background image

7

English

A. When the drain piping is tilted to the right, or to the right 

and back.
Place it level, or tilt it slightly to the right or the back. 
(Within 1°)

B. When the drain piping is tilted to the left, or to the left 

and back.
Place it level, or tilt it slightly to the left or the back. 
(Within 1°)

WARNING

The indoor unit must be securely installed on a place that 
can withstand the mass.
If the strength is insufficient, the indoor unit may fall down 
and cause injuries.

6.

REFRIGERANT PIPING WORK

• For the outdoor unit refrigerant piping, refer to the installation 

manual attached to the outdoor unit.

• Carry out insulation of both gas and liquid refrigerant piping 

securely. If not insulated, it may cause water leakage. For 
gas piping, use insulation material of which heat resistant 
temperature is not less than 120°C. For use under high 
humidity, strengthen the insulation material for refrigerant 
piping. If not strengthened, the surface of insulation material 
may sweat.

• Make sure to check in advance that the refrigerant to be used 

for installation work is according to the Outdoor Unit specifi-
cation. (Unless the refrigerant is correct type, the normal 
operation cannot be expected.)

• Pipework shall be protected from physical damage.
• Installation of pipework shall be kept to a minimum.
• Do NOT re-use joints which have been used already.
• Joints made in installation between parts of refrigerant sys-

tem shall be accessible for maintenance purposes.

• Refrigerating pipe or components are installed in a position 

where they are unlikely to be exposed to any substance 
which may corrode refrigerant containing components, 
unless the components are constructed of materials which 
are inherently resistant to being corroded or are suitably pro-
tected against being so corroded.

• Make sure to use a recommended bubble test solution from 

your wholesaler. Do not use soap water, which may cause 
cracking of flare nuts (soap water may contain salt, which 
absorbs moisture that will freeze when the piping gets cold), 
and/or lead to corrosion of flared joints (soap water may con-
tain ammonia which causes a corrosive effect between the 
brass flare nut and the copper flare).

CAUTION

This air conditioner is a dedicated model for refrigerant 
R410A or R32. Make sure to meet the requirements shown 
right and carry out installation work.

• Use dedicated piping cutters and flaring tools according to 

the used refrigerant type.

• When making a flare connection, coat the flared inner sur-

face only with ether oil or ester oil.

• Use only the flare nuts attached to the air conditioner. If 

other flare nuts are used, it may cause refrigerant leak-
age.

• To prevent contamination or moisture from getting into the 

piping, take measures such as pinching or taping the pip-
ings.

Do not mix substance other than the specified refrigerant 
such as air into the refrigeration circuit.
If the refrigerant leaks during the work, ventilate the room.

• Remove the stay for packing and delivering (reinforcing 

plate) before refrigerant piping work. 
(Refer to Fig. 18)

• The refrigerant is pre-charged in the outdoor unit.
• When connecting the pipings to the air conditioner, make 

sure to use a spanner and a torque wrench as shown in 
Fig.13.
For the dimension of flared part, refer to the Table 1.

• When making a flare connection, coat the flared inner sur-

face only with ether oil or ester oil. (Refer to Fig. 14) Then, 
turn the flare nut 3 to 4 times with your hand and screw in the 
nut.

• For the tightening torque, refer to the Table 1.

Table 1 

A

A.B

B

≤ 1°

≤ 1°

≤ 1°

Fig. 12

Piping size 

(mm)

Tightening 

torque (N·m)

Dimension 

for processing 

flare A (mm)

Flare shape

ø 6.4

15.7 ± 1.5

8.9 ± 0.2

ø 9.5

36.3 ± 3.6

13.0 ± 0.2

ø 12.7

54.9 ± 5.4

16.4 ± 0.2

ø15.9

68.6 ± 6.8

19.5 ± 0.2

Torque wrench

Spanner

Flare nut

Union joint

Fig. 13

Coat the flared inner surface 
only with ether oil or ester oil.

Fig. 14

R0.4-0.8

90°±2°

A

45°±2°

4PEN469440-1H.book  Page 7  Friday, March 22, 2019  2:36 PM

Summary of Contents for FHA100AVEB9

Page 1: ...INSTALLATION MANUAL FHA35AVEB99 FHA50AVEB99 FHA60AVEB99 FHA71AVEB99 FHA100AVEB9 FHA125AVEB9 FHA140AVEB9 Split System air conditioners 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM ...

Page 2: ... 2 5 8 286 2 4 4 74 6 0 22 8 2 4 49 0 6 0 306 2 6 5 13 6 2 24 3 2 6 57 5 6 2 327 2 8 5 53 6 4 25 9 2 8 66 7 6 4 349 3 0 5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31 0 3 4 98 4 7 0 417 3 6 8 20 7 2 32 8 3 6 110 7 2 441 3 8 9 14 7 4 34 7 3 8 123 7 4 466 4 0 10 1 7 6 36 6 4 0 136 7 6 492 4 2 11 2 7 8 38 5 4 2 150 7 8 518 4 4 12 3 7 956 40 1 4 4 165 7 956 539 m kg ...

Page 3: ...com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertifikat C 13 Huom jotka o...

Page 4: ...r dealer regarding what to do in case of refrigerant leakage When the air conditioner is installed in a small room it is nec essary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentration limit in the event of a leakage Otherwise this may lead to an accident due to oxygen defi ciency Be sure to use only the specified parts and accessories for installa...

Page 5: ...agnetic waves Electromagnetic waves may disturb the control system and cause malfunction of the equipment 4 Where flammable gases may leak where carbon fibre or ignitable dust is suspended in the air or where volatile flammables such as thinner or gasoline are handled If the gas should leak and remained around the air condi tioner it may cause ignition The air conditioner is not intended for use i...

Page 6: ...or unit installation manual Does not cool Does not heat Is the insulation of refriger ant piping and drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is the power supply voltage identical to that stated in the manufacturer s label on the air conditioner Does not operate burnout Are you sure that there is no wrong wiring or piping or no loose wiring D...

Page 7: ...radios to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise Install the indoor unit as far as possible from fluorescent lamps If a wireless remote controller kit is installed the transmission distance may be shorter in a room where an electronic light ing type inverter or rapid start type fluorescent lamp is installe...

Page 8: ...tion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name FHA A B C D E F G H J Class 35 50 960 920 378 324 270 375 398 377 260 Class 60 71 1270 1230 533 479 425 530 553 532 415 Class 100 125 140 1590 1550 693 639 585 690 713 692 575 G H J 5 175 200 View from...

Page 9: ... for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tighten the hanger fixing screws M5 at 2 places which were removed as they were before Refer to Fig 11 It is necessary to prevent misalignment of the indoor unit 4 Tighten the hanger installing bolts M8 ...

Page 10: ...r Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and or lead to corrosion of flared joints soap water may con tain ammonia which causes a corrosive effect between the brass flare nut and the copper flare CAUTION This air conditioner is a dedicated model for refrigerant R410A or R32 Make sure...

Page 11: ...ccessory to con duct piping Refer to Fig 16 and Fig 17 3 For right side piping Remove the stay for packing and delivering reinforcing plate at the right side and put back the screw to the orig inal position of the indoor unit Refer to Fig 18 Open the knockout hole at the decoration side panel right and connect piping Refer to Fig 18 Fig 15a Gas piping Liquid piping Indoor unit Joint insulating mat...

Page 12: ...cessory installing attach the protection net by reversing the steps taken to remove it Refer to Fig 21 Select the piping diameter equal to or larger than that of the drain hose 1 accessory polyvinyl chloride piping nominal diameter 20mm outside diameter 26mm Install the drain piping as short as possible with down ward inclination of 1 100 or more by avoiding air stagna tion Refer to Fig 22 and Fig...

Page 13: ...or The ammonia in the sewage may go through the drain piping and corrode the heat exchanger of the indoor unit When installing the drain pump kit optional accessory also refer to the installation manual included to the drain pump kit 2 After piping is finished check if the drain flows smoothly Gradually put about 0 6 liter of water for drain confirma tion into the drain pan from the air outlet Ref...

Page 14: ...e when conduit piping are used When the conduit piping are not used use H07RN F 60245 IEC 66 2 Sheathed vinyl cord or cable insulation thickness 1mm or more 9 HOW TO CONNECT WIRINGS AND WIRING EXAMPLE Wiring connection method Caution for wiring The indoor units in the same system can be connected to the power supply from one branch switch However selection of branch switch branch overcurrent circu...

Page 15: ...the wiring fixture 11 and clamp 4 attached to bind the wiring without applying tension to the connecting section of the wirings Remote controller wiring R10 or more Terminal block X2M R10 or more Transmission and earth wiring connection method R10 or more Earth terminal Outdoor unit Indoor unit Terminal block Terminal block Terminal numbers of outdoor and indoor units must be matched Transmission ...

Page 16: ... attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2 indoor units 2 indoor units operates equally Refer to Fig 32 Group control 1 remote controller controls up to 16 indoor units All indoor units operate according to the remote controller Refer to Fig ...

Page 17: ...en using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add wiring between the remote controller 2 Sub and the terminal P1 P2 of the terminal block X1M for the remote controller in the control box There is no polarity NOTE NOTE NOTE NOTE Terminal numbers of ou...

Page 18: ...hose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WHEN USING WIRELESS REMOTE CONTROLLER When using a wireless remote controller it is necessary to set the wireless remote controller address Refer to the installation manual attached to the wireless remo...

Page 19: ...mote controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate properly when two or more remote controllers are attached to the unit in the simultaneous operation system mode NOTE NOTE NOTE NOTE Terminal numbers of outdoor and indoor units must be matched 12 TO ...

Page 20: ...not OK 4 Press The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Return Setting Test Operation Return Setting Return Setting Air Volume direction Air Volume Direction Position 0 Low Return Setting Return Setting Air Volume direction Air Volume Direction Low Position ...

Page 21: ...RVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M P DRAIN PUMP MOTOR M S SWING MOTOR MR MRCW MRM MRN MAGNETIC RELAY N NEUTRAL n N NUMBER OF PASSES THROUGH FERRITE CORE PAM PULSE AMPLITUDE MODULATION PCB PRINTED CIRCUIT BOARD PM POWER...

Page 22: ...4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM ...

Page 23: ...4P469440 1H 2019 02 Copyright 2017 Daikin 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM ...

Reviews: