SiBE12-713
Specifications
Specifications
31
50Hz 230V
Note:
1. The operating sound is based on the rear side suction inlet and the external static pressure 30 Pa.
Operating sound for under side suction inlet : [operating sound for rear side suction inlet] +6 dB.
However, when installation to which the external static pressure becomes low is carried out,
6 dB or more may go up.
Model
FDXS25EAVMB
FDXS35EAVMB
Cooling
Heating
Cooling
Heating
Rated Capacity
2.5kW Class
3.5kW Class
Front Panel Color
—
—
Air Flow Rates
m³/min
(cfm)
H
8.7 (307)
8.7 (307)
8.7 (307)
8.7 (307)
M
8.0 (282)
8.0 (282)
8.0 (282)
8.0 (282)
L
7.3 (258)
7.3 (258)
7.3 (258)
7.3 (258)
SL
6.2 (219)
6.2 (219)
6.2 (219)
6.2 (219)
Fan
Type
Sirocco Fan
Sirocco Fan
Motor Output
W
62
62
Speed
Steps
5 Steps, Quiet, Auto
5 Steps, Quiet, Auto
Air Filter
Removable-Washable-Mildew Proof
Removable-Washable-Mildew Proof
Running Current (Rated)
A
0.48
0.48
0.48
0.48
Power Consumption (Rated)
W
71
71
71
71
Power Factor
%
64.3
64.3
64.3
64.3
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
200×700×620
200×700×620
Packaged Dimensions (H×W×D)
mm
274×906×751
274×906×751
Weight
kg
21
21
Gross Weight
kg
29
29
Operation
Sound
H/M/L/SL
dBA
35/33/31/29
35/33/31/29
35/33/31/29
35/33/31/29
External Static Pressure
Pa
30
30
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Piping Connection
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
9.5
φ
9.5
Drain
mm
VP20 (O.D.
φ
26 / I.D.
φ
20)
VP20 (O.D.
φ
26 / I.D.
φ
20)
Drawing No.
3D051881A
3D051883A
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Summary of Contents for F-Series
Page 1: ... Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump F Series SiBE12 713 ...
Page 11: ...Introduction SiBE12 713 x ...
Page 47: ...Specifications SiBE12 713 36 Specifications ...
Page 113: ...Control Specification SiBE12 713 102 Function and Control ...
Page 122: ...SiBE12 713 Instruction Operation Manual 111 FTK X S 20 25 35 C Names of parts Indoor Unit ...
Page 235: ...Instruction SiBE12 713 224 Operation Manual ...
Page 297: ...Check SiBE12 713 286 Service Diagnosis ...
Page 316: ...SiBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points ...