background image

 

9

Using the remote controller

Check on an indoor unit if the second code of mode No. 21 is set to
"01" (= factory setting). Change the second code according to the
external static pressure of the duct to be connected as shown in
table 2.

Table 2

Setting air filter sign

Remote controllers are equipped with liquid crystal air filter signs
to display the time to clean the air filter.

Change the Second code No. depending on the amount of dirt
or dust in the room. (Second code No. is factory set to "01" for
air filter contamination-light.)

Air filter contamination

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB".

Installation of the decoration panel

Refer to the installation manual attached to the decoration panel.

After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel.

Test operation

Refer to the section of 

"For the following items, take special care

during construction and check after installation is finished" on page 2

.

After finishing the construction of refrigerant piping, drain piping,
and electric wiring, conduct test operation accordingly to protect
the unit.

1

Open the gas side stop valve.

2

Open the liquid side stop valve.

3

Electrify crank case heater for 6 hours.

4

Set to cooling operation with the remote controller and start
operation by pushing ON/OFF button.

5

Press Inspection/Test Operation button 4 times and operate at
Test Operation mode for 3 minutes.

6

Press Inspection/Test Operation button and operate normally.

7

Confirm function of unit according to the operation manual.

If there is no change after airflow adjustment in the
ventilation paths, be sure to perform setting the
automatic airflow adjustment again.

Contact your dealer if there is no change after
performing airflow adjustment in the ventilation paths,
after performing the test operation of the outdoor unit
or when the air conditioning unit is moved to another
location.

If booster fans, an outdoor air processing unit or HRV
via duct are used, do not use automatic airflow
adjustment control with a remote controller.

If the ventilation paths have been changed, perform
the setting of the airflow automatic adjustment again
as described above from step 3 onwards.

NOTE

The second code No. is set to "01" by default.

Mode 

No.

First 

code No.

Second 

code No.

External static pressure (Pa)

FBQ

35

50

60

71

100

125

140

13 (23)

6

01

30

30

30

30

40

50

50

02

03

30

30

30

30

04

40

40

40

40

40

05

50

50

50

50

50

50

50

06

60

60

60

60

60

60

60

07

70

70

70

70

70

70

70

08

80

80

80

80

80

80

80

09

90

90

90

90

90

90

90

10

100

100

100

100

100

100

100

11

110

110

110

110

110

110

110

12

120

120

120

120

120

120

120

13

130

130

130

130

130

130

130

14

140

140

140

140

140

140

140

15

150

150

150

150

150

150

150

Setting

Display interval

Mode No.

First 

code No.

Second 

code No.

Light

±2500 hrs

10 (20)

0

01

Heavy

±1250 hrs

10 (20)

0

02

No display

10 (20)

3

02

NOTE

If the main power supply is turned off during operation,
operation will restart automatically after the power
turns back on again.

Summary of Contents for FBQ50D2VEB

Page 1: ...INSTALLATION MANUAL FBQ35D2VEB FBQ50D2VEB FBQ60D2VEB FBQ71D2VEB FBQ100D2VEB FBQ125D2VEB FBQ140D2VEB Split System air conditioners...

Page 2: ...1 2 4 5 3 6a 7c 6b 6c 8 9 10 11 2 1 3 5 4 5 2 1 1 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 6 3 5 6 4 2 1 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4...

Page 3: ...uerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Cer...

Page 4: ...alled at least 2 5 m from the floor Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install...

Page 5: ...he protection must comply with relevant European and national regulations 3 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If...

Page 6: ...duct according to the air inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape or something similar to prevent air escaping NOTE When installing...

Page 7: ...ea heater cooking stove etc Finally insulate as shown in the figures below Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazing without carrying o...

Page 8: ...level or slightly tilted up 75 mm The drain pump mounted in this unit is the high lift type The characteristic of this pump is that the higher the pump is the lower the drainage sound becomes Therefor...

Page 9: ...ically if the main power supply is turned off and then turned back on again Refer to the installation manual delivered with the outdoor unit for the size of power supply electric wire connected to the...

Page 10: ...e the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that they do...

Page 11: ...nd outlet is conform with the designed airflow rate Make sure the air conditioning unit is in fan operation mode Press and set the airflow adjustment button on the remote controller to change the airf...

Page 12: ...on Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation button and operate normally 7 Confirm function of unit according to the operation ma...