Installation manual

3

FCQ35~14 FCQH71~140C7VEB

Split System air conditioners

4PW31577-1B

Use the installation guide (delivered with the unit) for exact
vertical positioning of the unit. 

Installation is possible when opening dimensions are as follows.
When installing the unit within the frame for fixing ceiling
materials. 

(See figure 4)

2

Make the ceiling opening needed for installation where
applicable. (For existing ceilings.)

-

Refer to the paper pattern for installation for the ceiling 
opening dimensions.

-

Create the ceiling opening required for installation. From the 
side of the opening to the casing outlet, implement the 
refrigerant and drain piping and wiring for remote controller 
(unnecessary for wireless type). Refer to each piping or 
wiring section.

-

After making an opening in the ceiling, it may be necessary 
to reinforce ceiling beams to keep the ceiling level and to 
prevent it from vibrating. Consult the builder for details.

3

Install the suspension bolts. (Use either a W3/8 or M10 size
bolt.)

Use anchors for existing ceilings, and a sunken insert, sunken
anchors or other field supplied parts for new ceilings to reinforce
the ceiling in order to bear the weight of the unit. Adjust
clearance from the ceiling before proceeding further.
Installation example 

(See figure 5)

I

NDOOR

 

UNIT

 

INSTALLATION

When installing optional accessories (except for the decoration
panel), read also the installation manual of the optional accessories.
Depending on the field conditions, it may be easier to install optional
accessories before the indoor unit is installed. However, for existing
ceilings, always install fresh air intake kit before installing the unit.

1

Install the indoor unit temporarily.

-

Attach the hanger bracket to the suspension bolt. Be sure to 
fix it securely by using a nut and washer from the upper and 
lower sides of the hanger bracket.

-

Securing the hanger bracket 

(See figure 6)

2

Fix the paper pattern for installation. (For new ceilings only.)

-

The paper pattern for installation corresponds with the 
measurements of the ceiling opening. Consult the builder for 
details.

-

The centre of the ceiling opening is indicated on the paper 
pattern for installation. The centre of the unit is indicated on 
the unit casing.

-

After removing the packaging material from the paper pattern 
for installation, attach the paper pattern for installation to the 
unit with the attached screws as shown in 

figure 8

.

3

Adjust the unit to the right position for installation.

(See 

"Preparations before installation" on page 2

.)

4

Check if the unit is horizontally levelled.

-

Do not install the unit tilted. The indoor unit is equipped with a 
built-in drain pump and float switch. (If the unit is tilted 
against the direction of the condensate flow (the drain piping 
side is raised), the float switch may malfunction and cause 
water to drip.)

-

Check if the unit is levelled at all four corners with a water 
level or a water-filled vinyl tube as shown in 

figure 12

.

5

Remove the paper pattern for installation. (For new ceilings
only.)

Apply the short side 

of the installation guide in case of 

normal installation

Apply the long side 

of the installation guide in case of 

installation with fresh air intake kit

1

Lower ceiling surface

2

Underside of the unit

1

Dimensions inside frame

2

Opening dimension inside the frame for ceiling

3

Frame

4

Ceiling material

5

Ceiling opening dimension

6

Ceiling-panel overlapping dimension

NOTE

Installation is possible with a ceiling dimension of
910 mm (marked with*). However, to achieve a ceiling-
panel overlapping dimension of 20 mm, the spacing
between the ceiling and the unit should be 35 mm or
less. If the spacing between ceiling and the unit is over
35 mm, attach ceiling material to the part or recover
the ceiling.

1

Ceiling slab

2

Anchor

3

Long nut or turn-buckle

4

Suspension bolt

5

False ceiling

NOTE

All the above parts are field supplied.

For other installation than standard installation,
contact your dealer for details.

1

2

1

2

1

Nut (field supply)

2

Washer (supplied with the unit)

3

Hanger bracket

4

Double nut (field supply, tighten)

1

Paper pattern for installation

2

Centre of the ceiling opening

3

Centre of the unit

4

Screws (supplied with the unit)

1

Water level

2

Vinyl tube

Downloaded from AC-Manual.com Manuals

Summary of Contents for FCQ100C7VEB x 2

Page 1: ...ION MANUAL FCQ35C7VEB FCQ50C7VEB FCQ60C7VEB FCQ71C7VEB FCQ100C7VEB FCQ125C7VEB FCQ140C7VEB FCQH71C7VEB FCQH100C7VEB FCQH125C7VEB FCQH140C7VEB Split System air conditioners Downloaded from AC Manual co...

Page 2: ...1500 3 2 4 5 1 50 100 2 1 3 4 950 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 4 3 1 2 4 100 2 8 2 2 5 10 6 7 5 6 10 8 3 6 4 3 1 2 5 4 1 3 2 5 6 8 11 4 7 9 10 Downlo...

Page 3: ...instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmis t e standardi te ga v i teiste normati...

Page 4: ...the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the installation site use the supplied pa...

Page 5: ...t at a height over 2 7 m for FCQH100 140 units 3 2 m To avoid accidental touching it is recommended to install the unit higher than 2 5 m Refer to Field setting on page 8 and to the decoration panel i...

Page 6: ...urements of the ceiling opening Consult the builder for details The centre of the ceiling opening is indicated on the paper pattern for installation The centre of the unit is indicated on the unit cas...

Page 7: ...shown in the figure below use the supplied accessory parts Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazing without carrying out nitrogen rep...

Page 8: ...ed up 75 mm Testing of drain piping After the piping work is finished check if drainage flows smoothly Add approximately 1 l of water gradually through the air discharge outlet Method of adding water...

Page 9: ...nect to the remote controller wiring terminal block Securely fix the wiring using a clamp as indicated in the figure After connection Attach the small sealing supplied with the unit around the cables...

Page 10: ...anual attached to the outdoor units Confirm the system type Pair type or multi system 1 remote controller controls 1 indoor unit standard system Simultaneous operation system 1 remote controller contr...

Page 11: ...ing the master and slave unit separately Procedure See figure 17 1 Change the Second code No to 02 individual setting so that the slave unit can be individually set Second code No is factory set to 01...

Page 12: ...wired remote controller and start operation by pushing ON OFF button 5 Press Inspection Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation...

Page 13: ...lector switch MAIN SUB SS2 Selector switch wireless address set Connector for optional parts X24A Connector wireless remote controller X33A Connector adaptor for wiring X35A Connector group control ad...

Page 14: ...NOTES NOTES Downloaded from AC Manual com Manuals...

Page 15: ...2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 4 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 1 2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 5 6 4 8 4...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW31577 1B Downloaded from AC Manual com Manuals...

Reviews: