background image

7

English

A. When the drain piping is tilted to the right, or to the right 

and back.
Place it level, or tilt it slightly to the right or the back. 
(Within 1°)

B. When the drain piping is tilted to the left, or to the left 

and back.
Place it level, or tilt it slightly to the left or the back. 
(Within 1°)

WARNING

The indoor unit must be securely installed on a place that 
can withstand the mass.
If the strength is insufficient, the indoor unit may fall down 
and cause injuries.

6.

REFRIGERANT PIPING WORK

• For the outdoor unit refrigerant piping, refer to the installation 

manual attached to the outdoor unit.

• Carry out insulation of both gas and liquid refrigerant piping 

securely. If not insulated, it may cause water leakage. For 
gas piping, use insulation material of which heat resistant 
temperature is not less than 120°C. For use under high 
humidity, strengthen the insulation material for refrigerant 
piping. If not strengthened, the surface of insulation material 
may sweat.

• Make sure to check in advance that the refrigerant to be used 

for installation work is according to the Outdoor Unit specifi-
cation. (Unless the refrigerant is correct type, the normal 
operation cannot be expected.)

• Pipework shall be protected from physical damage.
• Installation of pipework shall be kept to a minimum.
• Do NOT re-use joints which have been used already.
• Joints made in installation between parts of refrigerant sys-

tem shall be accessible for maintenance purposes.

• Refrigerating pipe or components are installed in a position 

where they are unlikely to be exposed to any substance 
which may corrode refrigerant containing components, 
unless the components are constructed of materials which 
are inherently resistant to being corroded or are suitably pro-
tected against being so corroded.

• Make sure to use a recommended bubble test solution from 

your wholesaler. Do not use soap water, which may cause 
cracking of flare nuts (soap water may contain salt, which 
absorbs moisture that will freeze when the piping gets cold), 
and/or lead to corrosion of flared joints (soap water may con-
tain ammonia which causes a corrosive effect between the 
brass flare nut and the copper flare).

CAUTION

This air conditioner is a dedicated model for refrigerant 
R410A or R32. Make sure to meet the requirements shown 
right and carry out installation work.

• Use dedicated piping cutters and flaring tools according to 

the used refrigerant type.

• When making a flare connection, coat the flared inner sur-

face only with ether oil or ester oil.

• Use only the flare nuts attached to the air conditioner. If 

other flare nuts are used, it may cause refrigerant leak-
age.

• To prevent contamination or moisture from getting into the 

piping, take measures such as pinching or taping the pip-
ings.

Do not mix substance other than the specified refrigerant 
such as air into the refrigeration circuit.
If the refrigerant leaks during the work, ventilate the room.

• Remove the stay for packing and delivering (reinforcing 

plate) before refrigerant piping work. 
(Refer to Fig. 18)

• The refrigerant is pre-charged in the outdoor unit.
• When connecting the pipings to the air conditioner, make 

sure to use a spanner and a torque wrench as shown in 
Fig.13.
For the dimension of flared part, refer to the Table 1.

• When making a flare connection, coat the flared inner sur-

face only with ether oil or ester oil. (Refer to Fig. 14) Then, 
turn the flare nut 3 to 4 times with your hand and screw in the 
nut.

• For the tightening torque, refer to the Table 1.

Table 1 

A

A.B

B

≤ 1°

≤ 1°

≤ 1°

Fig. 12

Piping size 

(mm)

Tightening 

torque (N·m)

Dimension 

for processing 

flare A (mm)

Flare shape

ø 6.4

15.7 ± 1.5

8.9 ± 0.2

ø 9.5

36.3 ± 3.6

13.0 ± 0.2

ø 12.7

54.9 ± 5.4

16.4 ± 0.2

ø15.9

68.6 ± 6.8

19.5 ± 0.2

Torque wrench

Spanner

Flare nut

Union joint

Fig. 13

Coat the flared inner surface 
only with ether oil or ester oil.

Fig. 14

R0.4-0.8

90°±2°

A

45°±2°

4PEN469440-1H.book  Page 7  Friday, March 22, 2019  2:36 PM

Summary of Contents for FHA35AVEB99

Page 1: ...INSTALLATION MANUAL FHA35AVEB99 FHA50AVEB99 FHA60AVEB99 FHA71AVEB99 FHA100AVEB9 FHA125AVEB9 FHA140AVEB9 Split System air conditioners 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM...

Page 2: ...2 5 8 286 2 4 4 74 6 0 22 8 2 4 49 0 6 0 306 2 6 5 13 6 2 24 3 2 6 57 5 6 2 327 2 8 5 53 6 4 25 9 2 8 66 7 6 4 349 3 0 5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31...

Page 3: ...o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikat...

Page 4: ...dealer regarding what to do in case of refrigerant leakage When the air conditioner is installed in a small room it is nec essary to take proper measures so that the amount of any leaked refrigerant...

Page 5: ...gnetic waves Electromagnetic waves may disturb the control system and cause malfunction of the equipment 4 Where flammable gases may leak where carbon fibre or ignitable dust is suspended in the air o...

Page 6: ...r unit installation manual Does not cool Does not heat Is the insulation of refriger ant piping and drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is...

Page 7: ...adios to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise Install the indoor unit as far as possible from fluorescent...

Page 8: ...tion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name F...

Page 9: ...for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tigh...

Page 10: ...ler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and or lead to corrosion of flared joints...

Page 11: ...cessory to con duct piping Refer to Fig 16 and Fig 17 3 For right side piping Remove the stay for packing and delivering reinforcing plate at the right side and put back the screw to the orig inal pos...

Page 12: ...essory installing attach the protection net by reversing the steps taken to remove it Refer to Fig 21 Select the piping diameter equal to or larger than that of the drain hose 1 accessory polyvinyl ch...

Page 13: ...r The ammonia in the sewage may go through the drain piping and corrode the heat exchanger of the indoor unit When installing the drain pump kit optional accessory also refer to the installation manua...

Page 14: ...when conduit piping are used When the conduit piping are not used use H07RN F 60245 IEC 66 2 Sheathed vinyl cord or cable insulation thickness 1mm or more 9 HOW TO CONNECT WIRINGS AND WIRING EXAMPLE...

Page 15: ...he wiring fixture 11 and clamp 4 attached to bind the wiring without applying tension to the connecting section of the wirings Remote controller wiring R10 or more Terminal block X2M R10 or more Trans...

Page 16: ...attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2...

Page 17: ...n using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add w...

Page 18: ...ose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WHE...

Page 19: ...ote controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate...

Page 20: ...ot OK 4 Press The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Ret...

Page 21: ...TOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN M...

Page 22: ...4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM...

Page 23: ...4P469440 1H 2019 02 Copyright 2017 Daikin 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM...

Reviews: