background image

5

Ducted Air Conditioners

Installation Manual

NOTE TO THE INSTALLER

Be sure to instruct the customer how to properly operate the system (especially cleaning filters, operating the 
different functions and adjusting the temperature). It is recommended to ask the customer to carry out the 

operations themselves while you instruct them and refer them to the applicable place in the operation manual. 

FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK 

AFTER INSTALLATION IS FINISHED.

(1)  Items to be checked after completion of work.

Items to be checked

If not properly done, what is likely to occur

Check

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling or heating.

Does the unit require external insulation?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip. 

Does the power supply voltage correspond to that shown 

on the name plate?

The unit may malfunction or the components burn out.

Is the wiring and piping correct?

The unit may malfunction or the components burn out.

Is the unit safely grounded?

Dangerous during electric leakage.

Is the wiring size according to specification?

The unit may malfunction or the components burn out.

Is something blocking the air outlet or inlet of either the 

indoor or outdoor units?

It may result in insufficient cooling or heating.

Are refrigerant piping length and additional refrigerant 

charge noted down?

The refrigerant charge in the system is not clear.

Is the indoor unit positioned so that it is not in contact 

with parts of the ceiling?

Vibration and noise can be transmitted into building.

Is the airflow within specification?

Poor performance or malfunction.

Is an air filter installed in the return air?

Blocked heat exchanger causing malfunction or 

compressor failure.

Is an external drain tray installed?

Condensate water may drip.

(2)  Items to be checked at completion

• 

Did you show the customer how to operate the system while referring to the operation manual? 

 

  Detailed explanation about operation.      

 

Review the safety consideration.

• 

Did you hand the operation manual over to the customer?

SELECTING INSTALLATION SITE

(1) Select an installation site where the following 

 

  

     conditions are fulfilled and that meets your 

 

  

    

 

customer’s 

approval. 

    

 

      

 

        

• 

Where the indoor unit and remote controller are   

   

not exposed to rain or moisture.               

 

  

• 

Where the casing of the unit does not contact  

 

   

parts of the ceiling. 

 

 

 

 

  

• 

Where optimum air distribution can be ensured.   

   

• 

Where nothing blocks the air passage.   

 

   

• 

Where condensate can be properly drained. 

 

  

• 

Where the structure is strong enough to safely 

bear the indoor unit weight. 

 

 

 

 

 

• 

Where sufficient clearance for maintenance and    

  

service can be ensured. (see Fig. 1) 

 

 

  

 

• 

Where there is no risk of flammable gas leakage.

• 

Where piping between indoor and outdoor units is

possible within the allowable limit. (Refer to the 

installation manual for the outdoor unit.)

CAUTION

• 

Keep the indoor unit, outdoor unit, power supply

wiring and transmission wiring at least 1 metre

away from televisions and radios. This is to

prevent image interference and noise in those

electrical appliances. (Noise may be generated

depending on the conditions under which the 

electrical wave is generated, even if 1 metre is kept.)

(2) When using suspension bolts for installation, hanging

brackets should be installed. Confirm that the 

ceiling is strong enough to support the weight of

the indoor unit.

Summary of Contents for FDYQ100LBV1

Page 1: ...onditioners MODELS Ceiling concealed duct type FDYQ N 71LBV1 FDYQ T N 100LBV1 FDYQ T 125LBV1 FDYQ T 140LCV1 FDYQ T 160LBV1 PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL...

Page 2: ......

Page 3: ...6 INDOOR UNIT INSTALLATION 7 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK 9 ELECTRICAL WIRING WORK 10 WIRING EXAMPLE 12 FIELD SETTINGS 14 TEST OPERATION 19 CHECKING PROCEDURE FOR ERROR RECORD 22 REGIS...

Page 4: ...ak Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove or cooker Before obtaining access to the terminals and e...

Page 5: ...TIONS Be sure to read this manual before installing the indoor unit This unit is for indoor use only This unit is suitable for installation in a household commercial and light industrial environment D...

Page 6: ...bration and noise can be transmitted into building Is the airflow within specification Poor performance or malfunction Is an air filter installed in the return air Blocked heat exchanger causing malfu...

Page 7: ...r is introduced into the ceiling or the unit operates for 24 hours It is also important that a safety drain tray be used see Fig 11 PREPARATION BEFORE INSTALLATION To facilitate installation the indoo...

Page 8: ...as shown in the diagrams Fig 6 4 Tighten the upper nut REFRIGERANT PIPING WORK ALL REFRIGERANT PIPING WORK MUST ONLY BE CARRIED OUT BY A QUALIFIED PERSON For refrigerant piping of outdoor units see th...

Page 9: ...ch does not require flux Flux has an extremely harmful influence refrigerant piping systems For instance if chlorine based flux is used it will cause pipe corrosion particularly if the flux contains f...

Page 10: ...piping with either the same diameter or with the diameter larger excluding the raised section than that of the connecting pipe PVC pipe nominal diameter 25mm outside diameter 32mm Keep the drain pipe...

Page 11: ...local codes ie AS NZS 3000 A circuit breaker capable of shutting down power supply to the entire system must be installed Select and install the power supply wiring and transmission wiring in accorda...

Page 12: ...t below the terminal block Do not connect the N line with the earth terminal Wiring between indoor and outdoor units Connect the transmission wire between the indoor and outdoor unit using terminals 1...

Page 13: ...cribed wires are used carry out complete connections and secure the wires so that outside forces are not applied to the terminals CAUTION After connecting the wires be sure that no pressure is applied...

Page 14: ...d o o r u n i t e x a m p l e N I s o l a t i o n s w i t c h F u s e N P o w e r s u p p l y N L N L M a i n p o w e r s u p p l y I s o l a t i o n s w i t c h F u s e N I s o l a t i o n s w i t c...

Page 15: ...ormation in the option handbook Wired Remote Controller BRC1E62 1 Press and hold the Cancel button for 4 seconds or longer Service Settings menu is displayed 2 Select Field settings in the Service Set...

Page 16: ...ory setting is the highest speed ie 15 so if you experience excessive airflow during post installation checks please follow the field setting instructions to set a lower airflow Please note that any c...

Page 17: ...low Adjustment is successful do steps 3 to 4 7 02 should appear if not set the Automatic Airflow Adjustment again Note 1 If the indoor unit does not stop in the period of 10 minutes or 7 02 does not a...

Page 18: ...17 Ducted Air Conditioners Installation Manual OTHER SETTINGS Applicable to all models...

Page 19: ...ower Checking the connection Please stand by During above display backlight does not light by button operation When 1 indoor unit is controlled by 2 remote controllers Be sure to set sub remote contro...

Page 20: ...n according to following procedure 1 Make sure to turn on the power supply more than 6 hours before operation start with front panel closed to protect compressor 2 Confirm that stop valves of both liq...

Page 21: ...rvice Settings menu is displayed 11 Select Test Operation in the Service Settings menu and press Menu Enter button Basic screen returns and normal operation is conducted Note Test operation will autom...

Page 22: ...ct the failure diagnosis referring to Malfunction code list in the installation manual of the indoor unit After the failure diagnosis finishes press and hold ON OFF button for 4 seconds or longer in t...

Page 23: ...the Service Settings menu and press Menu Enter button The Error History menu screen is displayed 3 Select RC Error History in the Error History menu and press Menu Enter button Malfunction Error code...

Page 24: ...nu and press Menu Enter button Maintenance Contact menu screen is displayed 3 Select Maintenance Contact and press Menu Enter button 4 Enter the telephone number Numeric varies by using Down Up button...

Page 25: ...istor cables Socket location X18A X17A only for FDYQ71LB1 FDYQN100LBV1 models Fig 22 3 Remove 4 screws securing the electrical box to the fan deck compartment Fig 20 4 Untwist wire clamp securing the...

Page 26: ...an motor wiring Fig 20 12 Secure the fan deck compartment with 4 M6 bolts bolt Fig 20 13 Pass the 2 thermistor cables through the rubber bush on the electric box and plug in the respective sockets X18...

Page 27: ...26 Ducted Air Conditioners Installation Manual...

Page 28: ...a Phone 1300 36 24 38 Dakin New Zealand 525 Great South Rd Penrose Auckland 6 www daikin com au DAIKIN INDUSTRIES LTD Head office Umeda Centre Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan T...

Reviews: