 FHA125AVEB9 FHA140AVEB9 Split System air conditioners 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM...

Page 2: ...2 5 8 286 2 4 4 74 6 0 22 8 2 4 49 0 6 0 306 2 6 5 13 6 2 24 3 2 6 57 5 6 2 327 2 8 5 53 6 4 25 9 2 8 66 7 6 4 349 3 0 5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31...

Page 3: ...o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikat...

Page 4: ...dealer regarding what to do in case of refrigerant leakage When the air conditioner is installed in a small room it is nec essary to take proper measures so that the amount of any leaked refrigerant...

Page 5: ...gnetic waves Electromagnetic waves may disturb the control system and cause malfunction of the equipment 4 Where flammable gases may leak where carbon fibre or ignitable dust is suspended in the air o...

Page 6: ...r unit installation manual Does not cool Does not heat Is the insulation of refriger ant piping and drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is...

Page 7: ...adios to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise Install the indoor unit as far as possible from fluorescent...

Page 8: ...tion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name F...

Page 9: ...for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tigh...

Page 10: ...ler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and or lead to corrosion of flared joints...

Page 11: ...cessory to con duct piping Refer to Fig 16 and Fig 17 3 For right side piping Remove the stay for packing and delivering reinforcing plate at the right side and put back the screw to the orig inal pos...

Page 12: ...essory installing attach the protection net by reversing the steps taken to remove it Refer to Fig 21 Select the piping diameter equal to or larger than that of the drain hose 1 accessory polyvinyl ch...

Page 13: ...r The ammonia in the sewage may go through the drain piping and corrode the heat exchanger of the indoor unit When installing the drain pump kit optional accessory also refer to the installation manua...

Page 14: ...when conduit piping are used When the conduit piping are not used use H07RN F 60245 IEC 66 2 Sheathed vinyl cord or cable insulation thickness 1mm or more 9 HOW TO CONNECT WIRINGS AND WIRING EXAMPLE...

Page 15: ...he wiring fixture 11 and clamp 4 attached to bind the wiring without applying tension to the connecting section of the wirings Remote controller wiring R10 or more Terminal block X2M R10 or more Trans...

Page 16: ...attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2...

Page 17: ...n using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add w...

Page 18: ...ose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WHE...

Page 19: ...ote controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate...

Page 20: ...ot OK 4 Press The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Ret...

Page 21: ...TOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN M...

Page 22: ...4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM...

Page 23: ...4P469440 1H 2019 02 Copyright 2017 Daikin 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM...

Reviews: