background image

 

8

Wiring example

Fit the power supply wiring of each system with a switch and
fuse as shown in 

figure 14

 and 

figure 15

.

Complete system example (3 systems)

Precautions

1.

A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.

2.

For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.

3.

All transmission wiring except for the remote controller wiring is
polarized and must match the terminal symbol.

4.

In case of group control, perform the remote controller wiring to
the master unit when connecting to the simultaneous operation
system (wiring to the slave unit is unnecessary).

5.

When controlling the simultaneous operation system with
2 remote controllers, connect it to the master unit (wiring to the
slave unit is unnecessary).

6.

Be sure to connect the wiring to the master unit when combining
with a simultaneous operating multi-type in group control.

7.

Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.

Field setting

Field setting must be made from the remote controller in accordance
with the installation condition.

Setting can be made by changing the "Mode number", "FIRST
CODE No." and "SECOND CODE No.".

For setting and operation, refer to "Field setting" in the
installation manual of the remote controller.

Setting for optional accessories

In case of connecting optional accessories, refer to the operation
manuals provided with the optional accessories and establish
necessary settings.

External static pressure setting

Settings for external static pressure can be achieved in 2 ways:

Using the airflow automatic adjustment function

Airflow automatic adjustment is the volume of blow-off air that
has been automatically adjusted to the rated quantity.

1

Make sure the test run is done with a dry coil.
If the coil is not dry, run the unit for 2 hours with fan only to dry
the coil.

2

Check if the power supply wiring to the air conditioning unit is
completed along with the duct installation.
If a closing damper is installed in the air conditioning unit, make
sure that it is open.
Also check if the air filter is properly attached into the air
passage on the air suction side of the air conditioning unit.

3

If there is more than one air inlet and outlet, adjust the dampers
so that the airflow rate of each air inlet and outlet is conform with
the designed airflow rate. 
Make sure the air conditioning unit is in fan operation mode.
Press and set the airflow adjustment button on the remote
controller to change the airflow rate to H or L.

4

Setting the airflow automatic adjustment settings.
When the air conditioning unit is running in fan operation mode
perform the next steps:
- stop the air conditioning unit,
- go to field setting mode,
- select mode No. 21 (or 11 in case of group setting),
- set the first code No. to "7",
- set the second code No. to "03".
Return to normal operating mode after setting these settings and
press the ON/OFF operation button. The operation lamp will
light up and the air conditioning unit will start the fan operation
for airflow automatic adjustment.

After 1 to 8 minutes, the air conditioning unit stops operating
automatically when the fan operation for airflow automatic
adjustment has been carried out, the operation lamp will be off.

5

When the air conditioning unit has stopped, check on an indoor
unit if the second code No. of mode No. 21 is set to "02".
If the air conditioning unit does not stop operating or the second
code No. is not "02", repeat step 4.
If the outdoor unit is not turned on, the display on the remote
controller will show "

U4

" or "

UH

" (refer to 

"Test operation" on

page 9

). However, you can continue setting this function

because these messages are only applicable to outdoor units.
After setting this function, be sure to turn on the outdoor unit
before performing the test operation on the outdoor unit.
If any other error display occurs on the display of the remote
controller, refer to 

"Test operation" on page 9

 and the operation

manual of the outdoor unit. Check the defective point.

1

Power supply

2

Main switch

3

Fuse

4

Outdoor unit

5

Indoor unit

6

Remote controller (optional accessory)

When using 1 remote controller for 1 indoor unit. (Normal
operation) (See 

figure 14

 and 

figure 15

)

Use with 2 remote controllers 

(See figure 16)

(a)

(a) Shown in figure is with common power supply

For group control 

(See figure 17)

(a)

NOTE

It is not necessary to designate an indoor unit address
when using group control. The address is automatically
set when the power is activated.

NOTE

To comply with EN/IEC 61000-3-12

(b)

, following wiring

must be considered:

(b) European/International Technical Standard setting the limits for harmonic 

currents produced by equipment connected to low-voltage systems with 
input current >16 A and 

75 A per phase.

L N

1 2 3

Do not adjust the dampers during fan operation for
airflow automatic adjustment.

Mode 

No.

First 

code No.

Second 

code No.

Setting content

11 (21)

7

01

Airflow adjustment is OFF

02

Completion of airflow adjustment

03

Start of airflow adjustment

Summary of Contents for FBQ50D2VEB

Page 1: ...INSTALLATION MANUAL FBQ35D2VEB FBQ50D2VEB FBQ60D2VEB FBQ71D2VEB FBQ100D2VEB FBQ125D2VEB FBQ140D2VEB Split System air conditioners...

Page 2: ...1 2 4 5 3 6a 7c 6b 6c 8 9 10 11 2 1 3 5 4 5 2 1 1 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 6 3 5 6 4 2 1 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4...

Page 3: ...uerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Cer...

Page 4: ...alled at least 2 5 m from the floor Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install...

Page 5: ...he protection must comply with relevant European and national regulations 3 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If...

Page 6: ...duct according to the air inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape or something similar to prevent air escaping NOTE When installing...

Page 7: ...ea heater cooking stove etc Finally insulate as shown in the figures below Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazing without carrying o...

Page 8: ...level or slightly tilted up 75 mm The drain pump mounted in this unit is the high lift type The characteristic of this pump is that the higher the pump is the lower the drainage sound becomes Therefor...

Page 9: ...ically if the main power supply is turned off and then turned back on again Refer to the installation manual delivered with the outdoor unit for the size of power supply electric wire connected to the...

Page 10: ...e the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that they do...

Page 11: ...nd outlet is conform with the designed airflow rate Make sure the air conditioning unit is in fan operation mode Press and set the airflow adjustment button on the remote controller to change the airf...

Page 12: ...on Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation button and operate normally 7 Confirm function of unit according to the operation ma...

Page 13: ...CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING X33A CONNECTOR FOR WIRING X35A CONNECTOR POWER SUPPLY FOR ADAPTOR FIELD WIRING BLK BLACK PNK PINK CONNECTOR BL...

Page 14: ......

Page 15: ...3 4 5 P1 P2 P1 P2 6 1 2 3 2 3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 1 2 L N 3 2 3 2 3 1 2 3 4 5 P1 P2 P1 P2 6 L N L N 1 1 1 1 1 1 L N 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 16 1 4 2 3 5 7 8 11 12...

Page 16: ...4P391818 1B 2015 01 Copyright 2014 Daikin...

Reviews: