3

Mounting the air inlet panel with a canvas connection (See 

figure 7a

)

Mounting the air inlet panel directly (See 

figure 7b

)

Bottom suction (See 

figure 7c

)

2.

The fan speed for this indoor unit is preset to provide standard
external static pressure.
If higher or lower external static pressure is required, reset the
external static pressure by changing the initial setting from the
remote controller. 
Refer to 

"External static pressure setting" on page 8

.

3.

Install the suspension bolts.
(Use M10 size bolt for the suspension bolt.) Use anchors for
existing ceilings, and a sunken insert, sunken anchors or other
field supplied parts for new ceilings to reinforce the ceiling in
order to bear the weight of the unit.

Installation example 

(See 

figure 3

)

Indoor unit installation

When installing optional accessories (except for the air inlet panel),
read also the installation manual of the optional accessories.
Depending on the field conditions, it may be easier to install optional
accessories before the indoor unit is installed.

1.

Install the indoor unit temporarily.
• Attach the hanger bracket to the suspension bolt. Be sure to

fix it securely by using a nut and washer from the upper and
lower sides of the hanger bracket. 

(See figure 4)

2.

Check if the unit is horizontally levelled.
• Do not install the unit tilted. The indoor unit is equipped with a

built-in drain pump and float switch.
(If the unit is tilted against condensate flow, the float switch
may malfunction and cause water to drip.)

• Check if the unit is levelled at all four corners with a water

level or a water-filled vinyl tube as shown in 

figure 9

.

3.

Tighten the upper nut.

Installing the duct

Connect the duct supplied in the field.

Air inlet side

- Attach the duct and intake-side flange (field supply).
- Connect the flange to the main unit with accessory screws 

(7).

- Wrap the intake-side flange and duct connection area with 

aluminum tape or something similar to prevent air escaping.

Air outlet side

- Connect the duct according to the air inside of the outlet-side 

flange.

- Wrap the outlet-side flange and the duct connection area with 

aluminum tape or something similar to prevent air escaping.

NOTE

When installing an air inlet duct, select fixing screws
that shall stick out maximum 5 mm at the inside of the
flange to protect the air filter from damage during
maintenance of the filter.

1

Air inlet duct

2

Inside of the flange

3

Fixing screw

1

Ceiling surface

2

Ceiling opening

3

Air inlet panel (Optional accessory)

4

Indoor unit (Back side)

5

Canvas connection for air inlet panel (Optional accessory)

Model

A (mm)

35+50

760

60+71

1060

100~140

1460

NOTE

The unit can be used with bottom suction by replacing
the interchangeable plate by the air filter holding plate.

1

Air filter holding plate with air filter(s)

2

Interchangeable plate

NOTE

For other installation than standard installation, contact
your Daikin dealer for details.

1

Anchor

2

Ceiling slab

3

Long nut or turn-buckle

4

Suspension bolt

5

Indoor unit

NOTE

All the above parts are field supplied.

For other installation than standard installation,
contact your dealer for details.

1

2

3

5 mm

1

Nut (field supply)

2

Washer for hanger bracket (supplied with the unit)

3

Tighten (double nut)

1

Water level

2

Vinyl tube

When attaching a duct to the intake side, be sure to attach
an air filter inside the air passage on the intake side. (Use
an air filter whose dust collecting efficiency is at least 50%
in a gravimetric technique.)
The included filter is not used when the intake duct is
attached.

- Be sure to insulate the duct to prevent condensation 

from forming. (Material: glass wool or polyethylene 
foam, 25 mm thick)

- Use electric insulation between the duct and the wall 

when using metal ducts to pass metal laths of the net or 
fence shape or metal plating into wooden buildings.

- Be sure to explain about the way of maintaining and 

cleaning local procurements (air filter, grille (both air 
outlet and suction grille), etc.) to your customer.

Air outlet side

Air inlet side

Main unit

Aluminum tape

Aluminum tape

Flange

Flange

(Field supply)

(Field supply)

(Field supply)

(Field supply)

(accessory)

Connection screw (7)

Insulation 
material

Summary of Contents for FBQ50D2VEB

Page 1: ...INSTALLATION MANUAL FBQ35D2VEB FBQ50D2VEB FBQ60D2VEB FBQ71D2VEB FBQ100D2VEB FBQ125D2VEB FBQ140D2VEB Split System air conditioners...

Page 2: ...1 2 4 5 3 6a 7c 6b 6c 8 9 10 11 2 1 3 5 4 5 2 1 1 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 6 3 5 6 4 2 1 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4...

Page 3: ...uerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Cer...

Page 4: ...alled at least 2 5 m from the floor Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install...

Page 5: ...he protection must comply with relevant European and national regulations 3 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If...

Page 6: ...duct according to the air inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape or something similar to prevent air escaping NOTE When installing...

Page 7: ...ea heater cooking stove etc Finally insulate as shown in the figures below Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazing without carrying o...

Page 8: ...level or slightly tilted up 75 mm The drain pump mounted in this unit is the high lift type The characteristic of this pump is that the higher the pump is the lower the drainage sound becomes Therefor...

Page 9: ...ically if the main power supply is turned off and then turned back on again Refer to the installation manual delivered with the outdoor unit for the size of power supply electric wire connected to the...

Page 10: ...e the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that they do...

Page 11: ...nd outlet is conform with the designed airflow rate Make sure the air conditioning unit is in fan operation mode Press and set the airflow adjustment button on the remote controller to change the airf...

Page 12: ...on Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation button and operate normally 7 Confirm function of unit according to the operation ma...

Page 13: ...CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING X33A CONNECTOR FOR WIRING X35A CONNECTOR POWER SUPPLY FOR ADAPTOR FIELD WIRING BLK BLACK PNK PINK CONNECTOR BL...

Page 14: ......

Page 15: ...3 4 5 P1 P2 P1 P2 6 1 2 3 2 3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 1 2 L N 3 2 3 2 3 1 2 3 4 5 P1 P2 P1 P2 6 L N L N 1 1 1 1 1 1 L N 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 16 1 4 2 3 5 7 8 11 12...

Page 16: ...4P391818 1B 2015 01 Copyright 2014 Daikin...

Reviews: