English

16

11-6

SETTING NUMBER OF THE CONNECTED INDOOR 
UNITS AS SIMULTANEOUS OPERATION SYSTEM

• When using in simultaneous operation system mode, 

change the SECOND CODE No. as shown in Table 6.

• When using in simultaneous operation system mode, refer to 

“SIMULTANEOUS OPERATION SYSTEM INDIVIDUAL 
SETTING” section to set master and slave units separately.

Table 6

11-7

SIMULTANEOUS OPERATION SYSTEM INDIVIDUAL 
SETTING

It is easier if the optional remote controller is used when setting 
the slave unit.

< Procedure >

• Perform the following procedure when setting the master and 

slave unit separately.

• “ 

 ” in the tables indicates factory settings.

(Note) The “Mode No.” is set on a group basis. To individu-

ally set a Mode No. for each indoor unit or confirm the 
settings, set the Mode No. in the parenthesis.

(1) Change the SECOND CODE No. to “02”, individual setting, 

so that the slave unit can be individually set.

Table 7

(2) Perform field setting (Refer to 11-1 to 11-5) for the master 

unit.

(3) Turn off the main power supply switch after (2) is finished.
(4) Detach remote controller from the master unit and connect 

it to the slave unit.

(5) Turn on the main power supply switch again, and as in (1), 

change the SECOND CODE No. to “02”, individual setting.

(6) Perform field setting (Refer to 11-1 to 11-4) for the slave 

unit.

(7) Turn off the main power supply switch after (6) is finished.
(8) If there is more than one slave unit, repeat steps (4) to (7).
(9) Detach the remote controller from the slave unit after the 

setting, and reattach to the master unit. This is the end of 
the setting procedure.
* You do not need to rewire the remote controller from the 

master unit if the optional remote controller for slave unit 
is used. (However, remove the wiring attached to the 
remote controller terminal block of the master unit.) After 
the slave unit setting, remove the remote controller wir-
ing, and rewire the remote controller to the master unit. 
(The indoor unit does not operate properly when two or 
more remote controllers are attached to the unit in the 
simultaneous operation system mode.)

NOTE

NOTE

NOTE

NOTE

• Terminal numbers of outdoor and indoor units must be 

matched.

12.

TO PERFORM A TEST RUN

CAUTION

This task is only applicable when using the BRC1E52 or 
BRC1E53 user interface. When using any other user inter-
face, see the installation manual or service manual of the 
user interface.

NOTE

NOTE

NOTE

NOTE

Backlight.

 To perform an ON/OFF action on the user inter-

face, the backlight does not need to be lit. For any other 
action, it needs to be lit first. The backlight is lit for ±30 sec-
onds when you press a button.

1. Perform introductory steps.

Table 8

Setting

Mode No.

FIRST

CODE No.

SECOND

CODE No.

Pair system (1 unit)

11 (21)

0

01

Simultaneous

operation

system (2-unit)

02

Simultaneous

operation

system (3-unit)

03

Double twin multi

(4-unit)

04

Setting

Mode No.

FIRST

CODE No.

SECOND 

CODE No.

Unified setting

11 (21)

1

01

Individual setting

02

#

Action

1

Open the liquid stop valve (A) and gas stop valve (B) by remov-
ing the stem cap and turning counterclockwise with a hex 
wrench until it stops.

2 Close the service cover to prevent electric shocks.

3

Turn On power for at least 6 hours before starting operation to 
protect the compressor.

4 On the user interface, set the unit to cooling operation mode.

P1 P2

P1 P2

1 2 3

P1 P2

1 2 3

P1 P2

P1 P2

P1 P2

1 2 3

1 2 3

1 2 3

1 2 3

Outdoor 
unit

Outdoor 
unit

NOTE)

NOTE)

Indoor unit 
(Master)

Indoor unit 
(Master)

Indoor unit 
(Slave)

Indoor unit 
(Slave)

Remote controller

Remote controller

( 3 ) ( 7 )

( 1 ) 
( 2 )

( 4 )

( 9 )

( 5 ) 
( 6 )

Earth 
leakage 
breaker

Earth 
leakage 
breaker

Fig. 39

Power supply

220 - 240V

~

50Hz

Power supply

220 - 240V

~

50Hz

A

B

4PEN469440-1H.book  Page 16  Friday, March 22, 2019  2:36 PM

Summary of Contents for FHA35AVEB99

Page 1: ...INSTALLATION MANUAL FHA35AVEB99 FHA50AVEB99 FHA60AVEB99 FHA71AVEB99 FHA100AVEB9 FHA125AVEB9 FHA140AVEB9 Split System air conditioners 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM...

Page 2: ...2 5 8 286 2 4 4 74 6 0 22 8 2 4 49 0 6 0 306 2 6 5 13 6 2 24 3 2 6 57 5 6 2 327 2 8 5 53 6 4 25 9 2 8 66 7 6 4 349 3 0 5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31...

Page 3: ...o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikat...

Page 4: ...dealer regarding what to do in case of refrigerant leakage When the air conditioner is installed in a small room it is nec essary to take proper measures so that the amount of any leaked refrigerant...

Page 5: ...gnetic waves Electromagnetic waves may disturb the control system and cause malfunction of the equipment 4 Where flammable gases may leak where carbon fibre or ignitable dust is suspended in the air o...

Page 6: ...r unit installation manual Does not cool Does not heat Is the insulation of refriger ant piping and drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is...

Page 7: ...adios to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise Install the indoor unit as far as possible from fluorescent...

Page 8: ...tion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name F...

Page 9: ...for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tigh...

Page 10: ...ler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and or lead to corrosion of flared joints...

Page 11: ...cessory to con duct piping Refer to Fig 16 and Fig 17 3 For right side piping Remove the stay for packing and delivering reinforcing plate at the right side and put back the screw to the orig inal pos...

Page 12: ...essory installing attach the protection net by reversing the steps taken to remove it Refer to Fig 21 Select the piping diameter equal to or larger than that of the drain hose 1 accessory polyvinyl ch...

Page 13: ...r The ammonia in the sewage may go through the drain piping and corrode the heat exchanger of the indoor unit When installing the drain pump kit optional accessory also refer to the installation manua...

Page 14: ...when conduit piping are used When the conduit piping are not used use H07RN F 60245 IEC 66 2 Sheathed vinyl cord or cable insulation thickness 1mm or more 9 HOW TO CONNECT WIRINGS AND WIRING EXAMPLE...

Page 15: ...he wiring fixture 11 and clamp 4 attached to bind the wiring without applying tension to the connecting section of the wirings Remote controller wiring R10 or more Terminal block X2M R10 or more Trans...

Page 16: ...attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2...

Page 17: ...n using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add w...

Page 18: ...ose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WHE...

Page 19: ...ote controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate...

Page 20: ...ot OK 4 Press The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Ret...

Page 21: ...TOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN M...

Page 22: ...4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM...

Page 23: ...4P469440 1H 2019 02 Copyright 2017 Daikin 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM...

Reviews: