6
Ducted Air Conditioners
Installation Manual
•
Hanging brackets are sold as an optional accessory.
(3) If the installation requires the indoor unit to be exposed
please ensure the unit is more than 1.8m above the floor so
that children can not touch the unit.
(4) A suitable air filter (field supplied) must be installed within the
return air duct.
NOTE:
Additional thermal insulation material (thickness 10mm or more of glass wool or polyethylene foam)
may be required if the conditions in the ceiling exceeds 30
o
C and RH 80% or outside air is introduced into the
ceiling or the unit operates for 24 hours. It is also important that a safety drain tray be used. (see Fig. 11)
PREPARATION BEFORE INSTALLATION
To facilitate installation, the indoor unit can be easily separated into smaller parts to make it easier to move to the
final position. See page 23 for details.
Table 1
Model
A
B
C
D
E
F
FDYQ(N)71LBV1
1090
1142
354
863
354
1142
FDYQ(T/N)100LBV1
1128
1180
347
898
347
1180
FDYQ(T)125LBV1
1400
1365
347
898
459
1365
FDYQ(T)140LCV1,
FDYQ(T)160LBV1
1400
1364
377
943
502
1364
(1) Refer to Table
1 and Fig. 3 for suspension bolt position and horizontal representation of the indoor unit.
Electrical box
cover
Fig. 2
Fig. 3
FDYQ(N)71LBV1, FDYQ(T/N)100LBV1
FDYQ(T)125-160LBV1, LCV1