background image

9

English

• After piping is finished, cut the removed penetration 

cover along the shape of piping, and install it.
Also, for top panel penetration cover, as it was before 
removed, put the horizontal blade motor and thermistor 
lead through the clamp of the top panel penetration cover 
and fix. (Refer to Fig. 16 and Fig. 19)
When doing this, block any gaps between the piping pen-
etration cover and the piping using putty field supply to 
prevent dust from entering the indoor unit.

NOTE

NOTE

NOTE

NOTE

1. When carrying out leakage test of refrigerant piping and the 

indoor unit after the installation of indoor unit is finished, 
confirm the connecting outdoor unit installation manual for 
test pressure. Refer to also the outdoor unit installation 
manual or technical document for refrigerant piping.

2. In case of refrigerant shortage due to forgetting additional 

refrigerant charge etc., it will result in malfunction such as 
does not cool or does not heat. Refer to the outdoor unit 
installation manual or technical document for refrigerant 
piping.

7.

DRAIN PIPING WORK

(1) Carry out drain piping.

• Carry out drain piping so that drainage is ensured.
• Drain piping can be connected from the following direc-

tions: For right rear/right side, refer to Fig. 18 of ‘‘6. 
REFRIGERANT PIPING WORK’’, and for left rear/left 
side, refer to Fig. 20.

• When conducting left rear/left side drain piping, remove 

the protection net. Then, remove the drain socket cap 
and insulation material applied to left side drain socket 
and apply them to the right side drain socket. When doing 
this, insert the drain socket cap all the way in to prevent a 
water leakage.
After the drain hose (1) (accessory) installing, attach the 
protection net by reversing the steps taken to remove it. 
(Refer to Fig. 21)

• Select the piping diameter equal to or larger than that of 

the drain hose (1) (accessory) (polyvinyl chloride piping, 
nominal diameter 20mm, outside diameter 26mm).

• Install the drain piping as short as possible with down-

ward inclination of 1/100 or more by avoiding air stagna-
tion. (Refer to Fig. 22 and Fig. 23)
(It may cause abnormal sound such as bubbling noise.)

CAUTION

If drain stagnates in the drain piping, the piping may be 
clogged.

• Make sure to use the attached drain hose (1) and metal 

clamp (2). Also, insert the drain hose (1) into the root of 
the drain socket, and tighten the metal clamp (2) at the 
root of the drain socket tightly. 
(Refer to Fig. 24 and Fig. 25)
(Install the metal clamp (2) so that the tightening part is in 
the range of about 45°as shown in the Fig. 25.)
(Do not bond the drain socket and drain hose. If so, main-
tenance and inspection for the heat exchanger and oth-
ers cannot be conducted.)

Screw
(put back to the indoor unit)

Decoration side panel (right)
Separating parts

Cut only this part when laying only 
the drain piping on the right side.

Stay for packing and delivering
(reinforcing plate)

Right side refrigerant piping

Rear side drain piping

Rear side refrigerant piping

Right side drain piping

Fig. 18

Thermistor lead

Horizontal blade motor lead

Top panel penetration 
cover clamp part

Fig. 19

View from air inlet side

Back side (sheet metal)
Detach parts

Putty or insulation

(field supply)

Left side
Drain piping

Left side
Detach parts

Left rear side
Drain piping

Fig. 20

Protection net

Fixing 
screw for
protection net

Fig. 21

Good

Wrong

Supports

1-1.5m

Downward inclination of 1/100 or more

Do not lift

Make sure there is no slack

Make sure it is not in the water

Fig. 22

Fig. 23

4PEN469440-1H.book  Page 9  Friday, March 22, 2019  2:36 PM

Summary of Contents for FHA100AVEB9

Page 1: ...INSTALLATION MANUAL FHA35AVEB99 FHA50AVEB99 FHA60AVEB99 FHA71AVEB99 FHA100AVEB9 FHA125AVEB9 FHA140AVEB9 Split System air conditioners 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM ...

Page 2: ... 2 5 8 286 2 4 4 74 6 0 22 8 2 4 49 0 6 0 306 2 6 5 13 6 2 24 3 2 6 57 5 6 2 327 2 8 5 53 6 4 25 9 2 8 66 7 6 4 349 3 0 5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31 0 3 4 98 4 7 0 417 3 6 8 20 7 2 32 8 3 6 110 7 2 441 3 8 9 14 7 4 34 7 3 8 123 7 4 466 4 0 10 1 7 6 36 6 4 0 136 7 6 492 4 2 11 2 7 8 38 5 4 2 150 7 8 518 4 4 12 3 7 956 40 1 4 4 165 7 956 539 m kg ...

Page 3: ...com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertifikat C 13 Huom jotka o...

Page 4: ...r dealer regarding what to do in case of refrigerant leakage When the air conditioner is installed in a small room it is nec essary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentration limit in the event of a leakage Otherwise this may lead to an accident due to oxygen defi ciency Be sure to use only the specified parts and accessories for installa...

Page 5: ...agnetic waves Electromagnetic waves may disturb the control system and cause malfunction of the equipment 4 Where flammable gases may leak where carbon fibre or ignitable dust is suspended in the air or where volatile flammables such as thinner or gasoline are handled If the gas should leak and remained around the air condi tioner it may cause ignition The air conditioner is not intended for use i...

Page 6: ...or unit installation manual Does not cool Does not heat Is the insulation of refriger ant piping and drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is the power supply voltage identical to that stated in the manufacturer s label on the air conditioner Does not operate burnout Are you sure that there is no wrong wiring or piping or no loose wiring D...

Page 7: ...radios to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise Install the indoor unit as far as possible from fluorescent lamps If a wireless remote controller kit is installed the transmission distance may be shorter in a room where an electronic light ing type inverter or rapid start type fluorescent lamp is installe...

Page 8: ...tion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name FHA A B C D E F G H J Class 35 50 960 920 378 324 270 375 398 377 260 Class 60 71 1270 1230 533 479 425 530 553 532 415 Class 100 125 140 1590 1550 693 639 585 690 713 692 575 G H J 5 175 200 View from...

Page 9: ... for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tighten the hanger fixing screws M5 at 2 places which were removed as they were before Refer to Fig 11 It is necessary to prevent misalignment of the indoor unit 4 Tighten the hanger installing bolts M8 ...

Page 10: ...r Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and or lead to corrosion of flared joints soap water may con tain ammonia which causes a corrosive effect between the brass flare nut and the copper flare CAUTION This air conditioner is a dedicated model for refrigerant R410A or R32 Make sure...

Page 11: ...ccessory to con duct piping Refer to Fig 16 and Fig 17 3 For right side piping Remove the stay for packing and delivering reinforcing plate at the right side and put back the screw to the orig inal position of the indoor unit Refer to Fig 18 Open the knockout hole at the decoration side panel right and connect piping Refer to Fig 18 Fig 15a Gas piping Liquid piping Indoor unit Joint insulating mat...

Page 12: ...cessory installing attach the protection net by reversing the steps taken to remove it Refer to Fig 21 Select the piping diameter equal to or larger than that of the drain hose 1 accessory polyvinyl chloride piping nominal diameter 20mm outside diameter 26mm Install the drain piping as short as possible with down ward inclination of 1 100 or more by avoiding air stagna tion Refer to Fig 22 and Fig...

Page 13: ...or The ammonia in the sewage may go through the drain piping and corrode the heat exchanger of the indoor unit When installing the drain pump kit optional accessory also refer to the installation manual included to the drain pump kit 2 After piping is finished check if the drain flows smoothly Gradually put about 0 6 liter of water for drain confirma tion into the drain pan from the air outlet Ref...

Page 14: ...e when conduit piping are used When the conduit piping are not used use H07RN F 60245 IEC 66 2 Sheathed vinyl cord or cable insulation thickness 1mm or more 9 HOW TO CONNECT WIRINGS AND WIRING EXAMPLE Wiring connection method Caution for wiring The indoor units in the same system can be connected to the power supply from one branch switch However selection of branch switch branch overcurrent circu...

Page 15: ...the wiring fixture 11 and clamp 4 attached to bind the wiring without applying tension to the connecting section of the wirings Remote controller wiring R10 or more Terminal block X2M R10 or more Transmission and earth wiring connection method R10 or more Earth terminal Outdoor unit Indoor unit Terminal block Terminal block Terminal numbers of outdoor and indoor units must be matched Transmission ...

Page 16: ... attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2 indoor units 2 indoor units operates equally Refer to Fig 32 Group control 1 remote controller controls up to 16 indoor units All indoor units operate according to the remote controller Refer to Fig ...

Page 17: ...en using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add wiring between the remote controller 2 Sub and the terminal P1 P2 of the terminal block X1M for the remote controller in the control box There is no polarity NOTE NOTE NOTE NOTE Terminal numbers of ou...

Page 18: ...hose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WHEN USING WIRELESS REMOTE CONTROLLER When using a wireless remote controller it is necessary to set the wireless remote controller address Refer to the installation manual attached to the wireless remo...

Page 19: ...mote controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate properly when two or more remote controllers are attached to the unit in the simultaneous operation system mode NOTE NOTE NOTE NOTE Terminal numbers of outdoor and indoor units must be matched 12 TO ...

Page 20: ...not OK 4 Press The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Return Setting Test Operation Return Setting Return Setting Air Volume direction Air Volume Direction Position 0 Low Return Setting Return Setting Air Volume direction Air Volume Direction Low Position ...

Page 21: ...RVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M P DRAIN PUMP MOTOR M S SWING MOTOR MR MRCW MRM MRN MAGNETIC RELAY N NEUTRAL n N NUMBER OF PASSES THROUGH FERRITE CORE PAM PULSE AMPLITUDE MODULATION PCB PRINTED CIRCUIT BOARD PM POWER...

Page 22: ...4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM ...

Page 23: ...4P469440 1H 2019 02 Copyright 2017 Daikin 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM ...

Reviews: