background image

EWYQ080~250DAYN
Packaged air-cooled water chillers
4PW35559-1D – 03.2011

Installation manual

9

B

EFORE

 

STARTING

I do confirm having executed and checked all the above
mentioned items.

Keep for future reference

.

C

USTOMIZATION

 

IN

 

THE

 

SERVICE

 

MENU

To change a setting in the service menu:

1

Enter the usersettings menu (

Å

) as indicated in the operation

manual and press the 

Ì

 key to select the service menu, then

press the 

 key (this is only possible if the unit is off).

2

Enter the correct password using the 

 and 

Ì

 keys. The

password can be found in the service manual.

3

Press 

 to confirm the password and enter the service menu.

4

Go to the screen which contains the parameter to be modified by
using the 

 and 

Ì

 keys.

5

Position the cursor behind the parameter to be modified using
the 

 key.

6

Select the appropriate setting using the 

 and 

Ì

 keys.

7

Press 

 to confirm the modification. When the modification has

been confirmed, the cursor switches to the next parameter which
can now be configured.

8

Place the cursor in the top left corner of the screen when you are
finished changing the parameters on this screen.

9

Repeat from instruction 4 onwards to modify other parameters.

Settings for units with glycol application (OPZL)

It is possible to change the minimum outlet water temperature
(

MIN.OUTL.WATER

) in the service menu, submenu safety.

Before lowering the minimum outlet water temperature:

Make sure that sufficient glycol is added to the water system
according to the table.

Make sure that the settings are according to the table.

Settings as above result in cooling inlet and cooling outlet lower
limits as shown in the table below.

The unit may not be started, not even for a very short
period of time, before the following pre-commissioning
checklist is filled out completely.

tick 

 

when 

checked

standard steps to go through before starting the unit

1

Check for 

external damage

.

2

Open all 

shut-off valves

 indicated by a red label: "OPEN THIS 

VALVE BEFORE OPERATION". (Open the liquid line, discharge 
and suction stop valves (if provided (OP12)) completely.)

3

Install 

main fuses, earth leak detector

.

Recommended fuses: gL/gG according to IEC standard 269-2.

Refer to the wiring diagram for size

.

4

Supply the main voltage and check if it is within the allowable 
±10% limits of the nameplate rating.

The electrical main 

power supply

 must be arranged so, that it 

can be switched on or off independently of the electrical supply 
to other items of the plant and equipment in general.

Refer to the wiring diagram, terminals L1, L2, L3 and PE

.

5

Check if all 

field wiring

 is correctly installed.

6

Supply water to the evaporator and verify if 

water flow

 is within 

the limits as given in the table under 

"Water charge, flow and 

quality" on page 4

.

7

The piping must be completely 

purged

8

Connect the 

pump contact

, so that the unit can only come in 

operation when the water pumps are running and the water flow 
is sufficient.

For DICN configurations, every chiller shall have its own flow 
switch and shall be interlocked with the pump from which it gets 
the flow.

9

Check the 

oil level

 in the compressors.

10

Connect the power supply to the 

heater tape terminals 

(factory mounted OP10)

.

The heater tape must be connected to an independent, 
separately fused, power supply all year-round.

11

Check that all the 

water sensors

 are correctly fixed into the 

connection pipes of the heat exchanger.

12

Check if after the power supply has been switched on, all 

changeable inputs and outputs

 are correctly configured.

Note the correct configuration for each of the following 
changeable inputs and outputs:

• DI1 .....................................

• DI2 .....................................

• DI3 .....................................

• DI4 .....................................

• DO1 .....................................

• DO2 .....................................

• DO3 .....................................

• DO4 .....................................

• DO5 .....................................

• DO6 .....................................

• AI1 .....................................

• AI2 .....................................

• AI3 .....................................

• AI4 .....................................

• AO1 .....................................

NOTE

It is necessary to read the operation manual
delivered with the unit before operating the unit. It
will contribute to understand the operation of the
unit and its electronic controller.

Close all switchbox doors after installation of the
unit.

Date

Sign

All customized settings must be done by a licensed
technician.

LWE

(*)

(*)

LWE = Leaving water evaporator

°C –10~–5

–5~0

0~2

2~5

5~20

Ethylene glycol

%

40

30

20

10

0

Propylene glycol

%

40

35

25

15

0

MIN.OUTL.WATER

Minimum outlet water

–10

–5

0

2

5

FREEZE UP DIS

Freeze-up disable 
temperature setting

–11

–6

–1

1

4

RESET

Freeze-up disable 
temperature reset

–10

–5

0

2

5

REFR TEMP SET

Refrigerant gas 
temperature setting

–18.5

–13.5

–8.5

–6.5

–3.5

LP SETP. C:

Low pressure setpoint 
in cooling mode

0.5

0.5

0.5

1.2

1.2

PUMP ON SETP

Pump on temperature 
setting

(**)

(**) No heater tape is present

–21.5

–14.5

–7.5

–2.5

1.5

LWE

(*)

(*)

LWE = Leaving water evaporator

°C –10~–5

–5~0

0~2

2~5

5~20

Ethylene glycol

%

40

30

20

10

0

Propylene glycol

%

40

35

25

15

0

COOL. INLSP1

/

2

Lower limit of cooling 
inlet

–7

–2

3

5

8

COOL. OUTSP1

/

2

Lower limit of cooling 
outlet

–10

–5

0

2

5

Improper setting can result in severe damage of the
equipment.

Summary of Contents for EWYQ080DAYN

Page 1: ...INSTALLATION MANUAL EWYQ080DAYN EWYQ100DAYN EWYQ130DAYN EWYQ150DAYN EWYQ180DAYN EWYQ210DAYN EWYQ230DAYN EWYQ250DAYN Packaged air cooled water chillers...

Page 2: ...4P F13 230V 24V K4P M4P L2 L3 SLAVE 3 SLAVE 3 F14 F2 F3 N L1 F4 F15 230V 24V K3P M3P L2 L3 SLAVE 2 F16 F5 F6 N L1 F7 F17 230V 24V K2P M2P L2 L3 SLAVE 1 F18 F8 F9 N L1 F10 F19 230V 24V K1P M1P L2 L3 MA...

Page 3: ...ate cu Certificatul C conform celor stabilite n Dosarul tehnic de construc ie D i apreciate pozitiv de E Modul aplicat F n conformitate cu Certificatul G Categorie de risc H Consulta i de asemenea pag...

Page 4: ...stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin M...

Page 5: ...OP03 Condenser protection grills OPCG Inverter fans OPIF Low noise operation OPLN OPIF compressor housing Single pump OPSP High static pump OPHP Twin pump OPTP Heater tape s OP10 Glycol application f...

Page 6: ...either the discharged air nor the sound generated by the unit disturb anyone 7 Make sure that the air inlet and outlet of the unit are not positioned towards the main wind direction Frontal wind will...

Page 7: ...indicated The concrete foundation should approximately be 100 mm higher than the oor level for ease of plumbing work and better drain Make sure that the foundation surface is even and at 4 Remove the...

Page 8: ...ystem and the water ow through the evaporator must be within the operation range as speci ed in the table Cooling mode Heating mode Only for models with option OPSP OPTP or OPHP Maximum allowed instal...

Page 9: ...detectable corrosion Ammonium ion mg NH4 l 1 0 0 1 corrosion Remaining chloride mg Cl l 0 3 0 3 corrosion Free carbide mg CO2 l 4 0 4 0 corrosion Stability index corrosion scale The chillers are only...

Page 10: ...PTC K1S Overcurrent relay pump not for options OPSC OPTC OPSP OPTP and OPHP K2P Pump contactor only for options OPTP and OPTC M1P Pump motor 1 only for options OPSC OPTC OPSP OPTP and OPHP M2P Pump mo...

Page 11: ...ting of the eld wiring must be as indicated in the gures below In the cover plate some free space is provided to install the appropriate nipples drilling through the cover plate is required for single...

Page 12: ...of the cable 0 75 mm2 4 wire and maximum 500 m long Setting the addresses on the remote digital controller When a remote digital controller is used the address has to be set by means of DIP switches...

Page 13: ...ng The electrical main power supply must be arranged so that it can be switched on or off independently of the electrical supply to other items of the plant and equipment in general Refer to the wirin...

Page 14: ...it safety is active WARNING indicates that a warning is active C1 C2 OPERATION indicates that a compressor of that circuit is switched on 0 CAPACITY indicates that no compressors are switched on COOLI...

Page 15: ...cannot modify them De ning the thermostat settings For a stand alone unit Enter the rst screen of the THERMOSTAT submenu through the service menu De ning the thermostat settings for inlet or outlet wa...

Page 16: ...S1S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master unit M are switched ON or OFF using the remote start stop switch S1S M which is connected to the master unit The setpoint can be...

Page 17: ...t slave 3 S3 is kept as a standby unit Setup The system is controlled on entering water temperature The pumps of the slave units only run when their compressor is running energy saving After stopping...

Page 18: ...Installation manual 14 EWYQ080 250DAYN Packaged air cooled water chillers 4PW35559 1D 03 2011 NOTES...

Page 19: ...r circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emerge...

Page 20: ...4PW35559 1D 03 2011 Copyright 2007 Daikin...

Reviews: