17

English

2.  Start the test run.

Table 9

3. Check operation for 3 minutes.
4. Check operation of the airflow direction.

Table 10

5. Stop the test run.

Table 11

12-1

ERROR CODES WHEN PERFORMING A TEST RUN

If the installation of the outdoor unit has NOT been done cor-
rectly, the following error codes may be displayed on the user 
interface:

CAUTION

After test operation is completed, check the items mentioned in 
the clause 2 “Items to be checked after the installation work is 
completed” on page 3
.
If the interior finish work is not completed when the test opera-
tion is finished, for protection of the air conditioner, ask the cus-
tomer not operate the air conditioner until the interior finish work 
is completed. 
If the air conditioner is operated, the inside of the indoor units 
may be polluted by substances generated from the coating and 
adhesives used for the interior finish work and cause water 
splash and leakage. 

To the operator carrying out test operation

After test operation is completed, before delivering the air con-
ditioner to the customer, confirm that the control box cover is 
closed.
In addition, explain the power supply status (power supply ON/
OFF) to the customer.

#

Action

Result

1

Go to the home menu

2

Press at least 4 seconds.

The Service Setting menu is dis-

played.

3

Select the Test Operation.

4

Press.

Test Operation is displayed on 

the home menu.

5

Press within 10 seconds.

Test run starts.

#

Action

Result

1

Press.

2

Select Position 0.

3

Change the position.

If the airflow flap of the indoor 
unit moves, operation is OK.
If not, operation is not OK.

4

Press.

The home menu is displayed.

Cool

Set to

28

°C

Return

Setting

Service Settings                   1/3

Test Operation

Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address

Cool

Return

Setting

Test Operation

Return Setting

Return

Setting

Air Volume/direction

Air Volume

Direction

Position 0

Low

Return Setting

Return

Setting

Air Volume/direction

Air Volume

Direction

Low

Position 0

#

Action

Result

1

Press at least 4 seconds.

The Service Settings menu is 
displayed.

2

Select Test Operation.

3

Press.

The unit returns to normal oper-
ation, and the home menu is dis-
played.

Error code

Possible cause

Nothing displayed 
(The currently set 
temperature is not 
displayed)

•  The wiring is disconnected or there is a wiring 

error (between power supply and outdoor 
unit, between outdoor unit and indoor units, 
between indoor unit and remote controller)

•  The fuse on the outdoor unit PCB has blown 

out.

E3, E4 or L8

•  The stop valves are closed.
•  The air inlet or air outlet is blocked. 

E7

•  There is a missing phase in case of three-

phase power supply units.

•  Note: Operation will be impossible. Turn OFF 

the power, recheck the wiring, and switch 
two of the three electrical wires.

L4

The air inlet or air outlet is blocked.

U0

The sop valves are closed.

U2

•  There is a voltage imbalance. 
•  There is a missing phase in case of three-

phase power supply units. Note: Operation 
will be impossible. Turn OFF the power, 
recheck the wiring, and switch two of the 
three electrical wires.

U4 or UF

The inter-unit branch wiring is not correct.

UA

The outdoor and indoor unit are incompatible.

Return

Setting

Service Settings                   1/3

Test Operation

Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address

4PEN469440-1H.book  Page 17  Friday, March 22, 2019  2:36 PM

Summary of Contents for FHA100AVEB9

Page 1: ...INSTALLATION MANUAL FHA35AVEB99 FHA50AVEB99 FHA60AVEB99 FHA71AVEB99 FHA100AVEB9 FHA125AVEB9 FHA140AVEB9 Split System air conditioners 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM ...

Page 2: ... 2 5 8 286 2 4 4 74 6 0 22 8 2 4 49 0 6 0 306 2 6 5 13 6 2 24 3 2 6 57 5 6 2 327 2 8 5 53 6 4 25 9 2 8 66 7 6 4 349 3 0 5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31 0 3 4 98 4 7 0 417 3 6 8 20 7 2 32 8 3 6 110 7 2 441 3 8 9 14 7 4 34 7 3 8 123 7 4 466 4 0 10 1 7 6 36 6 4 0 136 7 6 492 4 2 11 2 7 8 38 5 4 2 150 7 8 518 4 4 12 3 7 956 40 1 4 4 165 7 956 539 m kg ...

Page 3: ...com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertifikat C 13 Huom jotka o...

Page 4: ...r dealer regarding what to do in case of refrigerant leakage When the air conditioner is installed in a small room it is nec essary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentration limit in the event of a leakage Otherwise this may lead to an accident due to oxygen defi ciency Be sure to use only the specified parts and accessories for installa...

Page 5: ...agnetic waves Electromagnetic waves may disturb the control system and cause malfunction of the equipment 4 Where flammable gases may leak where carbon fibre or ignitable dust is suspended in the air or where volatile flammables such as thinner or gasoline are handled If the gas should leak and remained around the air condi tioner it may cause ignition The air conditioner is not intended for use i...

Page 6: ...or unit installation manual Does not cool Does not heat Is the insulation of refriger ant piping and drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is the power supply voltage identical to that stated in the manufacturer s label on the air conditioner Does not operate burnout Are you sure that there is no wrong wiring or piping or no loose wiring D...

Page 7: ...radios to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise Install the indoor unit as far as possible from fluorescent lamps If a wireless remote controller kit is installed the transmission distance may be shorter in a room where an electronic light ing type inverter or rapid start type fluorescent lamp is installe...

Page 8: ...tion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name FHA A B C D E F G H J Class 35 50 960 920 378 324 270 375 398 377 260 Class 60 71 1270 1230 533 479 425 530 553 532 415 Class 100 125 140 1590 1550 693 639 585 690 713 692 575 G H J 5 175 200 View from...

Page 9: ... for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tighten the hanger fixing screws M5 at 2 places which were removed as they were before Refer to Fig 11 It is necessary to prevent misalignment of the indoor unit 4 Tighten the hanger installing bolts M8 ...

Page 10: ...r Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and or lead to corrosion of flared joints soap water may con tain ammonia which causes a corrosive effect between the brass flare nut and the copper flare CAUTION This air conditioner is a dedicated model for refrigerant R410A or R32 Make sure...

Page 11: ...ccessory to con duct piping Refer to Fig 16 and Fig 17 3 For right side piping Remove the stay for packing and delivering reinforcing plate at the right side and put back the screw to the orig inal position of the indoor unit Refer to Fig 18 Open the knockout hole at the decoration side panel right and connect piping Refer to Fig 18 Fig 15a Gas piping Liquid piping Indoor unit Joint insulating mat...

Page 12: ...cessory installing attach the protection net by reversing the steps taken to remove it Refer to Fig 21 Select the piping diameter equal to or larger than that of the drain hose 1 accessory polyvinyl chloride piping nominal diameter 20mm outside diameter 26mm Install the drain piping as short as possible with down ward inclination of 1 100 or more by avoiding air stagna tion Refer to Fig 22 and Fig...

Page 13: ...or The ammonia in the sewage may go through the drain piping and corrode the heat exchanger of the indoor unit When installing the drain pump kit optional accessory also refer to the installation manual included to the drain pump kit 2 After piping is finished check if the drain flows smoothly Gradually put about 0 6 liter of water for drain confirma tion into the drain pan from the air outlet Ref...

Page 14: ...e when conduit piping are used When the conduit piping are not used use H07RN F 60245 IEC 66 2 Sheathed vinyl cord or cable insulation thickness 1mm or more 9 HOW TO CONNECT WIRINGS AND WIRING EXAMPLE Wiring connection method Caution for wiring The indoor units in the same system can be connected to the power supply from one branch switch However selection of branch switch branch overcurrent circu...

Page 15: ...the wiring fixture 11 and clamp 4 attached to bind the wiring without applying tension to the connecting section of the wirings Remote controller wiring R10 or more Terminal block X2M R10 or more Transmission and earth wiring connection method R10 or more Earth terminal Outdoor unit Indoor unit Terminal block Terminal block Terminal numbers of outdoor and indoor units must be matched Transmission ...

Page 16: ... attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2 indoor units 2 indoor units operates equally Refer to Fig 32 Group control 1 remote controller controls up to 16 indoor units All indoor units operate according to the remote controller Refer to Fig ...

Page 17: ...en using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add wiring between the remote controller 2 Sub and the terminal P1 P2 of the terminal block X1M for the remote controller in the control box There is no polarity NOTE NOTE NOTE NOTE Terminal numbers of ou...

Page 18: ...hose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WHEN USING WIRELESS REMOTE CONTROLLER When using a wireless remote controller it is necessary to set the wireless remote controller address Refer to the installation manual attached to the wireless remo...

Page 19: ...mote controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate properly when two or more remote controllers are attached to the unit in the simultaneous operation system mode NOTE NOTE NOTE NOTE Terminal numbers of outdoor and indoor units must be matched 12 TO ...

Page 20: ...not OK 4 Press The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Return Setting Test Operation Return Setting Return Setting Air Volume direction Air Volume Direction Position 0 Low Return Setting Return Setting Air Volume direction Air Volume Direction Low Position ...

Page 21: ...RVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M P DRAIN PUMP MOTOR M S SWING MOTOR MR MRCW MRM MRN MAGNETIC RELAY N NEUTRAL n N NUMBER OF PASSES THROUGH FERRITE CORE PAM PULSE AMPLITUDE MODULATION PCB PRINTED CIRCUIT BOARD PM POWER...

Page 22: ...4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM ...

Page 23: ...4P469440 1H 2019 02 Copyright 2017 Daikin 4PEN469440 1H book Page 1 Friday March 22 2019 2 36 PM ...

Reviews: