FCQ35~14 FCQH71~140C7VEB
Split System air conditioners
4PW31577-1B

Installation manual

2

For the following items, take special care during 
construction and check after installation is finished

Notes to the installer

Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the system
and show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.

S

ELECTING

 

INSTALLATION

 

SITE

When the conditions in the ceiling are exceeding 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, an
additional insulation is required (minimum 10 

mm thickness,

polyethylene foam).

For this unit you can select different air flow directions. It is necessary
to purchase an optional blocking pad kit to discharge the air in 2, 3 or
4 (closed corners) directions.

1

Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate water can be properly drained.

Where the false ceiling is not noticeably on an incline.

Where sufficient clearance for maintenance and service can be
ensured.

Where there is no risk of flammable gas leaking.

Where piping between indoor and outdoor units is possible within
the allowable limit. (Refer to the installation manual of the outdoor
unit.)

Keep indoor unit, outdoor unit, inter unit wiring and remote
controller wiring at least 1 meter away from televisions and
radios. This is to prevent image interference and noise in those
electrical appliances. (Noise may be generated depending on the
conditions under which the electric wave is generated, even if
1 meter is kept.)

When installing the wireless remote controller kit, the distance
between wireless remote controller and indoor unit might be
shorter if there are fluorescent lights who are electrically started
in the room. The indoor unit must be installed as far as possible
away from fluorescent lights.

2

Ceiling height

This indoor unit may be installed on ceilings up to 3.5 m in
height (for FCQH100~140 units: 4.2 m). However, it becomes
necessary to make field settings using the remote controller
when installing the unit at a height over 2.7 

m (for

FCQH100~140 units: 3.2 m).
To  avoid accidental touching, it is recommended to install the
unit higher than 2.5 m.
Refer to 

"Field setting" on page 8

  and to the decoration panel

installation manual.

3

Air flow directions

Select the air flow directions best suited to the room and point of
installation. (For air discharge in 2 or 3 directions, it is necessary
to make field settings by means of the remote controller and to
close the air outlet(s). Refer to the installation manual of the
optional blocking pad kit and to 

"Field setting" on page 8

(See

figure 1)

 (

: air flow direction)

4

Use suspension bolts for installation. Check whether the ceiling
is strong enough to support the weight of the indoor unit. If there
is a risk, reinforce the ceiling before installing the unit.

(The installation pitch is marked on the paper pattern for
installation. Refer to it to check for points requiring reinforcing.)
Space required for installation see 

figure 2

  (

:  air flow

direction)

P

REPARATIONS

 

BEFORE

 

INSTALLATION

1

Relation of ceiling opening to unit and suspension bolt position.

(See figure 3)

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling or heating.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 
name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 
outdoor units?

It may result in insufficient cooling or heating.

Are refrigerant piping length and additional refrigerant charge 
noted down?

The refrigerant charge in the system might not be clear.

1

All-round air discharge

2

Air discharge in 4 directions

3

Air discharge in 3 directions

4

Air discharge in 2 directions

NOTE

Air flow directions as shown in 

figure 1

  merely

serve as examples of possible air flow directions.

1

Air discharge

2

Air inlet

NOTE

Leave 200 mm or more space where marked with *, on
sides where the air outlet is closed.

Model

H

Model

H

FCQ35~71

214

FCQH71

256

FCQ100~140

256

FCQH100~140

298

1

Refrigerant piping

2

Suspension bolt (x4)

3

Hanger bracket

4

False ceiling

5

Suspension bolt pitch

6

Indoor unit

7

Ceiling opening

8

Decoration panel

Downloaded from AC-Manual.com Manuals

Summary of Contents for FCQ100C7VEB x 2

Page 1: ...ION MANUAL FCQ35C7VEB FCQ50C7VEB FCQ60C7VEB FCQ71C7VEB FCQ100C7VEB FCQ125C7VEB FCQ140C7VEB FCQH71C7VEB FCQH100C7VEB FCQH125C7VEB FCQH140C7VEB Split System air conditioners Downloaded from AC Manual co...

Page 2: ...1500 3 2 4 5 1 50 100 2 1 3 4 950 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 4 3 1 2 4 100 2 8 2 2 5 10 6 7 5 6 10 8 3 6 4 3 1 2 5 4 1 3 2 5 6 8 11 4 7 9 10 Downlo...

Page 3: ...instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmis t e standardi te ga v i teiste normati...

Page 4: ...the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the installation site use the supplied pa...

Page 5: ...t at a height over 2 7 m for FCQH100 140 units 3 2 m To avoid accidental touching it is recommended to install the unit higher than 2 5 m Refer to Field setting on page 8 and to the decoration panel i...

Page 6: ...urements of the ceiling opening Consult the builder for details The centre of the ceiling opening is indicated on the paper pattern for installation The centre of the unit is indicated on the unit cas...

Page 7: ...shown in the figure below use the supplied accessory parts Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazing without carrying out nitrogen rep...

Page 8: ...ed up 75 mm Testing of drain piping After the piping work is finished check if drainage flows smoothly Add approximately 1 l of water gradually through the air discharge outlet Method of adding water...

Page 9: ...nect to the remote controller wiring terminal block Securely fix the wiring using a clamp as indicated in the figure After connection Attach the small sealing supplied with the unit around the cables...

Page 10: ...anual attached to the outdoor units Confirm the system type Pair type or multi system 1 remote controller controls 1 indoor unit standard system Simultaneous operation system 1 remote controller contr...

Page 11: ...ing the master and slave unit separately Procedure See figure 17 1 Change the Second code No to 02 individual setting so that the slave unit can be individually set Second code No is factory set to 01...

Page 12: ...wired remote controller and start operation by pushing ON OFF button 5 Press Inspection Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation...

Page 13: ...lector switch MAIN SUB SS2 Selector switch wireless address set Connector for optional parts X24A Connector wireless remote controller X33A Connector adaptor for wiring X35A Connector group control ad...

Page 14: ...NOTES NOTES Downloaded from AC Manual com Manuals...

Page 15: ...2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 4 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 1 2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 5 6 4 8 4...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW31577 1B Downloaded from AC Manual com Manuals...

Reviews: