EWYQ080~250DAYN
Packaged air-cooled water chillers
4PW35559-1D – 03.2011

Installation manual

7

Power circuit and cable requirements

1

The electrical power supply to the unit must be arranged so that
it can be switched on or off independently of the electrical supply
to other items of the plant and equipment in general.

2

A power circuit must be provided for connection of the unit. This
circuit must be protected with the required safety devices, i.e. a
circuit breaker, a slow blow fuse on each phase and an earth
leak detector (high speed type 100 mA rated). Recommended
fuses are mentioned on the wiring diagram supplied with the
unit. For a system with chillers in a DICN configuration, be sure
to provide a separate power circuit for every chiller.

Connection of the air-cooled water chiller power supply

1

Using the appropriate cable, connect the power circuit to the L1,
L2 and L3 terminals of the unit.

The power circuit must be connected to the terminals 2, 4 and 6
of the main isolator switch.

2

Connect the earth conductor (yellow/green) to the earthing
terminal .

Interconnection cables

Only for models without option OPSP, OPTP, OPHP, OPSC
or OPTC

Voltage free contacts (for all models)

The controller is provided with voltage free contacts to indicate
the status of the unit. These voltage free contacts can be wired
as described on the wiring diagram.

Remote inputs (for all models)

Besides the voltage free contacts, there are also possibilities to
install remote inputs. They can be installed as shown on the
wiring diagram.
For units in DICN configuration, note the following:

Switch for remote on/off:

Units with status 

NORMAL

 or 

STANDBY

 will be controlled

by the remote on/off switch connected to the chiller defined
as 

MASTER

.

Units with status 

DISCONNECT ON/OFF 

are controlled

by the switch connected to them.
See also operation manual: "Selecting local or remote on/off
control".

Remote dual setpoint switch:

The remote dual setpoint switch may only be connected to
the chiller defined as 

MASTER

.

However in case the master drops out because of e.g. a
power supply failure, it might be interesting to have the dual
temperature switch installed to the other units as well.

Connecting field wiring

The routing of the field wiring must be as indicated in the figures
below.

In the cover plate some free space is provided to install the
appropriate nipples (drilling through the cover plate is required),

-

for single circuit units: located below the field wiring 
terminals,

-

for double circuit units: located below the mainswitch.

Strap the wiring with a clamp (field supply) to the attachment plugs
(1) as shown in the figures below to ensure strain relief of the wiring.

Power supply of factory mounted heater tape (option OP10)
and additional heater tapes.

An independent power supply 1~50 

Hz, 230 

V must be

connected to the terminals as indicated on the wiring diagram
supplied with the unit. The heater tapes must be connected to
the independent power supply year-round. Separate fuses and a
heater tape isolator switch must be installed in the field. Connect
the earth conductor (yellow/green) to the earthing terminal 

.

(Refer to the wiring diagram supplied with the unit.)
Use a power supply cable containing 2 conductors and ground
with a cable section in function of:

maximum current of 10 A,

maximum ambient temperature of 60°C inside the switchbox.

Switch off the main isolator switch before making any
connections (switch off the circuit breaker, remove or
switch off the fuses).

A pump interlock contact must be installed to prevent
the unit from operating without water flow. A terminal
is provided in the switchbox for the electrical
connection of the interlock contact.
For units in a DICN configuration, every chiller can
either have an individual circulation pump or 1 pump
can discharge water in a distributor that leads water to
several chillers.
In both cases, all units must be equipped with an
interlock contact!

NOTE

Normally the unit will not operate if there is no flow
thanks to the standard installed flow switch.
But as to have a double safety, you 

must

 install

the pump interlock contact.
Operating the unit without flow will result in very
severe damage to the unit (freezing of the
evaporator).

NOTE

In case mechanical stress occurs on the wiring, the
earthing connections may not become loose before
current-carrying connections do. Therefore make the
earthing conductors longer than the current-carrying
conductors.

Connection of field wiring to terminals

Pay special attention to markings on the terminals. The
illustration below indicates corresponding positions to feed
field wiring through correctly.

Single circuit unit

1

Summary of Contents for EWYQ080DAYN

Page 1: ...INSTALLATION MANUAL EWYQ080DAYN EWYQ100DAYN EWYQ130DAYN EWYQ150DAYN EWYQ180DAYN EWYQ210DAYN EWYQ230DAYN EWYQ250DAYN Packaged air cooled water chillers...

Page 2: ...4P F13 230V 24V K4P M4P L2 L3 SLAVE 3 SLAVE 3 F14 F2 F3 N L1 F4 F15 230V 24V K3P M3P L2 L3 SLAVE 2 F16 F5 F6 N L1 F7 F17 230V 24V K2P M2P L2 L3 SLAVE 1 F18 F8 F9 N L1 F10 F19 230V 24V K1P M1P L2 L3 MA...

Page 3: ...ate cu Certificatul C conform celor stabilite n Dosarul tehnic de construc ie D i apreciate pozitiv de E Modul aplicat F n conformitate cu Certificatul G Categorie de risc H Consulta i de asemenea pag...

Page 4: ...stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin M...

Page 5: ...OP03 Condenser protection grills OPCG Inverter fans OPIF Low noise operation OPLN OPIF compressor housing Single pump OPSP High static pump OPHP Twin pump OPTP Heater tape s OP10 Glycol application f...

Page 6: ...either the discharged air nor the sound generated by the unit disturb anyone 7 Make sure that the air inlet and outlet of the unit are not positioned towards the main wind direction Frontal wind will...

Page 7: ...indicated The concrete foundation should approximately be 100 mm higher than the oor level for ease of plumbing work and better drain Make sure that the foundation surface is even and at 4 Remove the...

Page 8: ...ystem and the water ow through the evaporator must be within the operation range as speci ed in the table Cooling mode Heating mode Only for models with option OPSP OPTP or OPHP Maximum allowed instal...

Page 9: ...detectable corrosion Ammonium ion mg NH4 l 1 0 0 1 corrosion Remaining chloride mg Cl l 0 3 0 3 corrosion Free carbide mg CO2 l 4 0 4 0 corrosion Stability index corrosion scale The chillers are only...

Page 10: ...PTC K1S Overcurrent relay pump not for options OPSC OPTC OPSP OPTP and OPHP K2P Pump contactor only for options OPTP and OPTC M1P Pump motor 1 only for options OPSC OPTC OPSP OPTP and OPHP M2P Pump mo...

Page 11: ...ting of the eld wiring must be as indicated in the gures below In the cover plate some free space is provided to install the appropriate nipples drilling through the cover plate is required for single...

Page 12: ...of the cable 0 75 mm2 4 wire and maximum 500 m long Setting the addresses on the remote digital controller When a remote digital controller is used the address has to be set by means of DIP switches...

Page 13: ...ng The electrical main power supply must be arranged so that it can be switched on or off independently of the electrical supply to other items of the plant and equipment in general Refer to the wirin...

Page 14: ...it safety is active WARNING indicates that a warning is active C1 C2 OPERATION indicates that a compressor of that circuit is switched on 0 CAPACITY indicates that no compressors are switched on COOLI...

Page 15: ...cannot modify them De ning the thermostat settings For a stand alone unit Enter the rst screen of the THERMOSTAT submenu through the service menu De ning the thermostat settings for inlet or outlet wa...

Page 16: ...S1S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master unit M are switched ON or OFF using the remote start stop switch S1S M which is connected to the master unit The setpoint can be...