Installation manual

4

EWYQ080~250DAYN

Packaged air-cooled water chillers

4PW35559-1D – 03.2011

I

MPORTANT

 

INFORMATION

 

REGARDING

 

THE

 

REFRIGERANT

 

USED

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

(1)

 GWP = global warming potential

The refrigerant quantity is indicated on the unit name plate.

C

HECKING

 

THE

 

WATER

 

CIRCUIT

The units are equipped with a water inlet and water outlet for
connection to a water circuit. This circuit must be provided by a
licensed technician and must comply with all relevant European and
national regulations.

Before continuing the installation of the unit, check the following
points:

Only for EWYQ*DAYN 
(without option OPSP, OPTP or OPHP)

A circulation pump must be provided in such a way that it
discharges the water directly into the water heat exchanger.

Provide adequate safeguards in the water circuit to make sure
that the water pressure will never exceed the maximum
allowable working pressure (10 bar).

Shut-off valves must be provided at the unit so that normal
servicing can be accomplished without draining the system.

For all models

Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance or in
case of shut down. A drain plug is provided to drain the water
from the chiller water system.

Air vents must be provided at all high points of the system. The
vents should be located at points which are easily accessible for
servicing. An automatic air purge is provided on the chiller water
system.

Take care that the components installed in the field piping can
withstand at least the sum of opening pressure of the safety
valve + the static height of the pump.

C

ONNECTING

 

THE

 

WATER

 

CIRCUIT

Water connections must be made in accordance with the outlook
diagram delivered with the unit, respecting the water in- and outlet.

If air, moisture or dust gets in the water circuit, problems may occur.
Therefore, always take into account the following when connecting
the water circuit:

1

Use clean pipes only.

2

Hold the pipe end downwards when removing burrs.

3

Cover the pipe end when inserting it through a wall so that no dust
and dirt enter.

W

ATER

 

CHARGE

FLOW

 

AND

 

QUALITY

For all models

To assure proper operation of the unit a minimum water volume is
required in the system and the water flow through the evaporator
must be within the operation range as specified in the table.

Cooling mode

Heating mode

Only for models with option OPSP, OPTP or OPHP

Maximum allowed installation height in function of the water 
volume

Make sure to respect following limitations:

If the EWYQ unit is installed at the highest point of the system, then
there is no height difference to be considered.

If the EWYQ unit is placed on a height level other than the highest
point, refer to the figure in 

"Charging water" on page 5

 to read the

maximum allowed height difference in function of the water volume.

e.g. for EWYQ080~210: If water volume=650 l, the maximum
allowed installation height difference is 9 m.

e.g. for 250: If water volume=650 l, the maximum
allowed installation height difference is 13 m.

Setting the pre-pressure of the expansion vessel

The pre-pressure (Pg) on the expansion vessel has to be set before
filling the system with water or water/glycol solution in function of the
maximum installation height difference (H).

Use dry compressed air or nitrogen for this operation.

The pre-pressure (Pg) to be set is calculated as below:

Pg= (H/10+0.3) bar

H= Maximum installation height of the circuit above the EWYQ unit (m)

Be careful not to deform the unit piping by using excessive
force when connecting the piping. Deformation of the
piping can cause the unit to malfunction.

Unit

Minimum 

water volume (l)

(*)

(*)

a = cooling temperature difference (refer to

"Defining the thermostat 

settings" on page 11

)

Minimum 

water flow

Maximum 

water flow

EWYQ080

690/a

110 l/min

441 l/min

EWYQ100

896/a

143 l/min

573 l/min

EWYQ130

609/a

195 l/min

780 l/min

EWYQ150

649/a

208 l/min

831 l/min

EWYQ180

820/a

262 l/min

1049 l/min

EWYQ210

945/a

302 l/min

1210 l/min

EWYQ230

1030/a

330 l/min

1319 l/min

EWYQ250

1120/a

358 l/min

1433 l/min

Unit

Minimum 

water volume (l)

(*)

(*)

a = heating temperature difference (refer to

"Defining the thermostat 

settings" on page 11

)

Minimum 

water flow

Maximum 

water flow

EWYQ080

786/a

126 l/min

503 l/min

EWYQ100

1021/a

163 l/min

654 l/min

EWYQ130

667/a

214 l/min

854 l/min

EWYQ150

739/a

237 l/min

946 l/min

EWYQ180

891/a

285 l/min

1141 l/min

EWYQ210

1008/a

323 l/min

1290 l/min

EWYQ230

1120/a

358 l/min

1433 l/min

EWYQ250

1232/a

394 l/min

1577 l/min

EWYQ

080~210

230+250

Volume expansion vessel

35 l

50 l

NOTE

For EWYQ080~210: If H

12 m and the water

volume 

520 l, we recommend not to change the

factory setting of the pre-pressure (= 1.5 bar)

For 250: If H

12 m and the water

volume 

750 l, we recommend not to change the

factory setting of the pre-pressure (= 1.5 bar)

Summary of Contents for EWYQ080DAYN

Page 1: ...INSTALLATION MANUAL EWYQ080DAYN EWYQ100DAYN EWYQ130DAYN EWYQ150DAYN EWYQ180DAYN EWYQ210DAYN EWYQ230DAYN EWYQ250DAYN Packaged air cooled water chillers...

Page 2: ...4P F13 230V 24V K4P M4P L2 L3 SLAVE 3 SLAVE 3 F14 F2 F3 N L1 F4 F15 230V 24V K3P M3P L2 L3 SLAVE 2 F16 F5 F6 N L1 F7 F17 230V 24V K2P M2P L2 L3 SLAVE 1 F18 F8 F9 N L1 F10 F19 230V 24V K1P M1P L2 L3 MA...

Page 3: ...ate cu Certificatul C conform celor stabilite n Dosarul tehnic de construc ie D i apreciate pozitiv de E Modul aplicat F n conformitate cu Certificatul G Categorie de risc H Consulta i de asemenea pag...

Page 4: ...stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin M...

Page 5: ...OP03 Condenser protection grills OPCG Inverter fans OPIF Low noise operation OPLN OPIF compressor housing Single pump OPSP High static pump OPHP Twin pump OPTP Heater tape s OP10 Glycol application f...

Page 6: ...either the discharged air nor the sound generated by the unit disturb anyone 7 Make sure that the air inlet and outlet of the unit are not positioned towards the main wind direction Frontal wind will...

Page 7: ...indicated The concrete foundation should approximately be 100 mm higher than the oor level for ease of plumbing work and better drain Make sure that the foundation surface is even and at 4 Remove the...

Page 8: ...ystem and the water ow through the evaporator must be within the operation range as speci ed in the table Cooling mode Heating mode Only for models with option OPSP OPTP or OPHP Maximum allowed instal...

Page 9: ...detectable corrosion Ammonium ion mg NH4 l 1 0 0 1 corrosion Remaining chloride mg Cl l 0 3 0 3 corrosion Free carbide mg CO2 l 4 0 4 0 corrosion Stability index corrosion scale The chillers are only...

Page 10: ...PTC K1S Overcurrent relay pump not for options OPSC OPTC OPSP OPTP and OPHP K2P Pump contactor only for options OPTP and OPTC M1P Pump motor 1 only for options OPSC OPTC OPSP OPTP and OPHP M2P Pump mo...

Page 11: ...ting of the eld wiring must be as indicated in the gures below In the cover plate some free space is provided to install the appropriate nipples drilling through the cover plate is required for single...

Page 12: ...of the cable 0 75 mm2 4 wire and maximum 500 m long Setting the addresses on the remote digital controller When a remote digital controller is used the address has to be set by means of DIP switches...

Page 13: ...ng The electrical main power supply must be arranged so that it can be switched on or off independently of the electrical supply to other items of the plant and equipment in general Refer to the wirin...

Page 14: ...it safety is active WARNING indicates that a warning is active C1 C2 OPERATION indicates that a compressor of that circuit is switched on 0 CAPACITY indicates that no compressors are switched on COOLI...

Page 15: ...cannot modify them De ning the thermostat settings For a stand alone unit Enter the rst screen of the THERMOSTAT submenu through the service menu De ning the thermostat settings for inlet or outlet wa...

Page 16: ...S1S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master unit M are switched ON or OFF using the remote start stop switch S1S M which is connected to the master unit The setpoint can be...