![background image](http://html.mh-extra.com/html/daikin/fbq100dvet/fbq100dvet_service-manual_2460342010.webp)
Procedure to Remove Drain Pump and Float Switch
Si281313E
8
Removal Procedure
6. Procedure to Remove Drain Pump and Float
Switch
Procedure
Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
1. Removal of service lid (1)
assembly
Precautions for the removal
and attachment of the
service lid (1)
<Removal>
•
Check that the wires are not
twisted or get tangled.
<Attachment>
1. Attach the lid after checking
that the wires are not twisted
or tangled.
2. Check that the wires are not
caught between the lid (1)
and side plate.
3. Open the inspection port
after attachment work, and
check that the wires are not
in contact with or caught by
the float and that the float
operates normally.
(Otherwise, repeat
inspection steps 1 through
3.)
1
Remove the 5 screws
to dismount the service
lid (1) assembly.
2. Removal of drain pump
1
Cut the cable tie and
pull out the drain hose.
2
Remove the 2 screws
with washers to
dismount the drain
pump.
3. Removal of float switch
1
Remove the single
screw and slide the
float switch.
Service lid (1)
Drain hose
Drain pump
Cable tie
Fixing screw
Screw