background image

1

English

CONTENTS

1. SAFETY PRECAUTIONS ................................................1
2. BEFORE INSTALLATION ................................................2
3. SELECTION OF INSTALLATION LOCATION..................3
4. PREPARATION BEFORE INSTALLATION 
......................5
5. INSTALLATION OF THE INDOOR UNIT .........................6
6. REFRIGERANT PIPING WORK ......................................7
7. DRAIN PIPING WORK.....................................................9
8. ELECTRIC WIRING WORK........................................... 11
9. HOW TO CONNECT WIRINGS 

AND WIRING EXAMPLE ............................................... 11

10. MOUNTING SUCTION GRILLE · DECORATION 

SIDE PANEL ..................................................................15

11. FIELD SETTING ............................................................15

12. TO PERFORM A TEST RUN .........................................16
13. UNIFIED WIRING DIAGRAM LEGEND.........................18

The original instructions are written in English.
All other languages are translations of the original instructions.

* Only applicable if this appliance is connected with the
following models of outdoor units: RZAG35~140, 
RZASG71~140, RXM35~60, 3MXM40~68, 4MXM68~80, 
5MXM90

1.

SAFETY PRECAUTIONS

Carefully read these instructions before installation. Keep this 
manual in a handy place for future reference.
Be sure to follow this “SAFETY PRECAUTIONS”. 
This product comes under the term “appliances not accessible 
to the general public”.

• This manual classifies the precautions into WARNINGS and 

CAUTIONS.
Be sure to follow all the precautions below: They are all 
important for ensuring safety.

WARNING .................... Indicates a potentially hazard-

ous situation which, if not 
avoided, could result in death 
or serious injury.

CAUTION ..................... Indicates a potentially hazard-

ous situation which, if not 
avoided, may result in minor or 
moderate injury.
It may also be used to alert 
against unsafe practices.

• After the installation is completed, test the air conditioner and 

check if the air conditioner operates properly. Give the user 

adequate instructions concerning the use and cleaning of the 
indoor unit according to the Operation Manual. Ask the user 
to keep this manual and the Operation Manual together in a 
handy place for future reference.

WARNING

• Make sure installation, testing and applied materials comply 

with applicable legislation (on top of the instructions 
described in the Daikin documentation).

• The appliance shall be stored in a room without continuously 

operating ignition sources (example: open flames, an operat-
ing gas appliance or an operating electric heater).

• Ask your local dealer or qualified personnel to carry out 

installation work.
Improper installation may result in water leakage, electric 
shocks or a fire.

• Perform installation work in accordance with this installation 

manual.
Improper installation may result in water leakage, electric 
shocks or a fire.Consult your dealer regarding what to do in 
case of refrigerant leakage.
When the air conditioner is installed in a small room, it is nec-
essary to take proper measures so that the amount of any 
leaked refrigerant does not exceed the concentration limit in 
the event of a leakage.
Otherwise, this may lead to an accident due to oxygen defi-
ciency.

• Be sure to use only the specified parts and accessories for 

installation work.
Failure to use the specified parts may result in the air condi-
tioner falling down, water leakage, electric shocks, a fire, etc.

• Install the air conditioner on a foundation that can withstand 

its mass.
Insufficient strength may result in the air conditioner falling 
down and causing injury.
In addition, it may lead to vibration of indoor units and cause 
unpleasant chattering noise.

• Carry out the specified installation work in consideration of 

strong winds, typhoons, or earthquakes.
Improper installation may result in an accident such as air 
conditioner falling.

• Make certain that all electrical work is carried out by qualified 

personnel according to the applicable legislation (note 1) and 
this installation manual, using a separate circuit. 
In addition, even if the wiring is short, make sure to use a wir-
ing that has sufficient length and never connect additional 
wiring to make the length sufficient.
Insufficient capacity of the power supply circuit or improper 
electrical construction may lead to electric shocks or a fire. 
(note 1) applicable legislation means “All international, 

national and local directives, laws, regulations and/
or codes which are relevant and applicable for a 
certain product or domain”.

• Earth the air conditioner.

Do not connect the earth wiring to gas or water piping, light-
ning conductor or telephone earth wiring.
Incomplete earthing may cause electric shocks or a fire.

• Be sure to install an earth leakage breaker.

Failure to do so may cause electric shocks and a fire.

• Disconnect the power supply before touching the electric 

components.
If you touch the live part, you may get an electric shocks.

• Make sure that all wiring is secure, using the specified wir-

ings and ensuring that external forces do not act on the ter-
minal connections or wirings.
Incomplete connection or fixing may cause an overheat or a 
fire.

Symbol

Explanation

Before installation, read the installation and operation 

manual, and the wiring instruction sheet.

Before performing maintenance and service tasks, read 

the service manual.

For more information, see the installer and user 

reference guide.

This appliance is filled with R32.*

4PEN469440-1H.book  Page 1  Friday, March 22, 2019  2:36 PM

Summary of Contents for FHA100AVEB9

Page 1: ...INSTALLATION MANUAL FHA35AVEB99 FHA50AVEB99 FHA60AVEB99 FHA71AVEB99 FHA100AVEB9 FHA125AVEB9 FHA140AVEB9 Split System air conditioners 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM ...

Page 2: ... 2 5 8 286 2 4 4 74 6 0 22 8 2 4 49 0 6 0 306 2 6 5 13 6 2 24 3 2 6 57 5 6 2 327 2 8 5 53 6 4 25 9 2 8 66 7 6 4 349 3 0 5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31 0 3 4 98 4 7 0 417 3 6 8 20 7 2 32 8 3 6 110 7 2 441 3 8 9 14 7 4 34 7 3 8 123 7 4 466 4 0 10 1 7 6 36 6 4 0 136 7 6 492 4 2 11 2 7 8 38 5 4 2 150 7 8 518 4 4 12 3 7 956 40 1 4 4 165 7 956 539 m kg ...

Page 3: ...com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertifikat C 13 Huom jotka o...

Page 4: ...r dealer regarding what to do in case of refrigerant leakage When the air conditioner is installed in a small room it is nec essary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentration limit in the event of a leakage Otherwise this may lead to an accident due to oxygen defi ciency Be sure to use only the specified parts and accessories for installa...

Page 5: ...agnetic waves Electromagnetic waves may disturb the control system and cause malfunction of the equipment 4 Where flammable gases may leak where carbon fibre or ignitable dust is suspended in the air or where volatile flammables such as thinner or gasoline are handled If the gas should leak and remained around the air condi tioner it may cause ignition The air conditioner is not intended for use i...

Page 6: ...or unit installation manual Does not cool Does not heat Is the insulation of refriger ant piping and drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is the power supply voltage identical to that stated in the manufacturer s label on the air conditioner Does not operate burnout Are you sure that there is no wrong wiring or piping or no loose wiring D...

Page 7: ...radios to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise Install the indoor unit as far as possible from fluorescent lamps If a wireless remote controller kit is installed the transmission distance may be shorter in a room where an electronic light ing type inverter or rapid start type fluorescent lamp is installe...

Page 8: ...tion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name FHA A B C D E F G H J Class 35 50 960 920 378 324 270 375 398 377 260 Class 60 71 1270 1230 533 479 425 530 553 532 415 Class 100 125 140 1590 1550 693 639 585 690 713 692 575 G H J 5 175 200 View from...

Page 9: ... for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tighten the hanger fixing screws M5 at 2 places which were removed as they were before Refer to Fig 11 It is necessary to prevent misalignment of the indoor unit 4 Tighten the hanger installing bolts M8 ...

Page 10: ...r Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and or lead to corrosion of flared joints soap water may con tain ammonia which causes a corrosive effect between the brass flare nut and the copper flare CAUTION This air conditioner is a dedicated model for refrigerant R410A or R32 Make sure...

Page 11: ...ccessory to con duct piping Refer to Fig 16 and Fig 17 3 For right side piping Remove the stay for packing and delivering reinforcing plate at the right side and put back the screw to the orig inal position of the indoor unit Refer to Fig 18 Open the knockout hole at the decoration side panel right and connect piping Refer to Fig 18 Fig 15a Gas piping Liquid piping Indoor unit Joint insulating mat...

Page 12: ...cessory installing attach the protection net by reversing the steps taken to remove it Refer to Fig 21 Select the piping diameter equal to or larger than that of the drain hose 1 accessory polyvinyl chloride piping nominal diameter 20mm outside diameter 26mm Install the drain piping as short as possible with down ward inclination of 1 100 or more by avoiding air stagna tion Refer to Fig 22 and Fig...

Page 13: ...or The ammonia in the sewage may go through the drain piping and corrode the heat exchanger of the indoor unit When installing the drain pump kit optional accessory also refer to the installation manual included to the drain pump kit 2 After piping is finished check if the drain flows smoothly Gradually put about 0 6 liter of water for drain confirma tion into the drain pan from the air outlet Ref...

Page 14: ...e when conduit piping are used When the conduit piping are not used use H07RN F 60245 IEC 66 2 Sheathed vinyl cord or cable insulation thickness 1mm or more 9 HOW TO CONNECT WIRINGS AND WIRING EXAMPLE Wiring connection method Caution for wiring The indoor units in the same system can be connected to the power supply from one branch switch However selection of branch switch branch overcurrent circu...

Page 15: ...the wiring fixture 11 and clamp 4 attached to bind the wiring without applying tension to the connecting section of the wirings Remote controller wiring R10 or more Terminal block X2M R10 or more Transmission and earth wiring connection method R10 or more Earth terminal Outdoor unit Indoor unit Terminal block Terminal block Terminal numbers of outdoor and indoor units must be matched Transmission ...

Page 16: ... attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2 indoor units 2 indoor units operates equally Refer to Fig 32 Group control 1 remote controller controls up to 16 indoor units All indoor units operate according to the remote controller Refer to Fig ...

Page 17: ...en using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add wiring between the remote controller 2 Sub and the terminal P1 P2 of the terminal block X1M for the remote controller in the control box There is no polarity NOTE NOTE NOTE NOTE Terminal numbers of ou...

Page 18: ...hose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WHEN USING WIRELESS REMOTE CONTROLLER When using a wireless remote controller it is necessary to set the wireless remote controller address Refer to the installation manual attached to the wireless remo...

Page 19: ...mote controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate properly when two or more remote controllers are attached to the unit in the simultaneous operation system mode NOTE NOTE NOTE NOTE Terminal numbers of outdoor and indoor units must be matched 12 TO ...

Page 20: ...not OK 4 Press The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Return Setting Test Operation Return Setting Return Setting Air Volume direction Air Volume Direction Position 0 Low Return Setting Return Setting Air Volume direction Air Volume Direction Low Position ...

Page 21: ...RVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M P DRAIN PUMP MOTOR M S SWING MOTOR MR MRCW MRM MRN MAGNETIC RELAY N NEUTRAL n N NUMBER OF PASSES THROUGH FERRITE CORE PAM PULSE AMPLITUDE MODULATION PCB PRINTED CIRCUIT BOARD PM POWER...

Page 22: ...4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM ...

Page 23: ...4P469440 1H 2019 02 Copyright 2017 Daikin 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM ...

Reviews: