background image

 

Installation manual

7

FCQ35~14 FCQH71~140C7VEB

Split System air conditioners

4PW31577-1B

-

When connecting wires of the same gauge, connect them 
according to the figure.

Use the specified electric wire. Connect the wire securely to the
terminal. Lock the wire down without applying excessive force to
the terminal. Use torques according to the table below.

-

When attaching the control box lid, make sure not to pinch 
any wires.

-

After all wiring connections are done, fill in any gaps in the 
casing wiring holes with putty or insulation material (field 
supply) thus to prevent small animals or dirt from entering the 
unit from outside and causing short circuits in the control box.

2

Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal block of the unit
in accordance with electrical equipment standards, when using
two power wiring of a gauge greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

4

Remote controller wiring should be located at least 50 mm away
from inter unit wiring and other wiring. Not following this
guideline may result in malfunction due to electrical noise.

5

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

6

Never connect the inter unit wiring to the remote controller wiring.
This mistake could damage the entire system.

7

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worst case, electric shock
or fire.

W

IRING

 

EXAMPLE

For the wiring of outdoor units, refer to the installation manual
attached to the outdoor units.

Confirm the system type:

Pair type or multi system: 1 remote controller controls 1 indoor
unit (standard system).

Simultaneous operation system: 1 remote controller controls
2 indoor units (2 indoor units operate equally)

Group control: 1 remote controller controls up to 16 indoor units
(All indoor units operate according to the remote controller).

2 remote controller control: 2 remote controllers control 1 indoor
unit.

Pair type or multi system 

(See figure 13)

Simultaneous operation system 

(See figure 14)

Group control 

(See figure 15)

2 remote controller control 

(See figure 16)

Precautions

1

All transmission wiring except for the remote controller wiring is
polarized and must match the terminal symbol.

2

In case of group control, perform the remote controller wiring to
the master unit when connecting to the simultaneous operation
system (wiring to the slave unit is unnecessary).

3

For group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions
(as attached swing flap).

4

When controlling the simultaneous operation system with
2 remote controllers, connect it to the master unit (wiring to the
slave unit is unnecessary).

5

Be sure to connect the wiring to the master unit when combining
with a simultaneous operating multi-type in group control.

6

Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper ground-
ing could result in electric shock.

I

NSTALLATION

 

OF

 

THE

 

DECORATION

 

PANEL

Refer to the installation manual delivered with the decoration panel.

After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel. Otherwise air may leak
through the gap and cause dew drop.

Tightening torque (N•m)

Terminal block for remote controller

0.79~0.97

Terminal block for wiring the units

1.18~1.44

NOTE

The customer has the ability to select the remote
controller thermistor.

1

Main power supply

2

Main switch

3

Fuse

4

Remote controller (optional accessories)

5

Indoor unit (Master)

6

Indoor unit (Slave)

NOTE

It is not necessary to designate indoor unit address
when using group control. The address is auto-
matically set when the power is activated.

Downloaded from AC-Manual.com Manuals

Summary of Contents for FCQ100C7VEB x 2

Page 1: ...ION MANUAL FCQ35C7VEB FCQ50C7VEB FCQ60C7VEB FCQ71C7VEB FCQ100C7VEB FCQ125C7VEB FCQ140C7VEB FCQH71C7VEB FCQH100C7VEB FCQH125C7VEB FCQH140C7VEB Split System air conditioners Downloaded from AC Manual co...

Page 2: ...1500 3 2 4 5 1 50 100 2 1 3 4 950 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 4 3 1 2 4 100 2 8 2 2 5 10 6 7 5 6 10 8 3 6 4 3 1 2 5 4 1 3 2 5 6 8 11 4 7 9 10 Downlo...

Page 3: ...instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmis t e standardi te ga v i teiste normati...

Page 4: ...the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the installation site use the supplied pa...

Page 5: ...t at a height over 2 7 m for FCQH100 140 units 3 2 m To avoid accidental touching it is recommended to install the unit higher than 2 5 m Refer to Field setting on page 8 and to the decoration panel i...

Page 6: ...urements of the ceiling opening Consult the builder for details The centre of the ceiling opening is indicated on the paper pattern for installation The centre of the unit is indicated on the unit cas...

Page 7: ...shown in the figure below use the supplied accessory parts Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazing without carrying out nitrogen rep...

Page 8: ...ed up 75 mm Testing of drain piping After the piping work is finished check if drainage flows smoothly Add approximately 1 l of water gradually through the air discharge outlet Method of adding water...

Page 9: ...nect to the remote controller wiring terminal block Securely fix the wiring using a clamp as indicated in the figure After connection Attach the small sealing supplied with the unit around the cables...

Page 10: ...anual attached to the outdoor units Confirm the system type Pair type or multi system 1 remote controller controls 1 indoor unit standard system Simultaneous operation system 1 remote controller contr...

Page 11: ...ing the master and slave unit separately Procedure See figure 17 1 Change the Second code No to 02 individual setting so that the slave unit can be individually set Second code No is factory set to 01...

Page 12: ...wired remote controller and start operation by pushing ON OFF button 5 Press Inspection Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation...

Page 13: ...lector switch MAIN SUB SS2 Selector switch wireless address set Connector for optional parts X24A Connector wireless remote controller X33A Connector adaptor for wiring X35A Connector group control ad...

Page 14: ...NOTES NOTES Downloaded from AC Manual com Manuals...

Page 15: ...2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 4 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 1 2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 5 6 4 8 4...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW31577 1B Downloaded from AC Manual com Manuals...

Reviews: