![background image](http://html.mh-extra.com/html/daikin/fbq100dvet/fbq100dvet_service-manual_2460342008.webp)
Procedure to Remove Fan Motor
Si281313E
6
Removal Procedure
5. Procedure to Remove Fan Motor
Procedure
Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
Dismount the backside
plate and bottom plate
according to the removal
procedure for the drain
pan.
Dismount the switch box
lid according to the
removal procedure for it.
1. Removal of motor
connectors
1
Remove the fan motor
connectors.
2
Cut the 3 clamps.
2. Removal of fan housing
FBQ71
Dismount fan housings (1)
and (2) only.
FBQ100 to 140
Fan housings (1), (2), and
(3)
1
Press the protruding
part of the fan housing.
2
Open the fan housing
downward while
pressing the protruding
part.
3
Lift and dismount the
fan housing upward.
Clamp
Clamp
Fan motor
Radiator fins
Backside of EL. compo. box
L1R
A2P
A1P
A3P
Clamp
Inside of EL. compo. box
Fan motor
Fan housing (1)
Fan housing (2)
Fan housing (3)
(except FBQ71)
���
���
���