![background image](http://html1.mh-extra.com/html/daikin/fdyq100lbv1/fdyq100lbv1_installation-manual_2460406015.webp)
14
Ducted Air Conditioners
Installation Manual
Field Settings
How to Change the Field Settings with the Wired Remote Controller
The following functions of indoor unit can be changed from the remote controller. At the item of installation or
after service inspection / repair, make the local setting in accordance with the following description.
Wrong setting may cause malfunction.
•
Setting indoor fan target speed
•
Setting for T1, T2 input
•
Setting air filter sign
•
Setting for thermostat differential
•
Setting temperature sensor location
•
Setting for thermostat sensor in remote
•
Indoor fan setting during heating thermo
•
Setting for permission level
•
Indoor fan setting during cooling thermo
•
Setting for home leave function
•
Indoor fan setting during heating/cooling
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be required to change.
Refer to information in the option handbook.)
Wired Remote Controller <BRC1E62>
-1
Press and hold the Cancel button
for 4 seconds or longer.
Service Settings menu is
displayed.
-2
Select
Field settings
in the
Service Settings menu, and
press Menu/Enter button.
Field settings screen is
displayed.
-3
Highlight the Mode No., and
select desired “Mode No.” by
using “ “ (Down/Up) button.
For the commonly-used field
setting item, refer to page 14
and 15.
-4
In the case of setting per indoor
unit during group control (When
Mode No. such as
20
,
21
,
22
,
23
,
25
are selected),
“Indoor unit No.” to be set by
using “ “ (Down/Up) button.
(In case of group setting, this
operation is not needed.)
In case of individual setting
per indoor unit, current settings
are displayed. And, SECOND
CODE NO. “
-
” means no
function.
-5
Highlight SECOND CODE NO. of
the FIRST CONE NO. to be
changed, and select desired
“SECOND CODE NO.” by using
“ “ (Down/Up) button.
Multiple identical mode number
settings are available.
In case of group setting, all of
SECOND CODE NO. which may
be set are displayed as “
*
“.
“
*
“ is changed to SECOND
CODE NO. to be set.
And, SECOND CODE NO. “
-
”
means no function.