background image

English

2

• When wiring between the indoor and outdoor units, and wir-

ing the power supply, form the wirings orderly so that the con-
trol box cover can be securely fastened.
If the control box cover is not in place, overheat of the termi-
nals, electric shocks or a fire may be caused.

• If the supply cord is damaged, it must be replaced by the 

manufacturer, a service agent or similarly qualified persons 
in order to avoid a hazard.

• If refrigerant gas leaks during installation work, ventilate the 

area immediately.
Toxic gas may be produced if refrigerant gas comes into con-
tact with a fire.

• After completing the installation work, check to make sure 

that there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the 
room and comes into contact with a source of a fire, such as 
a fan heater, stove or cooker.

• Never directly touch any accidental leaking refrigerant. This 

could result in severe wounds caused by frostbite.

Instructions for equipment using R32 refrigerant

• Do NOT pierce or burn. 
• Do NOT use means to accelerate the defrosting process or 

to clean the equipment, other than those recommended by 
the manufacturer. 

• Be aware that R32 refrigerant does NOT contain an odour.
• The appliance shall be stored so as to prevent mechanical 

damage and in a well-ventilated room without continuously 
operating ignition sources (example: open flames, an operat-
ing gas appliance or an operating electric heater) and have a 
room size as specified in “SELECTION OF INSTALLATION 
LOCATION” on page 3.

CAUTION

• Install drain piping according to this installation manual to 

ensure good drainage, and insulate the piping to prevent 
condensation. 
Improper drain piping may cause water leakage, make the 
furniture get wet.

• Install the air conditioner, power supply wiring, remote con-

troller wiring and transmission wiring at least 1 meter away 
from televisions or radios to prevent image interference or 
noise.
(Depending on the radio waves, a distance of 1 meter may 
not be sufficient to eliminate the noise.)

• Install the indoor unit as far as possible from fluorescent 

lamps.
If a wireless remote controller kit is installed, the transmission 
distance may be shorter in a room where an electronic light-
ing type (inverter or rapid start type) fluorescent lamp is 
installed.

• Do not install the air conditioner in places such as the following:

1. Where there is mist of oil, oil spray or vapour for example 

a kitchen.
Resin parts may deteriorate, and cause them to fall out or 
water to leak. 

2. Where corrosive gas, such as sulfurous acid gas, is pro-

duced.
Corrosion of copper pipings or brazed parts may cause 
the refrigerant to leak.

3. Where there is machinery which emits electromagnetic 

waves.
Electromagnetic waves may disturb the control system, 
and cause malfunction of the equipment.

4. Where flammable gases may leak, where carbon fibre or 

ignitable dust is suspended in the air or where volatile 
flammables, such as thinner or gasoline, are handled.
If the gas should leak and remained around the air condi-
tioner, it may cause ignition.

• The air conditioner is not intended for use in a potentially 

explosive atmosphere.

• Only use accessories, optional equipment and spare parts 

made or approved by Daikin.

• Make sure the installation site withstands the unit's weight 

and vibration.

• Use an all-pole disconnection type breaker with at least 3 

mm between the contact point gaps that provide full discon-
nection under overvoltage category III.

2.

BEFORE INSTALLATION

When unpacking and moving the indoor unit after 
unpacked, do not apply force to the piping (refrigerant and 
drain) and resin parts.

• If appliances are connected to the outdoor unit which contain 

R32 refrigerant. Required floor area of the room in which 
appliances are installed, operated and stored must follow 
requirements in the installation manual of outdoor unit.

• Make sure to check in advance that the refrigerant to be used 

for installation work is according to the Outdoor Unit specifi-
cation.
(The air conditioner will not properly operate if a wrong refrig-
erant is used.)

• For installation of the outdoor unit, refer to the installation 

manual attached to the outdoor unit.

• Do not throw away the accessories until the installation work 

is completed.

• After the indoor unit is carried into the room, to avoid the 

indoor unit from getting damaged, take measures to protect 
the indoor unit with packing materials.
(1) Determine the route to carry the unit into the room.
(2) Do not unpack the unit until it is carried to the installation 

location.
Where unpacking is unavoidable, use a sling of soft 
material or protective plates together with a rope when 
lifting, to avoid damage or scratches to the indoor units.

• Have the customer actually operate the air conditioner while 

looking at the manual.
Instruct the customer how to operate the air conditioner (par-
ticularly cleaning of the air filters, operation procedures, and 
temperature adjustment).

• For selection of installation location, use the installation pat-

tern paper (used in common with the packing case.) as refer-
ence.

• Do not use the air conditioner where in the salty atmosphere 

such as coastal areas, vehicles, vessels or the voltage fluc-
tuation is frequent such as factories.

• Take off static electricity from the body when carrying out wir-

ing and the control box cover is removed. 
The electric parts may be damaged.

2-1

ACCESSORIES

Check if the following accessories are attached to the 
indoor unit.

Name

(1) Drain 

hose

(2) Metal 

clamp 

(3) Washer 

for hanger

(4) Clamp

Quantity

1 pc.

1 pc.

8 pcs.

7 pcs.

Shape

4PEN469440-1H.book  Page 2  Friday, March 22, 2019  2:36 PM

Summary of Contents for FHA35AVEB99

Page 1: ...INSTALLATION MANUAL FHA35AVEB99 FHA50AVEB99 FHA60AVEB99 FHA71AVEB99 FHA100AVEB9 FHA125AVEB9 FHA140AVEB9 Split System air conditioners 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM...

Page 2: ...2 5 8 286 2 4 4 74 6 0 22 8 2 4 49 0 6 0 306 2 6 5 13 6 2 24 3 2 6 57 5 6 2 327 2 8 5 53 6 4 25 9 2 8 66 7 6 4 349 3 0 5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31...

Page 3: ...o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikat...

Page 4: ...dealer regarding what to do in case of refrigerant leakage When the air conditioner is installed in a small room it is nec essary to take proper measures so that the amount of any leaked refrigerant...

Page 5: ...gnetic waves Electromagnetic waves may disturb the control system and cause malfunction of the equipment 4 Where flammable gases may leak where carbon fibre or ignitable dust is suspended in the air o...

Page 6: ...r unit installation manual Does not cool Does not heat Is the insulation of refriger ant piping and drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is...

Page 7: ...adios to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise Install the indoor unit as far as possible from fluorescent...

Page 8: ...tion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name F...

Page 9: ...for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tigh...

Page 10: ...ler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and or lead to corrosion of flared joints...

Page 11: ...cessory to con duct piping Refer to Fig 16 and Fig 17 3 For right side piping Remove the stay for packing and delivering reinforcing plate at the right side and put back the screw to the orig inal pos...

Page 12: ...essory installing attach the protection net by reversing the steps taken to remove it Refer to Fig 21 Select the piping diameter equal to or larger than that of the drain hose 1 accessory polyvinyl ch...

Page 13: ...r The ammonia in the sewage may go through the drain piping and corrode the heat exchanger of the indoor unit When installing the drain pump kit optional accessory also refer to the installation manua...

Page 14: ...when conduit piping are used When the conduit piping are not used use H07RN F 60245 IEC 66 2 Sheathed vinyl cord or cable insulation thickness 1mm or more 9 HOW TO CONNECT WIRINGS AND WIRING EXAMPLE...

Page 15: ...he wiring fixture 11 and clamp 4 attached to bind the wiring without applying tension to the connecting section of the wirings Remote controller wiring R10 or more Terminal block X2M R10 or more Trans...

Page 16: ...attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2...

Page 17: ...n using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add w...

Page 18: ...ose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WHE...

Page 19: ...ote controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate...

Page 20: ...ot OK 4 Press The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Ret...

Page 21: ...TOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN M...

Page 22: ...4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM...

Page 23: ...4P469440 1H 2019 02 Copyright 2017 Daikin 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM...

Reviews: