SiBE12-713
Outdoor Unit
Removal Procedure
297
14
The figure shows the
arrangement of the wire
harness under the
electrical box.
15
Undo the wire clip for
the thermistor lead wire.
3. Remove the electrical box
1
Loosen the 2 screws of
the earth terminal.
4. Disconnect the power
supply connecting wires
★
Illustrations are for 3 room
model.
1
Loosen the screws on
the terminal board and
disconnect the wires of
A, B, C, and D port.
Step
Procedure
Points