background image

 

6

First perform electric wiring work as instructed in 

"Electric wiring

work" on page 6

 and how to set the remote controller as explained in

"Wiring example and how to set the remote controller" on page 7

.

When electric wiring work is finished

Check drainage flow during COOL running, explained in 

"Test

operation" on page 9

.

When electric wiring work is not finished

Remove the switch box cover and connect the single-phase
power supply and the remote controller to the terminals. (Refer
to chapter 

"Electric wiring work" on page 6

 for switch box

attachment/detachment) (Refer to 

figure 12

 and 

13

)

Connect the single-phase power supply to connections 1 and 2
(as shown in the figure) on the power supply terminal board and
confirm drain operation.

Be aware that the fan will turn during the operation.

After confirming drainage, turn off the power.

Electric wiring work

General instructions

All field wiring and components must be installed by a licensed
electrician and must comply with relevant European and national
regulations.

Use copper wire only.

Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".

All wiring must be performed by an authorized electrician.

Attach the earth leakage circuit breaker and fuse to the power
supply line.

A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with relevant local and national legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.

Refer to the installation manual delivered with the outdoor unit
for the size of power supply electric wire connected to the
outdoor unit, the capacity of the earth leakage breaker and fuse
and for wiring instructions.

Be sure to ground the air conditioner.

Do not connect the ground wire to:
- gas pipes: might cause explosions or fire if gas leaks.
- telephone ground wires or lightning rods: might cause 

abnormally high electric potential in the ground during 
lightning storms.

- plumbing pipes: no grounding effect if hard vinyl piping is 

used.

Make sure that earth wire between the pull relief
and terminal is longer than other wires.

Be sure that the shape of the power supply
cable and any other cable, before entering unit,
should be as shown in this figure.

All cables entering the unit should be fixed by
tie wraps (accessory).

Use long sealing (accesory) to block entrance
of switch box as shown in 

figure 12

.

Caution for drain socket

Do not remove the drain pipe plug. Water might leak out.

The drain outlet is only used to discharge water if the drain
pump is not used or before maintenance. Gently put in and
out the drain plug. Excessive force may deform the drain
socket of the drain pan.

Pulling out the plug 

Do not wiggle the plug up and down

Pushing in the plug

Set the plug and push it by using a crosshead screw-
driver

1

1

Drain plug

1

2

1

Drain plug

2

Crosshead screwdriver

L N

L N

1 2 3

1

Switch box cover

2

Transmission wiring port

3

Power supply wiring port

4

Wiring diagram

5

Switch box

6

Plastic clamp

7

Remote controller wiring

8

Terminal board for unit transmission wiring

9

Power supply wiring

10

Indoor PCB board 1

11

Power supply terminal board

12

Transmission wiring between units

13

Indoor PCB board 2

14

Long sealing

15

Wiring

A

B

A<B

LN

Summary of Contents for FBQ50D2VEB

Page 1: ...INSTALLATION MANUAL FBQ35D2VEB FBQ50D2VEB FBQ60D2VEB FBQ71D2VEB FBQ100D2VEB FBQ125D2VEB FBQ140D2VEB Split System air conditioners...

Page 2: ...1 2 4 5 3 6a 7c 6b 6c 8 9 10 11 2 1 3 5 4 5 2 1 1 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 6 3 5 6 4 2 1 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4...

Page 3: ...uerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Cer...

Page 4: ...alled at least 2 5 m from the floor Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install...

Page 5: ...he protection must comply with relevant European and national regulations 3 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If...

Page 6: ...duct according to the air inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape or something similar to prevent air escaping NOTE When installing...

Page 7: ...ea heater cooking stove etc Finally insulate as shown in the figures below Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazing without carrying o...

Page 8: ...level or slightly tilted up 75 mm The drain pump mounted in this unit is the high lift type The characteristic of this pump is that the higher the pump is the lower the drainage sound becomes Therefor...

Page 9: ...ically if the main power supply is turned off and then turned back on again Refer to the installation manual delivered with the outdoor unit for the size of power supply electric wire connected to the...

Page 10: ...e the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that they do...

Page 11: ...nd outlet is conform with the designed airflow rate Make sure the air conditioning unit is in fan operation mode Press and set the airflow adjustment button on the remote controller to change the airf...

Page 12: ...on Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation button and operate normally 7 Confirm function of unit according to the operation ma...

Page 13: ...CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING X33A CONNECTOR FOR WIRING X35A CONNECTOR POWER SUPPLY FOR ADAPTOR FIELD WIRING BLK BLACK PNK PINK CONNECTOR BL...

Page 14: ......

Page 15: ...3 4 5 P1 P2 P1 P2 6 1 2 3 2 3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 1 2 L N 3 2 3 2 3 1 2 3 4 5 P1 P2 P1 P2 6 L N L N 1 1 1 1 1 1 L N 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 1 2 3 L N 1 2 3 16 1 4 2 3 5 7 8 11 12...

Page 16: ...4P391818 1B 2015 01 Copyright 2014 Daikin...