![background image](http://html1.mh-extra.com/html/daikin/fbq-c/fbq-c_technical-data-manual_2460340011.webp)
• Split Sky Air • Indoor Units
9
• Indoor Units • R-410A • FBQ-C7VEB
5
Dimensional drawing & centre of gravity
5 - 1 Dimensional drawing
FBQ100-140C
3TW31254-1A
NOTE
1
Refer to ‘outlook drawing for installing optional
accessories’ when installing optional accessories.
2
The required ceiling depth varies according to the
configuration of the specific system.
3
For maintenance of the air filter, it is necessary to
provide a service access panel.
Refer to the ‘filter installation method’ drawing.
View A-A
Detail B
Suspension bolt
(Service space)
Detail B
35
0 or
mor
e
(S
er
vi
ce sp
ace
)
(Suspension position)
631 (Suspension
posit
ion)
500 or more
Fresh air intake position
(Knock out hole)
(On circumference)
Nr
Name
Description
1
Liquid pipe connection
ø 9.52 flare (connection)
2
Gas pipe connection
ø 15.90 (flare connection)
3
Drain pipe connection
VP25 (O.D. ø 32 /I.D. ø 25)
4
Remote control wiring connection
5
Power supply connection
6
Drain hole
VP25 (OD ø 32 /I.D. ø 25)
7
Air filter
8
Air suction side
9
Air discharge side
10
Nameplate